Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 140

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 163
Image 163

Setting Data Links

Section 5-2

 

 

 

 

Item

Setting range

 

 

 

 

Number of common send

Set the number of words in BCD between 0 and 1,000.

 

words per master node

The number of common send words per master node

 

 

 

 

added to the number of individual send words per master

 

 

node multiplied by the number of slave nodes participat-

 

 

ing in the data links must not exceed 1,000.

 

 

Set to 0 if common data is not to be sent from a master

 

 

node to a slave node.

 

 

 

 

Number of individual

Set the number of words in BCD between 0 and 1,000.

 

send words per master

The number of common send words per master node

 

node

 

added to the number of individual send words per master

 

 

 

 

node multiplied by the number of slave nodes participat-

 

 

ing in the data links must not exceed 1,000.

 

 

Set to 0 if individual data is not to be sent from a master

 

 

node to a slave node.

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for slave node

Set to 0 if the slave node will transmit no data.

 

 

 

 

 

 

First data link status word

Set in BCD the first word used for storing data link status.

 

 

When automatic setup is used, status can be stored in

 

 

the IR or CIO Area only. The number of words used to

 

 

store status depends on the data link status storage for-

 

 

mat specification as below.

 

 

0 (*)

 

 

1 to 6128 (32 nodes max., 8-bit format: 16 words used)

 

 

*: When 0 is set, the status is saved in IR 1500 + unit

 

 

number x 25 (+ 7 to + 22).

 

 

 

 

Nodes to participate in

Set to ON (1) the bits corresponding to the nodes partici-

 

the data links

pating in the data links.

 

 

The data link will not start unless the startup node itself is

 

 

set as a participating node.

Note 1. Node 1 becomes the master node. Node 1 must be registered as a partic- ipating node.

2.Only one area can be specified when using the 1 to 1 type of 1:N alloca- tion.

3.The startup node (the node that sets the above DM parameter and starts the data link) must be set as a participating node of the data link. If not, the data links will not start.

4.The total number of words in data link send and receive areas must not ex- ceed 20,000 per node when using Controller Link Units with unit Ver. 1.2 or later, or 12,000 words per node if using pre-Ver. 1.2 Controller Link Units. The total number of words in data link send and receive areas of a master node must satisfy the following values. Since the number of master node words is greatest when 1:N allocation is used, the value can be esti- mated from the number of master node words.

Total number of words in data link send and receive areas of master node =

Number of common send words in master node +

Number of individual send words in master node Number of slave nodes participating in data links +

Number of send words in slave node Number of slave nodes partic- ipating in data links

5.The following values must be satisfied to ensure that the data link area is fully contained within the specified area.

140

Page 163
Image 163
Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual 140