CQM1H-series Controller Link Units

Section 4-5

Note 1. Always turn OFF the PLC’s power before setting the terminating resistance switch.

2.Turn ON the switch to connect terminating resistance at the nodes at both ends of the Network and turn OFF the switch at all other nodes. Normal communication cannot be performed in the Network unless all the nodes are set properly.

3.The TER indicator will light when the terminating resistance switch is set to ON.

4-5 CQM1H-series Controller Link Units

The following settings are required for a Controller Link Unit when used with a

CQM1H-series PLC.

Item

Switch

Page

 

 

 

Node address

Node address switch

101

 

 

 

Baud rate

Baud rate switch, pins 1 and 2

101

 

 

 

Terminating resistance

Terminating resistance switch

102

 

 

 

4-5-1 Overview

Node Addresses

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

 

 

Setting Baud Rate

Switch

Baud rate

Maximum

Nodes

 

 

 

transmis-

 

Pin 1

Pin 2

 

 

 

sion dis-

 

 

 

 

 

 

 

 

tance

 

 

 

 

 

 

OFF

OFF

2 Mbps

500 m

Set same

 

 

 

 

rate for all

ON

OFF

1 Mbps

800 m

nodes in Net-

 

 

 

 

OFF

ON

500 Kbps

1 km

work.

 

 

 

 

 

 

 

 

 

ON

ON

Do not set.

 

 

 

 

 

 

 

Note The factory default setting is in bold.

Terminating Resistance

Switch

Terminating

Nodes

 

resistance

 

 

 

 

OFF

Not connected

All the nodes

(default)

 

Turn ON the terminating resis-

 

 

ON

Connected

tance at the nodes at both

 

 

ends of the Network and turn it

 

 

OFF at all other nodes.

 

 

 

100

Page 123
Image 123
Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01 CQM1H-series Controller Link Units, Setting Baud Rate, Pin Sion dis Tance