Using the Message Service

 

 

Section 6-3

C200HX/HG/HE and

The results of executing SEND and RECV instructions are reflected as shown

CQM1H-series PLC

in the following table.

 

Response Codes

 

 

 

Code

Contents

Meaning

 

 

 

 

 

 

00 (Hex)

Normal end

Data transfer was completed successfully.

 

 

 

 

 

01 (Hex)

Parameter error

SEND/RECV instruction operands are not

 

 

 

within specified ranges.

 

 

 

 

 

02 (Hex)

Transmission impossible

The source node is not in the network or

 

 

 

the Unit was reset during execution of the

 

 

 

instruction.

 

 

 

 

 

03 (Hex)

Destination node error

The destination node is not in the network.

 

 

 

 

 

04 (Hex)

Destination node busy

The destination node is busy and cannot

 

 

error

receive the command.

 

 

 

 

 

05 (Hex)

Response timeout

A response was not received within the

 

 

 

time limit.

 

 

 

 

 

06 (Hex)

Response error

The response received from the destina-

 

 

 

tion node was incorrect.

 

 

 

 

 

07 (Hex)

Communications control-

An error occurred in the communications

 

 

ler error

controller.

 

 

 

 

 

08 (Hex)

Setting error

The destination node address was set

 

 

 

incorrectly.

 

 

 

 

 

09 (Hex)

CPU Unit error

A CPU Unit error occurred in the PLC of

 

 

 

the destination node.

 

 

 

 

 

10 (Hex)

Routing error

Command could not be sent because of

 

 

 

incorrect routing.

 

 

 

 

 

11 (Hex)

Relay error

Command did not reach the destination

 

 

 

node because of an error at the relay sta-

 

 

 

tion.

 

 

 

 

 

12 (Hex)

Source node busy error

The source node is busy and cannot send

 

 

 

the command.

CS/CJ-series, CVM1, and

The results of executing SEND, RECV, and CMND instructions are reflected

CV-series Response

as one word (two bytes) of data. Instruction response codes are the same as

Codes

FINS command response codes. Response code bits 08 to 15 correspond to

 

the first byte of the response code, and response code bits 00 to 07 corre-

spond to the second byte of the response code. For details, refer to 6-7 Response Codes.