Bryant 581B installation instructions General FAN Performance Notes

Page 33

Table 28 — Fan Performance 581B072 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

CFM

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

913

0.64

569

1010

0.80

715

1098

0.98

869

1178

1.16

1032

1252

1.35

1203

1900

952

0.73

652

1046

0.91

805

1131

1.09

965

1210

1.28

1134

1282

1.48

1311

2000

992

0.84

744

1083

1.02

903

1166

1.21

1070

1242

1.40

1245

1313

1.61

1427

2100

1032

0.95

844

1120

1.14

1010

1200

1.33

1184

1275

1.54

1365

1345

1.75

1553

2200

1073

1.07

954

1158

1.27

1127

1236

1.47

1307

1308

1.68

1495

1377

1.90

1689

2300

1114

1.21

1074

1196

1.41

1254

1272

1.62

1440

1343

1.84

1634

1409

2.07

1834

2400

1155

1.36

1204

1234

1.57

1391

1308

1.78

1584

1377

2.01

1784

1443

2.24

1990

2500

1196

1.51

1345

1273

1.73

1538

1345

1.96

1738

1412

2.19

1945

1477

2.43

2157

2600

1238

1.69

1497

1312

1.91

1697

1382

2.14

1904

1448

2.38

2117

1511

2.63

2335

2700

1280

1.87

1660

1352

2.10

1867

1420

2.34

2081

1484

2.59

2300

1546

2.84

2526

2800

1322

2.07

1835

1392

2.31

2050

1458

2.56

2270

1521

2.81

2496

2900

1364

2.28

2023

1432

2.53

2245

1496

2.78

2472

3000

1406

2.50

2224

1472

2.76

2452

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

CFM

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1322

1.56

1382

1388

1.77

1568

1451

1.98

1762

1510

2.21

1962

1568

2.44

2169

1900

1351

1.68

1495

1416

1.90

1686

1477

2.12

1885

1536

2.35

2090

1593

2.59

2302

2000

1380

1.82

1617

1444

2.04

1814

1505

2.27

2017

1563

2.51

2227

1619

2.75

2443

2100

1411

1.97

1748

1473

2.20

1950

1533

2.43

2159

1590

2.67

2374

2200

1441

2.13

1890

1503

2.36

2097

1562

2.60

2311

1618

2.85

2532

2300

1473

2.30

2041

1533

2.54

2254

1591

2.79

2474

2400

1505

2.48

2203

1564

2.73

2422

2500

1537

2.68

2376

2600

1571

2.88

2560

2700

2800

2900

3000

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Motor drive range: 1300 to 1686 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.90.

3.See below for general fan performance notes.

GENERAL FAN PERFORMANCE NOTES

1.Values include losses for filters, unit casing, and wet coils. See Fig. 38 and Table 9 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Tables 7 and 8 for additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Bryant repre- sentative to verify.

4.Interpolation is permissible. Do not extrapolate.

33

Image 33
Contents Safety Considerations ContentsInstallation Provide Unit SupportIII. Determine Location of Drain Line and External Trap II. Field Fabricate DuctworkCRBTMPWR001A01 Roof Curb Unit Size Accessory CRRFCURB001A01CRBTMPWR002A01 CRBTMPWR003A01VI. Install GAS Piping Install Flue HoodIV. RIG and Place Unit Positioning581B 036 Unit Operating Weight048 060Physical Data 581B036-072 Furnace Section LOSS-OF-CHARGE SWITCH/LOW-PRESSUREFreeze Protection Thermostat OUTDOOR-AIR Inlet ScreensBase Unit Dimensions 581B036-072 Field Control Wiring Field Power SupplyHeat Anticipator Settings Steel Pipe Spacing of Supports Nominal Diameter DimensionLow-Voltage Connections With or Without Economizer Power Wiring ConnectionsFAN Motor Power Exhaust MCA MocpDisconnect SIZE† RLA LRA FLA MCA MocpFAN Motor Supply SIZE†Disconnect Switch VIII. Adjust FACTORY-INSTALLED OptionsPerfect Humidity Dehumidification System LPSManual Outdoor-Air Damper Damper Panel with Manual Outdoor-Air Damper InstalledOptional Manual Outdoor-Air Damper With Hood Attached EconoMi$er IV Standard Sensors Indoor Coil Access Panel RelocationBarometric Flow Capacity Supply Air Sensor Temperature/Resistance Values EconoMi$er IV Control ModesEconoMi$er IV Sensor Usage Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page IX. Adjust EVAPORATOR-FAN Speed 581B Fan Rpm at Motor Pulley Setting With Standard Motor581B Fan Rpm at Motor Pulley Setting With High-Static Motor Unit Maximum Unit Voltage Phase Continuous BHP581B AMP DrawAccessory/FIOP EconoMi$er IV Static Pressure* in. wg Outdoor Sound Power Total UnitEvaporator-Fan Motor Data High-Static Motors 1265 1294 1175 1346 1275 1400 1147 9721320 1310 1371 1419 1500 1175 1086 1292670 666 257 778 367 871 471 952 572701 306 810 426 901 540 981 651 7601803 16491470 1784 19671008 643 967 563805 1049 731782 316 870 417 948 Rpm Bhp Watts 900 553 1341000 582 163 807 358 894 466 971 675 277 643 234 762 707 326 740 382839 412 938 505 1030 605 800 350 904 438 999 535879 483 974 580 919 561753 800 350 904 438 999 535 1087 640839 412 938 505 1030 605 1115 714 829General FAN Performance Notes VII. Refrigerant Service Ports VI. Internal WiringPRE-START-UP START-UP Unit PreparationCooling XI. Main BurnersXII. Heating XV. Operating Sequence XIII. Safety ReliefThermostat Input Economizer Function 581B Unit Operation Perfect Humidity Normal Design Cooling OperationIV. ECONOMI$ER IV Adjustment Service CleaningVI. HIGH-PRESSURE Switch VII. LOSS-OF-CHARGE SwitchLow Charge Cooling To Use Cooling Charging Chart, Standard UnitPerfect Humidity System Charging Unit 581BCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating XV. Replacement Parts XII. Limit SwitchFlue GAS Passageways XI. COMBUSTION-AIR BlowerMedium High Heat Units LOW Heat UnitsOLR CAPCLO CompLED Error Code Service Analysis Troubleshooting Unit TroubleshootingSymptom Cause Remedy LED OFFProblem Cause Remedy Heating Service AnalysisProblem Cause Remedy Cooling Service AnalysisII. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionInputs Outputs Demand Control EnthalpyIndex Page Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical