Setting Data Links

 

Section 5-2

 

 

 

 

 

 

Setting item

 

Setting range

 

 

 

 

Area 2

Data link

CIO Area: CIO 0000 to CIO 2555

 

 

start word

LR Area: LR 000 to LR 199 (*)

 

 

 

 

 

 

DM Area: DM 0000 to DM 8191 (CV500/CVM1-CPU01-EV@)

 

 

 

DM 0000 to DM 24575 (Other CPU Units)

 

 

 

EM Area: Banks 00 to 07, EM 0000 to EM 32765

 

 

 

(EM must be installed)

 

 

 

The same area cannot be set for both area 1 and area 2. Set dif-

 

 

 

ferent areas.

 

 

 

 

*: When a word between LR 000 and LR 199 is specified, the

 

 

 

data link area will be allocated between CIO 1000 and

 

 

 

CIO 1199.

 

 

 

 

 

 

 

 

Number of

Remote nodes:

0 to the number of source words

 

 

words

 

Set the number of words to be received.

 

 

 

Local node:

0 to 1,000

 

 

 

 

Set the number of words to be transmitted.

 

 

 

The total number of words in area 1 and area 2 in each node

 

 

 

must not exceed 1,000.

 

 

 

The numbers of words in both area 1 and area 2 in each node

 

 

 

must not be set to 0.

 

 

 

 

 

 

 

Offset

Remote nodes:

0 to one less than number of source words

 

 

 

 

Set the offset for the data to be received.

 

 

 

Local node:

Cannot be set.

 

 

 

This setting is not required if an offset is not used.

 

 

 

 

 

Note a) The total number of words in data link send and receive areas must not exceed 8,000 per node.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.

(Data link start word – 1) + Total number of send/receive words in area 2555 (CIO Area)

199 (LR Area)

8191 (DM Area for CV500/CVM1-CPU01-EV@) 24575 (DM Area for other CPU Units)

32765 (EM Area)

c)Refer to the Controller Link Support Boards Operation Manual (W307) for information on the Controller Link Support Board.

d)If CX-Net detects an error during the data link table check, trou- bleshoot the error referring to 9-4 Troubleshooting Error Mes- sages in CX-Net Data Link Table Check.

CQM1H-series PLCs

Setting item

Setting range

 

 

PLC model

Set the model of the PLC’s CPU Unit.

 

 

Nodes

1 to 32

 

Set the address of the refresh nodes.

 

It cannot be set to a parameter exceeding the “maximum node

 

address” of the network parameters.

 

 

120

Page 143
Image 143
Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21 operation manual CQM1H-series PLCs