Bryant 581B Flue GAS Passageways, XI. COMBUSTION-AIR Blower, XII. Limit Switch, XIV. Main Burners

Page 42

E. To Use Cooling Charging Charts, Units With Perfect Humidity™ Dehumidification System

Refer to charts (Fig. 52-55) to determine the proper leaving condenser pressure and temperature.

Example (Fig. 52):

Leaving Condenser Pressure. . . . . . . . . . . . . . . . . . . .250 psig Leaving Condenser Temperature . . . . . . . . . . . . . . . . . . 105 F

NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumid- ification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed control- ler jumpered to run the fan at full speed.

X. FLUE GAS PASSAGEWAYS

To inspect the flue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section following.

2.Remove the 3 screws holding the blower housing to the flue cover.

3.Remove the flue cover to inspect the heat exchanger.

4.Clean all surfaces as required using a wire brush.

XI. COMBUSTION-AIR BLOWER

Clean periodically to ensure proper airflow and heating effi- ciency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.

To inspect blower wheel, remove draft hood and screen. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows:

1.Slide burner access panel out.

2.Remove the 5 screws that attach induced-draft motor assembly to the vestibule cover.

3.Slide the motor and blower wheel assembly out of the blower housing. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5.

4.To remove blower from the motor shaft, by remove 2 setscrews.

5.To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.

6.To reinstall, reverse the procedure outlined above.

XII. LIMIT SWITCH

Remove blower access panel (Fig. 7). Limit switch is located on the fan deck.

XIII. BURNER IGNITION

Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 12). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. The LED can be observed through the viewport. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the evaporator fan on/off times delay will be reset. During servic- ing, refer to the label on the control box cover or Table 31 for an explanation of LED error code descriptions.

If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.

Table 31 — LED Error Code Description*

LED INDICATION

ERROR CODE DESCRIPTION

ON

Normal Operation

OFF

Hardware Failure

1 Flash†

Evaporator Fan On/Off Delay Modified

2 Flashes

Limit Switch Fault

3 Flashes

Flame Sense Fault

4 Flashes

4 Consecutive Limit Switch Faults

5 Flashes

Ignition Lockout Fault

6 Flashes

Induced-Draft Motor Fault

7 Flashes

Rollout Switch Fault

8 Flashes

Internal Control Fault

9 Flashes

Software Lockout

LEGEND

LED — Light-Emitting Diode

*A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.

†Indicates a code that is not an error. The unit will continue to operate when this code is displayed.

IMPORTANT: Refer to Troubleshooting Tables 32-36 for additional information.

XIV. MAIN BURNERS

At the beginning of each heating season, inspect for deteriora- tion or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.

CAUTION: When working on gas train, do not hit or plug orifice spuds.

A. Removal and Replacement of Gas Train (See Fig. 56 and 57)

1.Shut off manual gas valve.

2.Shut off power to unit tag disconnect.

3.Remove compressor access panel.

4.Slide out burner compartment side panel.

5.Disconnect gas piping at unit gas valve.

6.Remove wires connected to gas valve. Mark each wire.

7.Remove induced-draft motor, ignitor, and sensor wires at the Integrated Gas Unit Controller (IGC).

8.Remove the 2 screws that attach the burner rack to the vestibule plate.

9.Remove the gas valve bracket.

10.Slide the burner tray out of the unit (Fig. 57).

11.To reinstall, reverse the procedure outlined above.

B. Cleaning and Adjustment

1.Remove burner rack from unit as described above.

2.Inspect burners and, if dirty, remove burners from rack.

3.Using a soft brush, clean burners and cross-over port as required.

4.Adjust spark gap. See Fig. 58.

5.Reinstall burners on rack.

6.Reinstall burner rack as described above.

XV. REPLACEMENT PARTS

A complete list of replacement parts may be obtained from your Bryant distributor upon request. Refer to Fig. 59 for a typical unit wiring schematic.

42

Image 42
Contents Installation ContentsSafety Considerations Provide Unit SupportII. Field Fabricate Ductwork III. Determine Location of Drain Line and External TrapCRBTMPWR002A01 Roof Curb Unit Size Accessory CRRFCURB001A01CRBTMPWR001A01 CRBTMPWR003A01IV. RIG and Place Unit Install Flue HoodVI. Install GAS Piping Positioning048 Unit Operating Weight581B 036 060Physical Data 581B036-072 Freeze Protection Thermostat LOSS-OF-CHARGE SWITCH/LOW-PRESSUREFurnace Section OUTDOOR-AIR Inlet ScreensBase Unit Dimensions 581B036-072 Heat Anticipator Settings Field Power SupplyField Control Wiring Steel Pipe Spacing of Supports Nominal Diameter DimensionPower Wiring Connections Low-Voltage Connections With or Without EconomizerDisconnect SIZE† Power Exhaust MCA MocpFAN Motor RLA LRA FLA MCA MocpSIZE† FAN Motor SupplyPerfect Humidity Dehumidification System VIII. Adjust FACTORY-INSTALLED OptionsDisconnect Switch LPSDamper Panel with Manual Outdoor-Air Damper Installed Manual Outdoor-Air DamperOptional Manual Outdoor-Air Damper With Hood Attached Indoor Coil Access Panel Relocation EconoMi$er IV Standard SensorsBarometric Flow Capacity Supply Air Sensor Temperature/Resistance Values EconoMi$er IV Control ModesEconoMi$er IV Sensor Usage Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page IX. Adjust EVAPORATOR-FAN Speed 581B Fan Rpm at Motor Pulley Setting With Standard Motor581B Fan Rpm at Motor Pulley Setting With High-Static Motor 581B Phase Continuous BHPUnit Maximum Unit Voltage AMP DrawAccessory/FIOP EconoMi$er IV Static Pressure* in. wg Outdoor Sound Power Total UnitEvaporator-Fan Motor Data High-Static Motors 1320 1310 1371 1419 1500 1175 1086 1294 1175 1346 1275 1400 1147 9721265 1292701 306 810 426 901 540 981 651 666 257 778 367 871 471 952 572670 7601470 1784 16491803 1967805 967 5631008 643 1049 7311000 582 163 Rpm Bhp Watts 900 553 134782 316 870 417 948 807 358 894 466 971707 326 643 234 762675 277 740 382879 483 974 580 800 350 904 438 999 535839 412 938 505 1030 605 919 561839 412 938 505 1030 605 1115 714 800 350 904 438 999 535 1087 640753 829General FAN Performance Notes PRE-START-UP VI. Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationCooling XI. Main BurnersXII. Heating XIII. Safety Relief XV. Operating SequencePerfect Humidity Normal Design Cooling Operation Thermostat Input Economizer Function 581B Unit OperationVI. HIGH-PRESSURE Switch Service CleaningIV. ECONOMI$ER IV Adjustment VII. LOSS-OF-CHARGE SwitchPerfect Humidity System Charging To Use Cooling Charging Chart, Standard UnitLow Charge Cooling Unit 581BCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating Flue GAS Passageways XII. Limit SwitchXV. Replacement Parts XI. COMBUSTION-AIR BlowerLOW Heat Units Medium High Heat UnitsCLO CAPOLR CompSymptom Cause Remedy Troubleshooting Unit TroubleshootingLED Error Code Service Analysis LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis Problem Cause RemedyII. ECONOMI$ER IV Troubleshooting Inputs Outputs EconoMi$er IV Troubleshooting CompletionEconoMi$er IV Input/Output Logic Demand Control EnthalpyIndex Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 40 pages 47.12 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.