Setting Data Links

 

 

Section 5-2

 

 

 

 

 

 

Setting item

 

Setting range

 

 

 

 

First data link sta-

Set the first word to store data link status. An area of 16 words is

 

tus word

 

used.

 

 

 

 

 

IR Area:

IR 001 to IR 232

 

 

 

 

LR Area: LR 00 to LR 48

 

 

 

 

DM Area: DM 0000 to DM 5984

 

 

 

 

EM Area: EM 0000 to EM 6128 (EM must be installed)

 

 

 

 

When IR 000 is specified or when the default setting (–––––) is

 

 

 

 

left unchanged, the default first status word will be used. Refer

 

 

 

 

to 5-4 Checking Data Link Status for details.

 

 

 

 

 

 

Area 1

 

Data link

IR Area:

IR 000 to IR 247

 

 

 

start word

LR Area: LR 00 to LR 63

 

 

 

 

 

 

 

 

DM Area: DM 0000 to DM 5999

 

 

 

 

EM Area: EM 0000 to EM 6143 (EM must be installed)

 

 

 

 

The same memory area cannot be set for both area 1 and area

 

 

 

 

2. Set different memory areas.

 

 

 

 

 

 

 

 

Number of

Remote nodes: 0 to the number of source words

 

 

 

words

 

Set the number of words to be received.

 

 

 

 

Local node:

0 to 1,000

 

 

 

 

 

Set the number of words to be transmitted.

 

 

 

 

The total number of words in area 1 and area 2 in each node

 

 

 

 

must not exceed 1,000.

 

 

 

 

The numbers of words in both area 1 and area 2 in each node

 

 

 

 

must not be set to 0.

 

 

 

 

 

 

 

 

Offset

Remote nodes: 0 to one less than number of source words

 

 

 

 

 

Set the offset for the data to be received.

 

 

 

 

Local node:

Cannot be set.

 

 

 

 

This setting is not required if an offset is not used.

 

 

 

 

 

 

 

Area 2

 

Data link

IR Area:

IR 000 to IR 247

 

 

 

start word

LR Area: LR 00 to LR 63

 

 

 

 

 

 

 

 

DM Area: DM 0000 to DM 5999

 

 

 

 

EM Area: EM 0000 to EM 6143 (EM must be installed)

 

 

 

 

The same memory area cannot be set for both area 1 and area

 

 

 

 

2. Set different memory areas.

 

 

 

 

 

 

 

 

Number of

Remote nodes: 0 to the number of source words

 

 

 

words

 

Set the number of words to be received.

 

 

 

 

Local node:

0 to 1,000

 

 

 

 

 

Set the number of words to be transmitted.

 

 

 

 

The total number of words in area 1 and area 2 in each node

 

 

 

 

must not exceed 1,000.

 

 

 

 

The numbers of words in both area 1 and area 2 in each node

 

 

 

 

must not be set to 0.

 

 

 

 

 

 

 

 

Offset

Remote nodes: 0 to one less than number of source words

 

 

 

 

 

Set the offset for the data to be received.

 

 

 

 

Local node:

Cannot be set.

 

 

 

 

This setting is not required if an offset is not used.

 

 

 

 

 

 

Note a) The total number of words in data link send and receive areas must not exceed 8,000 per node.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.