Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 Repeater Units, Section

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 125
Image 125

Repeater Units

Section 4-6

Note Set the same baud rate for all the nodes on the Network. Normal communica- tion cannot be performed unless the same baud rate is set for all the nodes.

4-5-4 Terminating Resistance

Turn ON the terminating resistance using the switch on the bottom of the Unit for the Units of both ends of the Network. The terminating resistance is required at both ends of a Network to absorb unnecessary signals and reduce noise.

The Controller Link Unit has built-in terminating resistance, which can be con- nected simply by turning ON the slide switch.

 

(The diagram shows the factory setting.)

 

 

 

Switch at the front

 

Terminating resistance

 

 

 

OFF (default)

 

Not connected.

 

 

 

ON

 

connected

 

 

 

Note 1. Always turn OFF the PLC’s power before setting the terminating resistance switch.

2.Turn ON the switch to connect terminating resistance at the nodes at both ends of the Network and turn OFF the switch at all other nodes. Normal communication cannot be performed in the Network unless all the nodes are set properly.

3.The TER indicator will light when the terminating resistance switch is set to ON.

4.The switch is factory-set to OFF (terminating resistance not connected).

4-6 Repeater Units

Repeater Units must be set as shown in the following table before starting communications.

Item

Switch

Page

 

 

 

Baud rate

Baud rate switch, pin 1

103

 

 

 

Terminating resistance

Terminating resistance switch

104

 

 

 

102

Page 125
Image 125
Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21 operation manual Repeater Units, Section