Omron C200HW-CLK21, CVM1-CLK21 Terminating Resistance, Branch Wiring, Long-distance Wiring

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 105
Image 105

Constructing Networks with Repeater Units

Section 3-4

The path from one node to another travels

via three Repeater Units

(3 stages). This kind of network is NOT allowed.

 

Note If the Repeater Units are used incorrectly, communications errors may occur, or nodes may not be able to participate in the network.

3-4-3 Terminating Resistance

In a Wired Controller Link Network, turn ON the terminating resistance switches only at the nodes at both ends of the network.

When Repeater Units are used to divide the network into multiple segments, turn ON the terminating resistance switches of the nodes at both ends of each segment. When a Repeater Unit is connected to the end of a segment, turn ON the built-in terminating resistance switch of the Repeater Unit itself.

Connection examples are shown below.

T-Branch Wiring

Segment 1

Terminating resistance: ON

Terminating resistance: ON

Terminating

Segment 2

Segment 3

resistance: ON

 

 

Terminating resistance is turned ON at both ends of each segment. (Repeater Units are also equipped with a built-in terminating resistance switch.)

Terminating resistance: ON

Terminating resistance: ON

Terminating resistance: ON

CS1W-RPT01

Repeater Unit

Long-distance Wiring

Terminating

Terminating

Terminating

resistance: ON

resistance: ON

resistance: ON

 

Segment 1

 

Segment 2

Segment 3

Terminating

Terminating

Terminating

 

resistance: ON

resistance: ON

CS1W-RPT01

 

 

resistance: ON

 

 

 

Repeater Unit

82

Page 105
Image 105
Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1 Terminating Resistance, Branch Wiring, Long-distance Wiring