Status Area and Troubleshooting

 

 

Section 9-2

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Data link table error

The data link table data in

Refer to 5-3 Starting and

 

(CIO 1500 + 25

n, bit 1)

the CS/CJ CPU Bus Unit

Stopping Data Links and

 

is 1: ON

 

Area is damaged.

reset the data link tables

 

 

 

 

correctly. If the error occurs

 

 

 

 

again, replace the CPU

 

 

 

 

Unit.

 

 

 

 

 

 

 

 

There is an error in the

When using manually set

 

 

 

data link table settings.

data links, refer to 5-3

 

 

 

 

Starting and Stopping Data

 

 

 

 

Links and remake and set

 

 

 

 

the data link tables cor-

 

 

 

 

rectly. When manually set

 

 

 

 

data links are not being

 

 

 

 

used, delete the data link

 

 

 

 

tables.

 

 

 

 

 

Network parameter error

The network parameter

Refer to 8-1-3 Network

 

(CIO 1500 + 25

n, bit 0)

data in the CS/CJ CPU

Parameters and reset the

 

is 1: ON

 

Bus Unit Area is damaged.

data correctly. If the error

 

 

 

 

occurs again, replace the

 

 

 

 

CPU Unit.

 

 

 

 

 

 

 

 

 

Either set the EEPROM

 

 

 

 

Clear Bit in the DM Param-

 

 

 

 

eter Area to ON, or use the

 

 

 

 

Initialize network parame-

 

 

 

 

ters operation on the Main-

 

 

 

 

tenance Menu of the

 

 

 

 

Controller Link Support

 

 

 

 

Software to initialize the

 

 

 

 

network parameters and

 

 

 

 

then cycle the power sup-

 

 

 

 

ply.

 

 

 

 

 

 

 

 

There is an error in the net-

Refer to 8-1-3 Network

 

 

 

work parameter settings, or

Parameters and reset the

 

 

 

node address of the local

network parameters or the

 

 

 

node is larger then the

node address.

 

 

 

maximum address set

 

 

 

 

within the network parame-

 

 

 

 

ters.

 

 

 

 

 

 

Terminating Resistance Status: CIO 1500 + 25 (Unit No.) + 24

Terminating resistance status: 0: OFF 1: ON