Status Area and Troubleshooting

 

 

Section 9-2

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Data link table error

The data link table data in

Refer to 5-3 Starting and

 

(CIO 1500 + 25

n, bit 1)

the EEPROM of the CPU

Stopping Data Links and

 

is 1: ON

 

Unit is damaged.

reset the data link tables

 

 

 

 

correctly. If the error occurs

 

 

 

 

again, replace the CPU

 

 

 

 

Unit.

 

 

 

 

 

 

 

 

There is an error in the

When using manually set

 

 

 

data link table settings.

data links, refer to 5-3

 

 

 

 

Starting and Stopping Data

 

 

 

 

Links and remake and set

 

 

 

 

the data link tables cor-

 

 

 

 

rectly. When manually set

 

 

 

 

data links are not being

 

 

 

 

used, delete the data link

 

 

 

 

tables.

 

 

 

 

 

Network parameter error

The CPU Unit’s EEPROM

Refer to 8-1-3 Network

 

(CIO 1500 + 25

n, bit 0)

data link tables or the net-

Parameters and reset the

 

is 1: ON

 

work parameters are dam-

data correctly. If the error

 

 

 

aged.

occurs again, replace the

 

 

 

 

CPU Unit.

 

 

 

 

 

 

 

 

 

Either set the EEPROM

 

 

 

 

Clear Bit in the DM Param-

 

 

 

 

eter Area to ON, or use the

 

 

 

 

Initialize network parame-

 

 

 

 

ters operation on the Main-

 

 

 

 

tenance Menu of the

 

 

 

 

Controller Link Support

 

 

 

 

Software to initialize the

 

 

 

 

network parameters and

 

 

 

 

then cycle the power sup-

 

 

 

 

ply.

 

 

 

 

 

 

 

 

There is an error in the net-

Refer to 8-1-3 Network

 

 

 

work parameter settings, or

Parameters and reset the

 

 

 

node address of the local

network parameters or the

 

 

 

node is larger then the

node address.

 

 

 

maximum address set

 

 

 

 

within the network parame-

 

 

 

 

ters.

 

 

 

 

 

 

9-2-4 CQM1H-series Controller Link Units

Status Area

Error Information: IR 190

1: Network parameter error (In PLC's EEPROM)

1: Data link table error (in PLC's EEPROM)

1: Routing table error (in PLC's EEPROM)

1: PLC system setting error

1: EEPROM error

1: Duplicate node address setting error

1: Inconsistent network parameters

1: Communications controller send error

1: Error log exists

308

Page 331
Image 331
Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21 4 CQM1H-series Controller Link Units, Error Information IR