Omron CS1W-CLK21-V1, CVM1-CLK21 Checking Data Link Status, LED Indicators, Data Link Status Area

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 179
Image 179

Checking Data Link Status

Section 5-4

Issuing the FINS Command from CVM1, CV-series, CS/CJ-series, and CQM1H-series PLCs

CVM1, CV, CS/CJ, or CQM1H

FINS command:

RUN/STOP

Node in data links

Data links can be stopped by sending the FINS command “STOP.” The node to which the FINS command is issued must be participating in the data link.

5-4 Checking Data Link Status

There are two methods for checking the status of active data links:

Check the LED indicators on the front of the Units.

Check the data link status area.

5-4-1 LED Indicators

Check the LINK and M/A indicators on the front of the unit.

CS-series PLCs

CJ-series PLCs

C200HX/HG/HE PLCs CVM1 and CV-series PLCs CQM1H-series PLCs

 

 

 

 

 

 

 

 

 

 

 

 

CLK21-V1

CLK21-V1

INS

SD

 

 

CLK21

 

 

 

CLK21

 

 

 

 

 

 

 

 

RUN ERC

 

 

 

 

 

 

 

 

 

TER ERH M/A

LNK

RD

 

 

 

 

 

 

RUN

TER

 

 

 

 

 

 

 

ERC

ERH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN

TER

 

INS

M/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD RD

LNK

 

 

 

 

 

 

ERC

ERH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/A

 

 

 

 

 

 

 

 

 

INS

LNK

 

 

 

 

 

 

 

 

 

SD

RD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make sure that the LNK indicator is ON at nodes participating in the active data links.

Name

Color

Status

 

Contents

 

 

 

 

LNK

Yellow

ON

Participating in data links.

(data link)

 

 

 

 

 

Flashing

Data link table setting error

 

 

 

 

 

 

 

 

OFF

Not in data links or data links are inactive.

 

 

 

 

 

M/A

Yellow

ON

Manual

Note: This indicator will

(data link

 

 

 

always be OFF when the

 

OFF

Automatic

mode)

 

data links are not active.

 

 

 

The LNK indicator will be lit at all node participating in the data links as long as operation is normal. The data link mode (manual/automatic) can be checked using the M/A indicator. See 9-1 Troubleshooting Using Indicators for details.

5-4-2 Data Link Status Area

The data link status area can be used to check for errors when data link does not operate normally even though no abnormality has been detected by the PLC’s CPU Unit or the Controller Link Unit. The data link status area contains the data link status information shown below.

The number of words used for data link status and the information that is reflected depends on the setting (8-bit or 4-bit format) for the data link status storage format specification in the DM Parameters Area, as shown in the fol- lowing diagram.

See 9-2 Status Area and Troubleshooting for troubleshooting procedures and see Data Link Status Storage Format (CS/CJ Series Only) for details on set-

ting the data link status storage format in the DM Parameters Area when using CS- and CJ-series PLCs.

156

Page 179
Image 179
Omron CS1W-CLK21-V1 Checking Data Link Status, LED Indicators, Data Link Status Area, Name Color Status Contents