Bryant 581B Service Cleaning, II. Lubrication, IV. ECONOMI$ER IV Adjustment, Viii. Freeze-Stat

Page 38

SERVICE

CAUTION: When servicing unit, shut off all elec- trical power to unit and install lockout tag to avoid shock hazard or injury from rotating parts.

I. CLEANING

Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.

A.Evaporator Coil

1.Turn unit power off, tag disconnect. Remove evapora- tor coil access panel.

2.If economizer or two-position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws. Refer to accessory econo- mizer installation instructions or Optional EconoMi$er IV section on page 15 for additional information.

3.Slide filters out of unit.

4.Clean coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material. Flush condensate pan after completion.

5.Reinstall economizer and filters.

6.Reconnect wiring.

7.Replace access panels.

B.Condenser Coil

Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor air conditions.

One-Row Coil

Wash coil with commercial coil cleaner. It is not necessary to remove top panel.

2-Row Coils

Clean coil as follows:

1.Turn off unit power, tag disconnect.

2.Remove top panel screws on condenser end of unit.

3.Remove condenser coil corner post. See Fig. 44. To hold top panel open, place coil corner post between top panel and center post. See Fig. 45.

4.Remove screws securing coil to compressor plate and compressor access panel.

5.Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 46.

6.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

7.Secure inner and outer coil rows together with a field- supplied fastener.

8.Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.

C.Condensate Drain

Check and clean each year at start of cooling season. In win- ter, keep drain dry or protect against freeze-up.

D. Filters

Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.

E. Outdoor-Air Inlet Screens

Clean screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screen.

II. LUBRICATION

A. Compressors

Each compressor is charged with correct amount of oil at the factory.

B. Fan Motor Bearings

Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of con- denser-fan or evaporator-fan motors is required.

III. CONDENSER-FAN ADJUSTMENT (Fig. 47)

Shut off unit power supply. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 47. Tighten setscrews and replace condenser-fan assembly.

IV. ECONOMI$ER IV ADJUSTMENT

Refer to Optional EconoMi$er IV section on page 15.

V. EVAPORATOR FAN BELT INSPECTION

Check condition of evaporator belt or tension during heating and cooling inspections or as conditions require. Replace belt or adjust as necessary.

VI. HIGH-PRESSURE SWITCH

The high-pressure switch contains a Schrader core depressor, and is located on the compressor hot gas line. This switch opens at 428 psig and closes at 320 psig. No adjustments are necessary.

VII. LOSS-OF-CHARGE SWITCH

The loss-of-charge switch contains a Schrader core depressor, and is located on the compressor liquid line. This switch opens at 7 psig and closes at 22 psig. No adjustments are necessary.

VIII. FREEZE-STAT

The freeze-stat is a bimetal temperature-sensing switch that is located on the “hair-pin” end of the evaporator coil. The switch protects the evaporator coil from freeze-up due to lack of airflow. The switch opens at 30 F and closes at 45 F. No adjustments are necessary.

IX. REFRIGERANT CHARGE

Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to HVAC Servicing Procedures literature available at your local distributor and the follow- ing procedures.

Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 10 minutes before checking or adjusting refrigerant charge.

An accurate superheat, thermocouple-type or thermistor- type thermometer, and a gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.

38

Image 38
Contents Installation ContentsSafety Considerations Provide Unit SupportII. Field Fabricate Ductwork III. Determine Location of Drain Line and External TrapCRBTMPWR002A01 Roof Curb Unit Size Accessory CRRFCURB001A01CRBTMPWR001A01 CRBTMPWR003A01IV. RIG and Place Unit Install Flue HoodVI. Install GAS Piping Positioning048 Unit Operating Weight581B 036 060Physical Data 581B036-072 Freeze Protection Thermostat LOSS-OF-CHARGE SWITCH/LOW-PRESSUREFurnace Section OUTDOOR-AIR Inlet ScreensBase Unit Dimensions 581B036-072 Heat Anticipator Settings Field Power SupplyField Control Wiring Steel Pipe Spacing of Supports Nominal Diameter DimensionPower Wiring Connections Low-Voltage Connections With or Without EconomizerDisconnect SIZE† Power Exhaust MCA MocpFAN Motor RLA LRA FLA MCA MocpSIZE† FAN Motor SupplyPerfect Humidity Dehumidification System VIII. Adjust FACTORY-INSTALLED OptionsDisconnect Switch LPSDamper Panel with Manual Outdoor-Air Damper Installed Manual Outdoor-Air DamperOptional Manual Outdoor-Air Damper With Hood Attached Indoor Coil Access Panel Relocation EconoMi$er IV Standard SensorsBarometric Flow Capacity EconoMi$er IV Sensor Usage Supply Air Sensor Temperature/Resistance ValuesEconoMi$er IV Control Modes Return Air Temperature or Enthalpy Sensor Mounting Location Enthalpy Changeover Set Points Page 581B Fan Rpm at Motor Pulley Setting With High-Static Motor IX. Adjust EVAPORATOR-FAN Speed581B Fan Rpm at Motor Pulley Setting With Standard Motor 581B Phase Continuous BHPUnit Maximum Unit Voltage AMP DrawEvaporator-Fan Motor Data High-Static Motors Accessory/FIOP EconoMi$er IV Static Pressure* in. wgOutdoor Sound Power Total Unit 1320 1310 1371 1419 1500 1175 1086 1294 1175 1346 1275 1400 1147 9721265 1292701 306 810 426 901 540 981 651 666 257 778 367 871 471 952 572670 7601470 1784 16491803 1967805 967 5631008 643 1049 7311000 582 163 Rpm Bhp Watts 900 553 134782 316 870 417 948 807 358 894 466 971707 326 643 234 762675 277 740 382879 483 974 580 800 350 904 438 999 535839 412 938 505 1030 605 919 561839 412 938 505 1030 605 1115 714 800 350 904 438 999 535 1087 640753 829General FAN Performance Notes PRE-START-UP VI. Internal WiringVII. Refrigerant Service Ports START-UP Unit PreparationXII. Heating CoolingXI. Main Burners XIII. Safety Relief XV. Operating SequencePerfect Humidity Normal Design Cooling Operation Thermostat Input Economizer Function 581B Unit OperationVI. HIGH-PRESSURE Switch Service CleaningIV. ECONOMI$ER IV Adjustment VII. LOSS-OF-CHARGE SwitchPerfect Humidity System Charging To Use Cooling Charging Chart, Standard UnitLow Charge Cooling Unit 581BCooling Charging Chart, Standard 581B036 Condenser FAN Must be Operating Flue GAS Passageways XII. Limit SwitchXV. Replacement Parts XI. COMBUSTION-AIR BlowerLOW Heat Units Medium High Heat UnitsCLO CAPOLR CompSymptom Cause Remedy Troubleshooting Unit TroubleshootingLED Error Code Service Analysis LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis Problem Cause RemedyII. ECONOMI$ER IV Troubleshooting Inputs Outputs EconoMi$er IV Troubleshooting CompletionEconoMi$er IV Input/Output Logic Demand Control EnthalpyIndex Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 40 pages 47.12 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.