Bryant 581B Indoor Coil Access Panel Relocation, EconoMi$er IV Standard Sensors

Page 16

IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.

3.The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bot- tom of the indoor coil access panel. See Fig. 24.

4.Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 25.

5.Remove the shipping tape holding the economizer barometric relief damper in place.

6.Insert the hood divider between the hood sides. See Fig. 25 and 26. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.

SIDE

PANEL

 

TOP

 

SIDE

 

PANEL

 

CAULK

 

HERE

INDOOR

INDOOR

COIL

COIL

ACCESS

ACCESS

PANEL

PANEL

Fig. 24 — Indoor Coil Access Panel Relocation

TOP

PANEL

INDOOR COIL

ACCESS PANEL

LEFT

 

HOOD

SCREW

SIDE

B

 

19 1/16”

33 3/8”

HOOD DIVIDER

Fig. 25 — Outdoor-Air Hood Construction

17 1/4”

DIVIDER

OUTSIDE

AIR

HOOD

CLEANABLE

ALUMINUM FILTER

FILTER

BAROMETRIC RELIEF

FILTER CLIP

Fig. 26 — Filter Installation

7.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bot- tom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 26.

8.Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 24.

9.Replace the filter access panel.

10.Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 27.

Barometric flow capacity is shown in Fig. 28. Outdoor air leakage is shown in Fig. 29. Return air pressure drop is shown in Fig. 30.

F. EconoMi$er IV Standard Sensors

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 21. The operating range of temperature measurement is 40 to 100 F.

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 31. This sensor is factory installed. The operating range of temperature measurement is 0° to 158 F. See Table 3 for sensor tempera- ture/resistance values.

The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.

Outdoor Air Lockout Sensor

The EconoMi$er IV is equipped with an ambient tempera- ture lockout switch located in the outdoor airstream which is used to lockout the compressors below a 42 F ambient tem- perature. See Fig. 21.

16

Image 16
Contents Contents Safety ConsiderationsInstallation Provide Unit SupportII. Field Fabricate Ductwork III. Determine Location of Drain Line and External TrapRoof Curb Unit Size Accessory CRRFCURB001A01 CRBTMPWR001A01CRBTMPWR002A01 CRBTMPWR003A01Install Flue Hood VI. Install GAS PipingIV. RIG and Place Unit PositioningUnit Operating Weight 581B 036048 060Physical Data 581B036-072 LOSS-OF-CHARGE SWITCH/LOW-PRESSURE Furnace SectionFreeze Protection Thermostat OUTDOOR-AIR Inlet ScreensBase Unit Dimensions 581B036-072 Field Power Supply Field Control WiringHeat Anticipator Settings Steel Pipe Spacing of Supports Nominal Diameter DimensionPower Wiring Connections Low-Voltage Connections With or Without EconomizerPower Exhaust MCA Mocp FAN MotorDisconnect SIZE† RLA LRA FLA MCA MocpSIZE† FAN Motor Supply VIII. Adjust FACTORY-INSTALLED Options Disconnect Switch Perfect Humidity Dehumidification System LPSDamper Panel with Manual Outdoor-Air Damper Installed Manual Outdoor-Air DamperOptional Manual Outdoor-Air Damper With Hood Attached Indoor Coil Access Panel Relocation EconoMi$er IV Standard SensorsBarometric Flow Capacity EconoMi$er IV Control Modes Supply Air Sensor Temperature/Resistance ValuesEconoMi$er IV Sensor Usage Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page 581B Fan Rpm at Motor Pulley Setting With Standard Motor IX. Adjust EVAPORATOR-FAN Speed581B Fan Rpm at Motor Pulley Setting With High-Static Motor Phase Continuous BHP Unit Maximum Unit Voltage581B AMP DrawOutdoor Sound Power Total Unit Accessory/FIOP EconoMi$er IV Static Pressure* in. wgEvaporator-Fan Motor Data High-Static Motors 1294 1175 1346 1275 1400 1147 972 12651320 1310 1371 1419 1500 1175 1086 1292666 257 778 367 871 471 952 572 670701 306 810 426 901 540 981 651 7601649 18031470 1784 1967967 563 1008 643805 1049 731Rpm Bhp Watts 900 553 134 782 316 870 417 9481000 582 163 807 358 894 466 971643 234 762 675 277707 326 740 382800 350 904 438 999 535 839 412 938 505 1030 605879 483 974 580 919 561800 350 904 438 999 535 1087 640 753839 412 938 505 1030 605 1115 714 829General FAN Performance Notes VI. Internal Wiring VII. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationXI. Main Burners CoolingXII. Heating XIII. Safety Relief XV. Operating SequencePerfect Humidity Normal Design Cooling Operation Thermostat Input Economizer Function 581B Unit OperationService Cleaning IV. ECONOMI$ER IV AdjustmentVI. HIGH-PRESSURE Switch VII. LOSS-OF-CHARGE SwitchTo Use Cooling Charging Chart, Standard Unit Low Charge CoolingPerfect Humidity System Charging Unit 581BCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating XII. Limit Switch XV. Replacement PartsFlue GAS Passageways XI. COMBUSTION-AIR BlowerLOW Heat Units Medium High Heat UnitsCAP OLRCLO CompTroubleshooting Unit Troubleshooting LED Error Code Service AnalysisSymptom Cause Remedy LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis Problem Cause RemedyII. ECONOMI$ER IV Troubleshooting EconoMi$er IV Troubleshooting Completion EconoMi$er IV Input/Output LogicInputs Outputs Demand Control EnthalpyIndex Page START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 40 pages 47.12 Kb Manual 64 pages 44.36 Kb