Troubleshooting Using Indicators

 

 

 

 

Section 9-1

 

• Setting hardware switches.

 

 

 

 

 

 

 

 

 

 

Indicators

 

Probable cause

Probable remedy

 

 

 

 

 

 

 

 

RUN

ERC

ERH

INS

 

 

 

 

 

 

 

 

 

 

Lit

Not lit

Not lit

Lit

Unit operating normally;

---

 

 

 

 

 

Network participation nor-

 

 

 

 

 

 

mal.

 

 

 

 

 

 

 

 

 

Not lit

Lit

---

---

Controller Link Unit faulty.

If the ERC indicators still

 

 

 

 

 

 

lights when the Unit is

 

 

 

 

 

 

mounted on another PLC,

 

 

 

 

 

 

replace the Controller Link

 

 

 

 

 

 

Unit.

 

 

 

 

 

 

 

 

Not lit

Not lit

Not lit

Not lit

Power is not being sup-

Check the power supply

 

 

 

 

 

plied correctly to the PLC.

voltage and supply at the

 

 

 

 

 

 

recommended voltage.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit

Secure the Controller Link

 

 

 

 

 

has become loose.

Unit firmly.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit is

Refer to CVM1 and CV-

 

 

 

 

 

mounted in the wrong slot.

series PLCs and mount the

 

 

 

 

 

 

Unit correctly.

 

 

 

 

 

 

 

 

 

 

 

 

The Controller Link Unit is

If the indicators do not light

 

 

 

 

 

faulty.

when the Unit is mounted

 

 

 

 

 

 

in another PLC, replace

 

 

 

 

 

 

the Controller Link Unit.

 

 

 

 

 

 

 

 

Lit

Lit

---

Not lit

The node address is out-

Reset the node address to

 

 

 

 

 

side the setting range.

within the 1 to 32 range.

 

 

 

 

 

 

 

 

 

 

 

 

The same node address is

Reset so that each node

 

 

 

 

 

being used by two different

address is used only once

 

 

 

 

 

Units.

within the same Network.

 

 

 

 

 

 

 

 

Lit

---

Lit

---

Routing table setting error

Remake and set the rout-

 

 

 

 

 

or a Routing Table Enable/

ing table correctly, referring

 

 

 

 

 

Disable Bit setting error.

to 7-4 Setting Routing

 

 

 

 

 

 

Tables. When no routing

 

 

 

 

 

 

table is being used, set the

 

 

 

 

 

 

Routing Table Enable/Dis-

 

 

 

 

 

 

able Bit to OFF.

 

 

 

 

 

 

 

 

 

 

 

 

The Unit is mounted to a

Refer to 1-2-4 Controller

 

 

 

 

 

non-compatible PLC.

Link Unit Models and PLCs

 

 

 

 

 

 

and reinstall the Unit on

 

 

 

 

 

 

the appropriate PLC.

 

 

 

 

 

 

 

 

 

 

 

 

An error has occurred in

Refer to the PLC’s opera-

 

 

 

 

 

the PLC.

tion manual and correct

 

 

 

 

 

 

the error. If the error occurs

 

 

 

 

 

 

again, replace the PLC.

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error

Refer to 9-2 Status Area

 

 

 

 

 

 

and Troubleshooting, cor-

 

 

 

 

 

 

rect the data where the

 

 

 

 

 

 

error has occurred, and

 

 

 

 

 

 

reset the Unit. If the error

 

 

 

 

 

 

occurs again, replace the

 

 

 

 

 

 

Controller Link Unit.

 

 

 

 

 

 

 

 

 

 

 

 

The unit number is not set

Reset the Unit number to

 

 

 

 

 

in the range from 0 to 15.

within a range of 0 to 15.

 

 

 

 

 

 

 

 

 

 

 

 

The same unit number is

Reset so that each unit

 

 

 

 

 

set more than once for the

number is set only once

 

 

 

 

 

same PLC.

within the same PLC

 

 

 

 

 

 

(including the Expansion

 

 

 

 

 

 

CPU Backplane.)

 

 

 

 

 

 

 

 

 

 

 

 

I/O tables have not been

Create I/O tables for the

 

 

 

 

 

created for the PLC or they

PLC correctly.

 

 

 

 

 

are faulty.

 

 

 

 

 

 

 

 