Omron C200HW-CLK21 Status Area and Troubleshooting, Troubleshooting with the PWR Indicator

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 315
Image 315

Status Area and Troubleshooting

 

Section 9-2

Troubleshooting with the PWR Indicator

 

 

 

 

 

 

indicator

Unit status

Possible error

Probable cause

Probable remedy

status

 

 

 

 

 

 

 

 

 

Lit

Power is being sup-

---

---

---

 

plied normally

 

 

 

 

 

 

 

 

Not lit

Power supply error

Power supply

Cables are loose.

Check the cable connections.

 

 

cables

 

 

 

 

Cables are broken.

Check whether any of the cables

 

 

 

 

 

 

 

are broken.

 

 

 

 

 

 

 

 

Cable polarity is incorrect.

Check the cable connections.

 

 

 

 

 

 

 

Power supply

Power supply voltage or current is

Check the power supply voltage,

 

 

 

wrong.

and replace the power supply with

 

 

 

 

a Power Supply Unit that will pro-

 

 

 

 

vide a correct supply.

 

 

 

 

 

 

 

Repeater Unit

The Repeater Unit is faulty.

Replace the Repeater Unit.

 

 

 

 

 

Troubleshooting with the T/R1 and T/R2 Indicators

 

 

 

 

 

 

indicator

Unit status

Possible error

Probable cause

Probable remedy

status

 

 

 

 

Lit or

The Unit is commu-

---

Unit operating normally.

---

flashing

nicating normally.

 

 

 

 

 

 

 

 

Not lit

Communications

Communica-

Cables are loose.

Check the cable connections.

 

error (transmission

tions cables

 

 

 

Cables are broken.

Check whether any of the cables

 

signal error or no

 

 

 

 

are broken.

 

signal)

 

 

 

 

 

 

 

 

Cable polarity is incorrect.

Check the cable connections.

 

 

 

 

 

 

 

 

 

 

 

Noise interference in cables.

Check the wiring environment of

 

 

 

 

the cables.

 

 

 

 

 

 

 

Other nodes

The destination node does not

Check the destination Controller

 

 

 

exist.

Link Unit status (power supply,

 

 

 

 

cable connections).

 

 

 

 

 

 

 

 

The destination node has an

Check the destination Controller

 

 

 

error.

Link Unit status (baud rate setting,

 

 

 

 

terminating resistance settings,

 

 

 

 

statuses, error log, etc.).

 

 

 

 

 

 

 

Repeater Unit

Terminating resistance is set

Check the terminating resistance

 

 

 

incorrectly.

setting for the network.

 

 

 

 

 

 

 

 

The baud rate setting is incorrect.

Check that the same baud rate is

 

 

 

 

set for all nodes in the same net-

 

 

 

 

work.

 

 

 

 

 

 

 

 

Noise interference

Check the operating environment

 

 

 

 

of the Unit.

 

 

 

 

 

 

 

 

The Repeater Unit is faulty.

Replace the Repeater Unit.

 

 

 

 

 

9-2 Status Area and Troubleshooting

The status of the Unit and the communications status of the Controller Link Unit is recorded in the Status Area of the PLC. The cause of errors can be found by searching the Status Area. The Status Area can be read using a Pro- gramming Console, the SYSMAC Support Software, or the Controller Link Support Software.

This section explains the contents of the Status Area and tells how to trouble- shoot errors recorded there.