Troubleshooting Using Indicators

 

 

 

 

Section 9-1

 

 

 

 

 

 

 

 

 

Indicators

 

Probable cause

Probable remedy

 

 

 

 

 

 

 

 

RUN

ERC

ERH

INS

 

 

 

 

 

 

 

 

 

 

Lit

---

---

Not lit

Terminating resistance is

Turn ON the terminating

 

 

 

 

 

not set correctly.

resistance at the nodes at

 

 

 

 

 

 

both ends of the Network

 

 

 

 

 

 

and turn it OFF at all other

 

 

 

 

 

 

nodes.

 

 

 

 

 

 

 

 

 

 

 

 

Cables are not connected

Check the cable connec-

 

 

 

 

 

correctly.

tions and reconnect cor-

 

 

 

 

 

 

rectly.

 

 

 

 

 

 

 

 

 

 

 

 

The node address is larger

Either reset the maximum

 

 

 

 

 

than the maximum node

node address using the

 

 

 

 

 

address set for the network

Controller Link Support

 

 

 

 

 

parameters.

Software or reset the node

 

 

 

 

 

 

address to below the maxi-

 

 

 

 

 

 

mum.

 

 

 

 

 

 

 

 

 

 

 

 

No other nodes exist.

Ensure that 2 or more

 

 

 

 

 

 

nodes exist within the Net-

 

 

 

 

 

 

work.

 

 

 

 

 

 

 

 

 

 

 

 

No nodes have been set as

Refer to 8-1-2 Setting the

 

 

 

 

 

polling nodes.

Polling and Polled Nodes

 

 

 

 

 

 

and set at least one polling

 

 

 

 

 

 

node. (Controller Link

 

 

 

 

 

 

Units should normally be

 

 

 

 

 

 

set as polling nodes.)

 

 

 

 

 

 

 

 

 

 

 

 

The same operating level

Reset so that each operat-

 

 

 

 

 

is set more than once for

ing level is used only once.

 

 

 

 

 

the same PLC.

 

 

 

 

 

 

 

 

 

 

 

 

 

The Bus Connection Unit

Tighten the mounting

 

 

 

 

 

has become loose.

screws on the Bus Con-

 

 

 

 

 

 

nection Unit (C200HX/HG/

 

 

 

 

 

 

HE PLCs only).

 

 

 

 

 

 

 

 

 

 

 

 

The set baud rate is differ-

Refer to SECTION 4 Prep-

 

 

 

 

 

ent to other nodes.

arations for Communica-

 

 

 

 

 

 

tions and set all nodes on

 

 

 

 

 

 

the network to the same

 

 

 

 

 

 

baud rate.

 

 

 

 

 

 

 

Troubleshooting with LNK and M/A Indicators

 

Data Link Cannot be

The following table describes the LNK and M/A indicators at the startup node

Started

and their use in troubleshooting when a data link cannot be started.

Starting a data link depends on the Controller Link Unit operating normally and participating in the Network. Refer to Troubleshooting with RUN, ERC, ERH and INS Indicators earlier in this section and check Unit operation before using the following table.