Response Codes

 

 

Section 6-7

 

 

 

 

Main code

Sub-

Probable cause

Remedy

 

code

 

 

 

 

 

 

01: Local node error

01

Local node not part of Network

Add to Network.

 

 

 

 

 

02

Token time-out, node address too large

Set the local node’s node address below

 

 

 

the maximum node address.

 

 

 

 

 

03

Number of transmit retries exceeded

Check communications with ECHOBACK

 

 

 

TEST. If the test fails, check network.

 

 

 

 

 

04

Maximum number of frames exceeded

Either check the execution of events in the

 

 

 

network and reduce the number of events

 

 

 

occurring in one cycle, or increase the max-

 

 

 

imum number of frames.

 

 

 

 

 

05

Node address setting error (range)

Correctly set the Controller Link BIOS /N

 

 

 

option. Make sure the node address is

 

 

 

within specified range and that there are no

 

 

 

node addresses that are set twice.

 

 

 

 

 

06

Node address duplication error

Make sure that there are no node

 

 

 

addresses that are set twice.

 

 

 

 

02: Destination node

01

Destination node not part of Network

Add to Network.

error

 

 

 

02

No node with the specified node

Check the destination node’s node address.

 

 

 

address

 

 

 

 

 

 

03

Third node not part of Network

Check the third node’s node address.

 

 

 

 

 

 

Broadcasting was specified.

Check the control data and specify only one

 

 

 

node as the third node.

 

 

 

 

 

04

Busy error, destination node busy

Increase the number of transmit retry

 

 

 

attempts or re-evaluate the system so that

 

 

 

the destination node is not so busy receiv-

 

 

 

ing data.

 

 

 

 

 

05

Response time-out, message packet

Increase the number of transmit retry

 

 

was corrupted by noise

attempts.

 

 

 

 

 

 

Response time-out, response watch-

Increase the value for the response watch-

 

 

dog timer interval too short

dog timer interval in the control data.

 

 

 

 

 

 

Frame lost in transmission

Check the error log and correct the process.

 

 

 

 

03: Communications con-

01

Error occurred in the communications

Take corrective action, referring to commu-

troller error

 

controller, ERC indicator is lit

nications controller errors and remedies

 

 

 

table at end of this section.

 

 

 

 

 

02

CPU Unit error occurred in the PLC at

Clear the error in the CPU Unit (refer to the

 

 

the destination node

PLC’s operation manuals).

 

 

 

 

 

03

A controller error has prevented a nor-

Check network communications status and

 

 

mal response from being returned.

reset the controller board. If the error still

 

 

 

exists, replace the controller board.

 

 

 

 

 

04

Unit address setting error

Make sure the Unit address is within the

 

 

 

specified range and that there are no node

 

 

 

addresses that are set twice.

 

 

 

 

04: Not executable

01

An undefined command has been

Check the command code and be sure that

 

 

used.

the Unit supports it.

 

 

 

 

 

02

Cannot process command because the

Check the unit model and version.

 

 

specified unit model or version is

 

 

 

wrong.

 

 

 

 

 