Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 Examples of Incorrect Repeater Unit Connections

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 104
Image 104

Constructing Networks with Repeater Units

Section 3-4

Long-distance Wiring: 2-stage Repeater Unit Connection

Stage 2

CS1W-RPT01

Repeater Unit

Not more than 2 Repeater Units (2 stages) must be passed for any node to reach any other node

Partial Optical Conversion: 2-stage Repeater Unit Connection

Stage 1

Optical

fiber cable

Stage 2

 

CS1W-RPT02 or

 

CS1W-RPT03

 

 

 

 

Repeater Unit

Two Wire-to-Optical Repeater Units make up a single set counted as a single stage. Therefore, not more than 4 Repeater Units (2 stages) must be passed for any node to reach any other node.

Examples of Incorrect Repeater Unit Connections

More than 2 Stages of Repeater Units

PLC A

PLC B

CS1W-RPT01

Repeater Unit

The path from PLC A to PLC B travels via 3 Repeater Units (3 stages). This kind of network is NOT allowed.

More than 2 Stages of Repeater Units

CS1W-RPT01

Repeater Unit

81

Page 104
Image 104
Omron CJ1W-CLK21-V1 Examples of Incorrect Repeater Unit Connections, Long-distance Wiring 2-stage Repeater Unit Connection