Data Link I/O Response Time

Section 8-3

CVM1, CV-series, CS/CJ-series PLCs Under Synchronous Operation or C200HX/HG/ HE and CQM1H-series PLCs

Maximum I/O Response The maximum data link I/O response time is calculated for four cases.

Time

Case 1

The following diagram illustrates the data flow that will produce the maximum data link I/O response time when the cycle time of the PLC at nodes #1 and 7 are greater than the communications cycle time.

Input

 

 

 

 

Input device

 

 

 

 

 

Input ON delay

 

 

 

 

 

 

 

 

X

1 cycle

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program

X

(2)

Communications cycle time

I/O refresh

Data exchange

PLC at node #1

 

 

 

Controller Link Unit

 

 

 

transmission processing

 

 

 

 

 

 

 

 

 

 

Data link transmission

X (3) X

 

 

 

 

Controller Link Unit

Previous communica

 

 

transmission processing

 

 

 

tions cycle data

 

 

 

X(4)

PLC at node #7

Program

 

1 cycle

 

Output device

 

Output ON delay

Data link I/O response time

Output

 

There are four points shown in the diagram above where processing is delayed, increasing the data link I/O response time.

1,2,3... 1. The input arrives in the PLC just after I/O refreshing, causing a delay of up to one cycle before the input is read into the PLC.

2.Data exchange occurs just after the PLC at node #1 passes the token that makes it the polling node, causing a delay of up to one communications cy- cle time before the data is transferred in data link processing.

3.At node #7, data from the previous data exchange is still being transferred, causing a delay of up to one cycle before the input is read into the PLC.

4.The data transferred in data link processing arrives at the PLC at node #7 after data exchange, so the data will not be read into the PLC until the next data exchange, causing a delay of up to 1 to 2 cycle.

The maximum number of words that can be exchanged in a single data ex- change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700 words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE PLCs, and approx. 1,200 words for CQM1H-series PLCs.

256

Page 279
Image 279