Bryant 581B installation instructions Return Air Temperature or Enthalpy Sensor Mounting Location

Page 19

ECONOMI$ER IV

ECONOMI$ER IV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT (FIELD-PROVIDED)

Exhaust Set Point Adjustment

The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 32. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

Minimum Position Control

There is a minimum damper position potentiometer on the EconoMi$er IV controller. See Fig. 32. The minimum damper position maintains the minimum airflow into the building during the occupied period.

Fig. 34 — Return Air Temperature or Enthalpy

Sensor Mounting Location

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part num- ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 21. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiome- ter on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 35. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 21 and 36.

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$er IV control- ler uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sen- sor with the accessory enthalpy sensor in the same mounting location. See Fig. 21. Mount the return air enthalpy sensor in the return air duct. See Fig. 34. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 27. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV con- troller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting.

Indoor Air Quality (IAQ) Sensor Input

The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct.

Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiome- ters to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 37.

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

When using demand ventilation, the minimum damper posi- tion represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu- pied ventilation.

When demand ventilation control is not being used, the min- imum position potentiometer should be used to set the occu- pied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F temperature difference between the out- door and return-air temperatures.

To determine the minimum position setting, perform the fol- lowing procedure:

1.Calculate the appropriate mixed air temperature using the following formula:

(TO x

OA

RA

 

100 ) + (TR x

 

) = TM

100

TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air dur- ing occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.

(60 x .10) + (75 x .90) = 73.5 F

2.Disconnect the supply air sensor from terminals T and T1.

3.Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper posi- tioning is being used, make sure that the terminals are wired according to Fig. 27 and that the minimum position potentiometer is turned fully clockwise.

4.Connect 24 vac across terminals TR and TR1.

5.Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value.

6.Reconnect the supply air sensor to terminals T and T1.

Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location.

19

Image 19
Contents Provide Unit Support ContentsSafety Considerations InstallationIII. Determine Location of Drain Line and External Trap II. Field Fabricate DuctworkCRBTMPWR003A01 Roof Curb Unit Size Accessory CRRFCURB001A01CRBTMPWR001A01 CRBTMPWR002A01Positioning Install Flue HoodVI. Install GAS Piping IV. RIG and Place Unit060 Unit Operating Weight581B 036 048Physical Data 581B036-072 OUTDOOR-AIR Inlet Screens LOSS-OF-CHARGE SWITCH/LOW-PRESSUREFurnace Section Freeze Protection ThermostatBase Unit Dimensions 581B036-072 Steel Pipe Spacing of Supports Nominal Diameter Dimension Field Power SupplyField Control Wiring Heat Anticipator SettingsLow-Voltage Connections With or Without Economizer Power Wiring ConnectionsRLA LRA FLA MCA Mocp Power Exhaust MCA MocpFAN Motor Disconnect SIZE†FAN Motor Supply SIZE†LPS VIII. Adjust FACTORY-INSTALLED OptionsDisconnect Switch Perfect Humidity Dehumidification SystemManual Outdoor-Air Damper Damper Panel with Manual Outdoor-Air Damper InstalledOptional Manual Outdoor-Air Damper With Hood Attached EconoMi$er IV Standard Sensors Indoor Coil Access Panel RelocationBarometric Flow Capacity EconoMi$er IV Control Modes Supply Air Sensor Temperature/Resistance ValuesEconoMi$er IV Sensor Usage Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page 581B Fan Rpm at Motor Pulley Setting With Standard Motor IX. Adjust EVAPORATOR-FAN Speed581B Fan Rpm at Motor Pulley Setting With High-Static Motor AMP Draw Phase Continuous BHPUnit Maximum Unit Voltage 581BOutdoor Sound Power Total Unit Accessory/FIOP EconoMi$er IV Static Pressure* in. wgEvaporator-Fan Motor Data High-Static Motors 1292 1294 1175 1346 1275 1400 1147 9721265 1320 1310 1371 1419 1500 1175 1086760 666 257 778 367 871 471 952 572670 701 306 810 426 901 540 981 6511967 16491803 1470 17841049 731 967 5631008 643 805807 358 894 466 971 Rpm Bhp Watts 900 553 134782 316 870 417 948 1000 582 163740 382 643 234 762675 277 707 326919 561 800 350 904 438 999 535839 412 938 505 1030 605 879 483 974 580829 800 350 904 438 999 535 1087 640753 839 412 938 505 1030 605 1115 714General FAN Performance Notes START-UP Unit Preparation VI. Internal WiringVII. Refrigerant Service Ports PRE-START-UPXI. Main Burners CoolingXII. Heating XV. Operating Sequence XIII. Safety ReliefThermostat Input Economizer Function 581B Unit Operation Perfect Humidity Normal Design Cooling OperationVII. LOSS-OF-CHARGE Switch Service CleaningIV. ECONOMI$ER IV Adjustment VI. HIGH-PRESSURE SwitchUnit 581B To Use Cooling Charging Chart, Standard UnitLow Charge Cooling Perfect Humidity System ChargingCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating XI. COMBUSTION-AIR Blower XII. Limit SwitchXV. Replacement Parts Flue GAS PassagewaysMedium High Heat Units LOW Heat UnitsComp CAPOLR CLOLED OFF Troubleshooting Unit TroubleshootingLED Error Code Service Analysis Symptom Cause RemedyProblem Cause Remedy Heating Service AnalysisProblem Cause Remedy Cooling Service AnalysisII. ECONOMI$ER IV Troubleshooting Demand Control Enthalpy EconoMi$er IV Troubleshooting CompletionEconoMi$er IV Input/Output Logic Inputs OutputsIndex Page III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 40 pages 47.12 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.