Data Links Procedures

 

 

Section 2-1

8. Start the data links.

 

 

 

 

 

 

 

 

 

 

 

 

 

Contents

 

Method

Nodes

 

Page

 

 

 

 

 

 

Start the data links.

Switch the Data link

Data link startup node

153

 

 

Start/Stop Bit (listed

(The Start Bit can be

 

 

 

below) from OFF to

 

 

 

turned ON in more

 

 

 

ON using either the

 

 

 

then one node to

 

 

 

 

Programming Device,

 

 

 

 

make sure the data

 

 

 

the user program, the

 

 

 

links start even when

 

 

 

Controller Link Sup-

 

 

 

the startup node is

 

 

 

port Software or CX-

 

 

 

down.)

 

 

 

 

Programmer.

 

 

 

 

 

 

 

 

Note a) Data link Start/Stop Bit (N= unit number):

 

 

 

CS/CJ Series:

Word 0 of DM30000 + 100

N

 

C200HX/HG/HE:

AR 0700 (operating level #0),

 

 

 

AR 0704 (operating level #1)

 

 

 

CVM1/CV Series:

Word 0 of DM 2000 + 100

N

 

CQM1H Series:

AR 0700

 

 

 

b)The data links will not start if there is an error in the data link tables in the startup node.

9.Stop the data links.

Contents

Method

Nodes

Page

 

 

 

 

Stop the data links.

Switch the Data link

Any node that is active

153

 

Start/Stop Bit (listed

in the data link

 

 

below) from OFF to

 

 

 

ON using either the

 

 

 

Programming Device,

 

 

 

the user program, the

 

 

 

Controller Link Sup-

 

 

 

port Software or CX-

 

 

 

Programmer.

 

 

Note Data link Start/Stop Bit (N= unit number):

CS/CJ Series: Word 0 of DM30000 + 100 N

C200HX/HG/HE: AR 0700 (operating level #0),

AR 0704 (operating level #1)

CVM1/CV Series: Word 0 of DM 2000 + 100 N

CQM1H Series: AR 0700

2-1-2 Automatically Setting Data Links

Data link tables can be automatically created by setting the data link mode to automatic data link table creation. Use the following procedure.

1,2,3... 1. Install and wire the Units.

Contents

Method

Nodes

Page

 

 

 

 

a. Mount the Units to

---

All nodes

59

the PLCs.

 

 

 

 

 

 

 

b. Wire the Network.

---

All nodes

66

 

 

 

 

34

Page 57
Image 57
Omron C200HW-CLK21 Automatically Setting Data Links, Start the data links, CS/CJ Series Word 0 of DM30000 + 100 ⋅