Response Codes

 

 

Section 6-7

 

 

 

 

Main code

Sub-

Probable cause

Remedy

 

code

 

 

 

 

 

 

20: Read not possible

02

The data is protected.

Execute the instruction again after issuing

 

 

 

the PROGRAM AREA PROTECT CLEAR

 

 

 

command to the PLC.

 

 

 

 

 

 

An attempt was made to download a

Check the file name and either interrupt ser-

 

 

file that is being uploaded.

vicing or wait for servicing to complete

 

 

 

before re-executing the command.

 

 

 

 

 

03

The registered table does not exist or is

Set or reset the registered table.

 

 

incorrect.

 

 

 

 

 

 

 

Too many files open.

Close open files and re-execute the com-

 

 

 

mand.

 

 

 

 

 

04

The corresponding search data does

---

 

 

not exist.

 

 

 

 

 

 

05

A non-existing program no. has been

Check the program number and be sure

 

 

specified.

that it is set correctly.

 

 

 

 

 

06

A non-existing file has been specified.

Check whether the correct file name was

 

 

 

used.

 

 

 

 

 

07

A verification error has occurred.

Check whether the memory contents are

 

 

 

correct and replace if incorrect.

 

 

 

 

 

 

 

Check the contents of the file. A read error

 

 

 

may have occurred.

 

 

 

 

21: Write not possible

01

The specified area is read-only or is

If the specified area is read-only, the write

 

 

write-protected.

cannot be performed. If it is write-protected,

 

 

 

turn off the write-protect switch and execute

 

 

 

the instruction again.

 

 

 

 

 

02

The data is protected.

Execute the instruction again after issuing

 

 

 

the PROGRAM AREA PROTECT CLEAR

 

 

 

command to the PLC.

 

 

 

 

 

 

An attempt was made to simulta-

Check the file name and either interrupt ser-

 

 

neously download and upload a file.

vicing or wait for servicing to complete

 

 

 

before re-executing the command.

 

 

 

 

 

 

The data link tables cannot be written

Change the data link mode to manual.

 

 

manual because the Unit is set for

 

 

 

automatic generation.

 

 

 

 

 

 

03

The number of files exceeds the maxi-

Write the file(s) again after erasing

 

 

mum permissible.

unneeded files, or use different disk or

 

 

 

Memory Card that has free space.

 

 

 

 

 

 

Too many files open.

Close open files and re-execute the com-

 

 

 

mand.

 

 

 

 

 

05

A non-existing program no. has been

Check the program number and be sure

 

 

specified.

that it is set correctly.

 

 

 

 

 

06

A non-existent file has been specified.

Check the file name and execute again.

 

 

 

 

 

07

The specified file already exists.

Change the name of the file and execute

 

 

 

the instruction again.

 

 

 

 

 

08

Data cannot be changed.

---

 

 

 

 

230