Troubleshooting Using Indicators

 

 

 

 

Section 9-1

 

 

 

 

 

 

 

 

 

Indicators

 

Probable cause

Probable remedy

 

 

 

 

 

 

 

 

RUN

ERC

ERH

INS

 

 

 

 

 

 

 

 

 

 

Not lit

Not lit

Not lit

Not lit

Power is not being sup-

Check the power supply

 

 

 

 

 

plied correctly to the PLC.

voltage and supply at the

 

 

 

 

 

 

recommended voltage.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit

Secure the Controller Link

 

 

 

 

 

has become loose.

Unit firmly.

 

 

 

 

 

 

 

 

 

 

 

 

The Bus Connection Unit

Tighten the mounting

 

 

 

 

 

has become loose.

screws on the Bus Con-

 

 

 

 

 

 

nection Unit.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit is

Refer to C200HX/HG/HE

 

 

 

 

 

mounted in the wrong slot.

PLCs and CJ-series PLCs

 

 

 

 

 

 

and mount the Unit cor-

 

 

 

 

 

 

rectly.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit is

If the indicators do not light

 

 

 

 

 

faulty.

when the Unit is mounted

 

 

 

 

 

 

on another PLC, replace

 

 

 

 

 

 

the Controller Link Unit.

 

 

 

 

 

 

 

 

Lit

Lit

---

Not lit

The node address is out-

Reset the node address to

 

 

 

 

 

side the setting range.

within the 1 to 32 range.

 

 

 

 

 

 

 

 

 

 

 

 

The same node address is

Reset so that each node

 

 

 

 

 

being used by two different

address is used only once

 

 

 

 

 

Units.

within the same Network.

 

 

 

 

 

 

 

 

Lit

---

Lit

---

Routing table setting error

Remake and set the rout-

 

 

 

 

 

or a Routing Table Enable

ing table correctly, referring

 

 

 

 

 

Bit setting error.

to 7-4 Setting Routing

 

 

 

 

 

 

Tables. When no routing

 

 

 

 

 

 

table is being used, turn

 

 

 

 

 

 

OFF the Routing Table

 

 

 

 

 

 

Enable Bit.

 

 

 

 

 

 

 

 

 

 

 

 

The Unit is mounted to a

Refer to 1-2-4 Controller

 

 

 

 

 

non-compatible PLC.

Link Unit Models and PLCs

 

 

 

 

 

 

and reinstall the Unit on

 

 

 

 

 

 

the appropriate PLC.

 

 

 

 

 

 

 

 

 

 

 

 

An error has occurred in

Refer to the PLC’s opera-

 

 

 

 

 

the PLC.

tion manual and correct

 

 

 

 

 

 

the error. If the error occurs

 

 

 

 

 

 

again, replace the PLC.

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error

Refer to 9-2 Status Area

 

 

 

 

 

 

and Troubleshooting, cor-

 

 

 

 

 

 

rect the data where the

 

 

 

 

 

 

error has occurred, and

 

 

 

 

 

 

reset the Unit. If the error

 

 

 

 

 

 

occurs again, replace the

 

 

 

 

 

 

Controller Link Unit.

 

 

 

 

 

 

 