Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01 CIO Area CPU Bus Unit Area, CPU Bus Unit Numbers

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 381
Image 381

Memory Areas

Appendix B

CPU Bus Unit Numbers

Bits A41000 through A41015 correspond to CPU Bus Units #0 through #15, respectively. When two CPU Bus Units have the same unit number, the bits corresponding to the unit numbers of the CPU Bus Units involved are turned ON.

Network Status Flags

Bits A50200 through A50207 are turned ON to indicate that ports #0 through #7, respectively, are enabled for the SEND(192), RECV(193), and CMND(194). Bits A50208 through A50215 are turned ON to indicate that an error has occurred in ports #0 through #7, respectively, during data communications using SEND(192), RECV(193), or CMND(194).

A503 through A510 contain the completion codes for ports #0 through #7, respectively, following data commu- nications using SEND(192), RECV(193), or CMND(194).

CIO Area: CPU Bus Unit Area

The CPU Bus Unit Area is allocated to CPU Bus Units according to the unit numbers assigned to them, as shown below. Each Unit is allocated 25 words. The Controller Link Units use 22 of the words allocated to them.

Unit no.

Words

 

Unit no.

Words

 

 

 

 

 

0

1500 to 1524

8

 

1700 to 1724

 

 

 

 

 

1

1525 to 1549

9

 

1725 to 1749

 

 

 

 

 

2

1550 to 1574

10

 

1750 to 1774

 

 

 

 

 

3

1575 to 1599

11

 

1775 to 1799

 

 

 

 

 

4

1600 to 1624

12

 

1800 to 1824

 

 

 

 

 

5

1625 to 1649

13

 

1825 to 1849

 

 

 

 

 

6

1650 to 1674

14

 

1850 to 1874

 

 

 

 

 

7

1675 to 1699

15

 

1875 to 1899

 

 

 

 

 

Error Information: CIO 1500 + 25 (Unit No.) (See page 304.)

1: Network parameter error (In PLC's EEPROM)

1: Data link table error (in PLC's EEPROM)

1: Routing table error (in PLC's EEPROM)

1: PLC system setting error

1: EEPROM error

1: Duplicate node address setting error

1: Inconsistent network parameters

1: Communications controller send error

1: Error log exists

Polling Node Address, Startup Node Address: CIO 1500 + 25 (Unit No.) + 1 (See page 304.)

Polling node address

Startup node address

Each node address is displayed in 2-digit BCD.

Network Participation Status: CIO 1500 + 25 (Unit No.) + 2, + 3 (See pages 190, 304.)

+2

+3

The numbers in the squares indicate node addresses.

The corresponding node participation status is as follows:

0:Not part of the network

1:Part of the network

358

Page 381
Image 381