Bryant 581B installation instructions Perfect Humidity Normal Design Cooling Operation

Page 37

Hot Gas Reheat Mode

When the humidity levels in the space require humidity con- trol, a hot gas solenoid valve (specific to hot gas reheat mode only) will open to bypass a portion of hot gas refrigerant around the condenser coil (see Fig. 43).

This hot gas will mix with liquid refrigerant leaving the con- denser coil and flow to the subcooling/reheat dehumidification coil. Now the conditioned air coming off the evaporator will be cooled and dehumidified, but will be warmed to neutral conditions (72 F to 75 F) by the subcooling/reheat dehumidification coil.

The net effect of the rooftop when in hot gas reheat mode is to provide nearly all latent capacity removal from the space when sensible loads diminish (when outdoor temperature conditions are moderate). When in hot gas reheat mode, the unit will operate to provide mostly latent capacity and extremely low sensible heat ratio capability.

Similar to the subcooling mode of operation, hot gas reheat mode operates only when the outside-air temperature is warmer than 40 F. Below this temperature, a factory-installed outside air temperature switch will lock out this mode of operation.

See Table 30 for the dehumidification system sequence of operation.

Fig. 41 — Perfect Humidity™ Normal

Design Cooling Operation

Fig. 42 — Perfect Humidity Subcooling

Mode Operation

Fig. 43 — Perfect Humidity Hot Gas

Reheat Mode Operation

Table 30 — Perfect Humidity Dehumidification System Sequence of Operation and

System Response — Single Compressor Unit

THERMOSTAT INPUT

ECONOMIZER FUNCTION

 

 

 

 

581B UNIT OPERATION

H

Y1

 

Y2

OAT. < Economizer Set Point

Economizer

 

Comp. 1

 

Subcooling Mode

Hot Gas Reheat Mode

Off

 

 

 

Normal Operation

 

 

On

On

 

On

No

 

Off

 

On

 

Yes

No

On

On

 

Off

No

 

Off

 

On

 

Yes

No

On

On

 

On

Yes

 

On

 

On

 

Yes

No

On

On

 

Off

Yes

 

On

 

On

 

No

Yes

On

Off

 

Off

No

 

Off

 

On

 

No

Yes

 

LEGEND

 

 

 

NOTE: On a thermostat call for W1, all cooling and dehumidification will

OAT — Outdoor Air Temperature

 

be off.

 

 

 

 

37

Image 37
Contents Safety Considerations ContentsInstallation Provide Unit SupportIII. Determine Location of Drain Line and External Trap II. Field Fabricate DuctworkCRBTMPWR001A01 Roof Curb Unit Size Accessory CRRFCURB001A01CRBTMPWR002A01 CRBTMPWR003A01VI. Install GAS Piping Install Flue HoodIV. RIG and Place Unit Positioning581B 036 Unit Operating Weight048 060Physical Data 581B036-072 Furnace Section LOSS-OF-CHARGE SWITCH/LOW-PRESSUREFreeze Protection Thermostat OUTDOOR-AIR Inlet ScreensBase Unit Dimensions 581B036-072 Field Control Wiring Field Power SupplyHeat Anticipator Settings Steel Pipe Spacing of Supports Nominal Diameter DimensionLow-Voltage Connections With or Without Economizer Power Wiring ConnectionsFAN Motor Power Exhaust MCA MocpDisconnect SIZE† RLA LRA FLA MCA MocpFAN Motor Supply SIZE†Disconnect Switch VIII. Adjust FACTORY-INSTALLED OptionsPerfect Humidity Dehumidification System LPSManual Outdoor-Air Damper Damper Panel with Manual Outdoor-Air Damper InstalledOptional Manual Outdoor-Air Damper With Hood Attached EconoMi$er IV Standard Sensors Indoor Coil Access Panel RelocationBarometric Flow Capacity EconoMi$er IV Control Modes Supply Air Sensor Temperature/Resistance ValuesEconoMi$er IV Sensor Usage Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page 581B Fan Rpm at Motor Pulley Setting With Standard Motor IX. Adjust EVAPORATOR-FAN Speed581B Fan Rpm at Motor Pulley Setting With High-Static Motor Unit Maximum Unit Voltage Phase Continuous BHP581B AMP DrawOutdoor Sound Power Total Unit Accessory/FIOP EconoMi$er IV Static Pressure* in. wgEvaporator-Fan Motor Data High-Static Motors 1265 1294 1175 1346 1275 1400 1147 9721320 1310 1371 1419 1500 1175 1086 1292670 666 257 778 367 871 471 952 572701 306 810 426 901 540 981 651 7601803 16491470 1784 19671008 643 967 563805 1049 731782 316 870 417 948 Rpm Bhp Watts 900 553 1341000 582 163 807 358 894 466 971675 277 643 234 762707 326 740 382839 412 938 505 1030 605 800 350 904 438 999 535879 483 974 580 919 561753 800 350 904 438 999 535 1087 640839 412 938 505 1030 605 1115 714 829General FAN Performance Notes VII. Refrigerant Service Ports VI. Internal WiringPRE-START-UP START-UP Unit PreparationXI. Main Burners CoolingXII. Heating XV. Operating Sequence XIII. Safety ReliefThermostat Input Economizer Function 581B Unit Operation Perfect Humidity Normal Design Cooling OperationIV. ECONOMI$ER IV Adjustment Service CleaningVI. HIGH-PRESSURE Switch VII. LOSS-OF-CHARGE SwitchLow Charge Cooling To Use Cooling Charging Chart, Standard UnitPerfect Humidity System Charging Unit 581BCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating XV. Replacement Parts XII. Limit SwitchFlue GAS Passageways XI. COMBUSTION-AIR BlowerMedium High Heat Units LOW Heat UnitsOLR CAPCLO CompLED Error Code Service Analysis Troubleshooting Unit TroubleshootingSymptom Cause Remedy LED OFFProblem Cause Remedy Heating Service AnalysisProblem Cause Remedy Cooling Service AnalysisII. ECONOMI$ER IV Troubleshooting EconoMi$er IV Input/Output Logic EconoMi$er IV Troubleshooting CompletionInputs Outputs Demand Control EnthalpyIndex Page Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 40 pages 47.12 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.