1 401
Download 401 pages 33.98 Kb
Page 339
Image 339

Error Log

 

 

 

 

Section 9-3

 

 

 

 

 

 

 

 

Error

Contents

Detail code

Correction

Written to

 

Applicable

code

 

 

 

 

EEPROM

 

PLC

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0101

Transmission failed; local node

Command block

Refer to page 276

No

 

All

Hex

not in Network

Bits 0 to 7:

 

Troubleshooting

 

 

 

 

 

Source node address

Using Indicators and

 

 

 

 

 

Bits 8 to 14:

 

place the local node

 

 

 

 

 

Source Network

into Network.

 

 

 

0103

Transmission failed; retry count

address

 

Using the Controller

No

 

All

Hex

exceeded

Bit 15:

 

Link Support Soft-

 

 

 

 

 

OFF

 

ware or FINS

 

 

 

 

 

Response block

commands, run

 

 

 

 

 

Bits 0 to 7:

 

echoback test and

 

 

 

 

 

Destination node

check operating envi-

 

 

 

 

 

ronment if errors

 

 

 

 

 

address

 

 

 

 

 

 

 

occur.

 

 

 

 

 

Bits 8 to 14:

 

 

 

 

 

 

 

 

 

 

 

0104

Transmission failed; maximum

 

Reduce the number

No

 

All

Destination Network

 

Hex

number of frames exceeded.

address

 

of events per com-

 

 

 

 

 

 

munications cycle or

 

 

 

 

 

Bit 15:

 

 

 

 

 

 

 

increase the maxi-

 

 

 

 

 

ON

 

 

 

 

 

 

 

mum number of

 

 

 

 

 

(1st byte: bits 8 to 15;

 

 

 

 

 

network parameter

 

 

 

 

 

2nd byte, bits 0 to 7)

 

 

 

 

 

frames.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0105

Transmission failed; node

 

 

Refer to 4-2 CJ-

No

 

All

Hex

address incorrect

 

 

series Controller Link

 

 

 

 

 

 

 

Unitsor 4-4 CVM1

 

 

 

 

 

 

 

and CV-series Con-

 

 

 

 

 

 

 

troller Link Units and

 

 

 

 

 

 

 

check node address

 

 

 

 

 

 

 

settings to be sure

 

 

 

 

 

 

 

they are within range

 

 

 

 

 

 

 

and unique.

 

 

 

 

 

 

 

 

 

 

 

0106

Transmission failed; redundant

 

 

Correct node

No

 

All

Hex

node address

 

 

addresses so that

 

 

 

 

 

 

 

they are unique

 

 

 

 

 

 

 

within the same

 

 

 

 

 

 

 

Network.

 

 

 

 

 

 

 

 

 

 

 

0107

Transmission failed; destination

 

 

Refer to 9-1 Trouble-

No

 

All

Hex

node not in Network

 

 

shooting Using Indi-

 

 

 

 

 

 

 

cators and place

 

 

 

 

 

 

 

destination node into

 

 

 

 

 

 

 

Network.

 

 

 

 

 

 

 

 

 

 

 

0108

Transmission failed; specified

 

 

Refer to 4-4 CVM1

No

 

All

Hex

Unit does not exist

 

 

and CV-series Con-

 

 

 

 

 

 

 

troller Link Units and

 

 

 

 

 

 

 

check unit address

 

 

 

 

 

 

 

and unit number of

 

 

 

 

 

 

 

destination.

 

 

 

 

 

 

 

 

 

 

 

316

Page 339
Image 339