Data Link I/O Response Time

Section 8-3

Case 4

The following diagram illustrates the data flow that will produce the maximum data link I/O response time when the cycle time of the PLC at node #1 < the communications cycle time and the cycle time of the PLC at node #7 < the communications cycle time.

Input

 

 

 

Input device

 

I/O refresh

 

 

 

 

 

 

 

Data exchange

 

 

 

 

 

 

Input ON delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

(1)

 

1 cycle

 

 

 

Program

 

PLC at node #1

 

 

X

(2)

 

 

 

A

Controller Link Unit

 

 

 

 

 

 

 

transmission processing

 

 

 

 

Data link transmission

 

 

Communications

Controller Link Unit

 

 

cycle time

 

transmission processing

 

 

 

 

(3)

 

 

 

Previous communications

 

 

 

cycle data

X

 

 

 

 

 

 

PLC at node #7

Program

 

 

 

 

1 cycle

 

 

 

 

Output device

 

 

 

 

Output ON

 

 

 

 

delay

 

 

Data link I/O response time

Output

There are three points shown in the diagram above where processing is delayed, increasing the data link I/O response time.

1,2,3... 1. The input arrives in the PLC just after I/O refreshing, causing a delay of up to one cycle before the input is read into the PLC.

2.At point A data from the previous data exchange is still being transferred, so the new data cannot be exchanged, causing a delay of up to one com- munications cycle time. Furthermore, the data exchange then occurs just after the PLC at node #1 passes the token that makes it the polling node, causing another delay of up to one communications cycle time before the data is transferred in data link processing.

3.The data transferred in data link processing arrives at the PLC at node #7 while data exchange is taking place, so the data will not be read into the PLC until the next data exchange, causing a delay of up to 1 to 2 cycle.

The maximum number of words that can be exchanged in a single data ex- change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700 words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE PLCs, and approx. 1,200 words for CQM1H-series PLCs.

261

Page 284