Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 Polling Node Address, Startup Node Address SR 238, SR

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 323
Image 323

Status Area and Troubleshooting

 

Section 9-2

Polling Node Address, Startup Node Address: SR 238, SR 242

 

Operating level 0

Operating level 1

 

SR 238

SR 242

 

 

Polling node address

Startup node address

 

Each node address is displayed in 2-digit BCD.

Data Link Status: SR 239 to SR 241, SR 243 to SR 245

Operating

Operating

 

 

level 0

level 1

 

 

SR 239

SR 243

Node

2

SR 240

SR 244

Node

4

SR 241

SR 245

Node

6

When the data link status stored in the start word for the manual setting data link table or automatic setting data link parameters is not set or is set to 0, the data link status of only node addresses 1 to 6 will be displayed in the following area.

Node 1

Node 3

Node 5

PLC status

0: Inactive (user program not running)

1: Active (user program running)

PLC's CPU Unit error 0: Normal

1: Error

Communications error (data link reception) 0: Normal

1: Error

Data link participation

0:Not in data link or data link inactive

1:In data link

 

 

 

Offset error

Error: Offset exceeds

 

 

 

 

 

 

0: Normal

number of send words.

 

 

 

1: Error

 

 

Insufficient (short) receive area Insufficient: Receive

 

 

0: Sufficient

area is smaller than

 

1: Insufficient

send area. Excess data

 

 

 

 

is truncated; other data

 

 

 

 

is received.

Remaining receive area

Remaining: Receive area

0:

 

Not remaining

is larger than send area.

1:

 

Remaining

Data is received and

 

 

 

 

remaining words are

 

 

 

 

cleared.

Operating Level Status: SR 252

1: Local node data link participating

SEND/RECV Enable Flag 0: Disabled (operating)

1: Enabled (not operating)

Operating level 1

 

 

 

 

SEND/RECV Error Flag

 

 

 

 

 

 

0: Normal completion

 

 

 

1: Error

 

 

 

 

 

 

 

1: Local node data link participating

 

 

 

 

 

 

SEND/RECV Enable Flag

Operating level 0

0: Disabled (operating)

 

 

1: Enabled (not operating)

 

 

 

 

 

 

 

 

 

SEND/RECV Error Flag

 

0: Normal completion

 

 

1: Error

 

Note Data link status is valid only when the local node is participating in the data link. Confirm that the local node’s data links are active in the operating level status in SR 252 before referencing the data link status.

300

Page 323
Image 323
Omron CS1W-CLK21-V1 Polling Node Address, Startup Node Address SR 238, SR, Data Link Status SR 239 to SR 241, SR 243 to SR