Omron CVM1-CLK21 CVM1 and CV-series Controller Link Units, Node Addresses, Setting Baud Rates

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 120
Image 120

CVM1 and CV-series Controller Link Units

Section 4-4

4-4 CVM1 and CV-series Controller Link Units

The following settings are required for a Controller Link Unit when used with a

CVM1 or CV-series PLC.

Item

Switch

Page

 

 

 

Unit number

Unit number switch

98

 

 

 

Node address

Node address switch

98

 

 

 

Baud rate

Baud rate switch, pins 1 and 2

99

 

 

 

Terminating resistance

Terminating resistance switch

99

 

 

 

4-4-1 Overview

CLK21

 

 

 

RUN

 

M/A

 

ERC

 

LNK

 

 

 

M/A

 

INS

 

LNK

 

 

RD

 

SD

 

 

 

 

X101

 

 

 

UNIT

 

 

NO.

 

 

 

X101

0

0

X100

NODE

 

 

NO.

 

 

0

X101

0

0

X10

 

ON

 

 

 

 

1

BAUD

SW1

 

2

RATE

 

3

RSV

 

 

4

RSV

BAUD RATE

BIT2 BIT1 RATE

OFF OFF 2MBP OFF ON 1MBP ON OFF 500KBP

TER SW

BD H

BD L

SHLD

UNIT

NO.

X101 0

NODE

NO.

X101 0

ON

1 2 3 4

0X100

1X100

1BAUD

2RATE

3RSV

4RSV

Unit Number

Setting range

Nodes

 

 

00 to 15 (default is 00)

All nodes in the Network

 

 

Node Addresses

Setting range

Nodes

 

 

01 to 32 (default is 01)

All nodes in the Network

 

 

Setting Baud Rates

 

Switch

Baud rate

Maximum

Nodes

 

 

 

 

transmis-

 

Pin 1

 

Pin 2

 

 

 

 

sion dis-

 

 

 

 

 

 

 

 

 

 

tance

 

 

 

 

 

 

 

OFF

 

OFF

2 Mbps

500 m

Set same

 

 

 

 

 

rate for all

ON

 

OFF

1 Mbps

800 m

 

nodes in

 

 

 

 

 

OFF

 

ON

500 Kbps

1 km

 

Network.

 

 

 

 

 

 

 

 

 

 

 

ON

 

ON

Do not set.

 

 

 

 

 

 

 

 

Note The factory default setting is in bold.

Always keep pins 3 and 4 set to OFF.

Terminating Resistance

Bottom switch

Terminating

Nodes

 

resistance

 

 

 

 

OFF

Not connected

All the nodes

(factory default)

 

Turn ON the terminating resis-

 

 

ON

Connected

tance at the nodes at both

 

 

ends of the Network and turn it

 

 

OFF at all other nodes.

 

 

 

97

Page 120
Image 120
Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1 CVM1 and CV-series Controller Link Units, Node Addresses, Setting Baud Rates