Memory Areas

Appendix B

Routing Tables (DM 6450 to DM 6499) (See page 243.)

When the use of routing tables is enabled by the software switch setting, the routing tables are stored in these words. Do not use them for anything else.

CVM1 and CV-series PLCs

Auxiliary Area

Word(s)

Bit(s)

Function

 

 

 

A001

00 to 15

CPU Bus Unit Restart Bits

 

 

 

A015

00 to 15

CPU Bus Service Disable Bits

 

 

 

A302

00 to 15

CPU Bus Unit Initializing Flags

 

 

 

A401

12

CPU Bus Error Flag

 

 

 

A402

03

CPU Bus Unit Setting Error Flag

 

 

 

 

07

CPU Bus Unit Error Flag

 

 

 

A405

00 to 15

CPU Bus Unit Error Unit Number

 

 

 

A410

00 to 15

CPU Bus Unit Duplicate Number

 

 

 

A422

00 to 15

CPU Bus Unit Error Unit Number

 

 

 

A427

00 to 15

CPU Bus Unit Setting Error Unit Number

 

 

 

A502

00 to 07

Port #0 to #7 Enabled Flags

 

 

 

 

08 to 15

Port #0 to #7 Execute Error Flags

 

 

 

A503 to A510

00 to 15

Port #0 to #7 Completion Codes (See page 191)

 

 

 

CPU Bus Unit Restart Bits

Bits A00100 through A00115 can be turned ON to reset CPU Bus Units number #0 through #15, respectively. The Restart Bits are turned OFF automatically when restarting is completed.

Do not turn these bits ON and OFF in the program; manipulate them from the CVSS.

CPU Bus Service Disable Bits

Bits A01500 through A01515 can be turned ON to stop service to CPU Bus Units numbered #0 through #15, respectively. Turn the appropriate bit OFF again to resume service to the CPU Bus Unit.

CPU Bus Unit Initializing Flags

Bits A30200 through A30215 turn ON while the corresponding CPU Bus Units (Units #0 through #15, respec- tively) are initializing.

CPU Bus Error and Unit Flags

Bit A40112 is turned ON when an error occurs during the transmission of data between the CPU Unit and CPU Bus Units, or a WDT (watchdog timer) error occurs in a CPU Bus Unit. The unit number of the CPU Bus Unit involved is contained in word A405.

Bits A40500 through A40515 correspond to CPU Bus Units #0 through #15, respectively. When a CPU Bus Error occurs, the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.

CPU Bus Unit Setting Error Flag and Unit Number

Bit A40203 is turned ON when the CPU Bus Units actually installed differ from the Units registered in the I/O table. The unit number of the CPU Bus Unit involved is written to word A427.

Bits A42700 through A42715 correspond to CPU Bus Units #0 through #15, respectively. When a error occurs, the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.

CPU Bus Unit Error Flag and Unit Numbers

Bit A40207 is turned ON when a parity error occurs during the transmission of data between the CPU Unit and CPU Bus Units. The unit number of the CPU Bus Unit involved is written to word A422.

Bits A42200 through A42215 correspond to CPU Bus Units #0 through #15, respectively. When a CPU Bus Unit Error occurs, the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.

357

Page 380
Image 380
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual CVM1 and CV-series PLCs