Setting Data Links

Section 5-2

 

 

 

 

Item

Setting range

 

 

 

 

Area start word

Set the word address in BCD.

 

 

IR or CIO Area: 0 to 6143

 

 

LR Area: LR 000 to LR 199 (1000 to 1199) (*)

 

 

DM Area: DM 0 to 32767

 

 

EM Area: Banks 0 to 12 EM 0 to 32767

 

 

*: When a word between LR 000 and LR 199 is speci-

 

 

fied, the data link area will be allocated between

 

 

words 1000 and 1199 in the IR or CIO Area.

 

 

 

 

Area

Set the area type of area 1 as a hexadecimal number.

 

 

IR Area: 80 Hex

 

 

LR Area: 86 Hex

 

 

DM Area: 82 Hex

 

 

EM Area Banks 0 to 7: 90 to 97 Hex

 

 

Banks 8 to 12: A8 to AC Hex

 

 

 

 

Number of master com-

Set the number of words in BCD between 0 and 1,000.

 

mon send words

The number of common send words per master node

 

 

 

 

added to the number of delivery send words per node

 

 

must not exceed 1,000.

 

 

Set to 0 if common data is not to be sent from a master

 

 

node to a slave node.

 

 

 

 

No. of receive and send

Set the number of words in BCD between 0 and 1,000.

 

words per node

The number of common send words per master node

 

 

 

 

added to the number of delivery send words per node

 

 

must not exceed 1,000.

 

 

Set to 0 if delivery data is not to be sent.

 

 

 

 

First word to store data

Set in BCD the first word used for storing data link status.

 

link status

When automatic setup is used, status can be stored in

 

 

the IR or CIO Area only. The number of words used to

 

 

store status depends on the data link status storage for-

 

 

mat specification as below.

 

 

0 (*)

 

 

1 to 6128 (32 nodes max., 8-bit format: 16 words used)

 

 

*: When 0 is set, the status is saved in IR 1500 + unit

 

 

number x 25 (+ 7 to + 22).

 

 

 

 

Nodes to participate in

Set to ON (1) the bits corresponding to the nodes partici-

 

the data links

pating in the data links.

 

 

The data link will not start unless the startup node itself is

 

 

set as a participating node.

 

 

 

Note 1. Node 1 becomes the master node. Node 1 must be registered as a partic- ipating node.

2.Only one area can be specified when using the chain type of 1:N alloca- tion.

3.The startup node (the node that sets the above DM parameter and starts the data link) must be set as a participating node of the data link. If not, the data links will not start.

4.The total number of words in data link send and receive areas must not ex- ceed 20,000 per node when using Controller Link Units with unit Ver. 1.2 or later, or 12,000 words per node if using pre-Ver. 1.2 Controller Link Units. The total number of words in data link send and receive areas of a master node must satisfy the following values. Since the number of master node words is greatest when 1:N allocation is used, the value can be esti- mated from the number of master node words.