GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)

569D072-120, 576C120, 569F120

J.Special Features:

1.Low-Ambient Temperature Control Accessory:

Low-ambient control shall be available as a factory- installed option or a field-installed accessory and shall regulate speed of condenser-fan motor in response to the saturated condensing temperature of the unit. The control shall maintain correct con- densing pressure at outdoor temperatures down to –20 F (fan motor change required for 569D and 576C units).

2. Optional Condenser Coil Materials:

a. Pre-Coated Aluminum-Fin Coils:

Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal envi- ronments. Coating shall be applied to the alumi- num fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.

b. E-Coated Aluminum-Fin Coils:

Shall have a flexible epoxy polymer coating uni- formly applied to all coil surface areas without material bridging between fins. Coating process shall ensure complete coil encapsulation. Color shall be high gloss black with gloss requirements of 60° of 65-90% per ASTM D523-89. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges. Superior hardness char- acteristics of 2H per ASTM D3363-92A and cross hatch adhesion of 4B-5B per ASTM D3359-93. Impact resistance shall be up to 160 in./lb (ASTM D2794-93). Humidity and water immersion resis- tance shall be up to a minimum of 1000 and

250hours respectively (ASTM-D2247-92 and ASTM D870-92). Corrosion durability shall be con- firmed through testing to no less than 1000 hours salt spray per ASTM B117-90. Coil construction

shall be aluminum-fins mechanically bonded to copper tubes.

3.Thermostat Control Accessory:

a.Commercial Electronic Thermostat with 7-day timeclock, auto-changeover, multi-stage capabil- ity, and large LCD temperature display.

b.Commercial Electronic Non-programmable Ther- mostat with auto-changeover, multi-stage capacity, and large LCD display.

4.Hail Guard Accessory:

Hail guard package shall protect coils against dam- age from hail and other flying debris.

5. Condenser Coil Grille Accessory:

Grille shall add decorative appearance to unit and protect condenser coil after installation.

6. Electric Solenoid Unloader Accessory:

Electric unloader valve piston, coil, and hardware shall be supplied to convert the pressure-operated compressor unloader to electric unloading (576C120 only).

7. Unit-Mounted, Non-Fused Disconnect Switch:

Shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall provide unit power shutoff. Shall be accessible from outside the unit and shall provide power off lockout capability. Not to be used when rooftop electrical rating exceeds 80 amperes.

8. Convenience Outlet:

Shall be factory-installed and internally mounted with easily accessible 115-v female receptacle. Shall include 15 amp GFI receptacle with independent fuse protection. Voltage required to operate conve- nience outlet shall be provided by a factory-installed step-down transformer. Shall be accessible from out- side the unit.

30

Image 30
Contents FEATURES/BENEFITS 524A AIR-HANDLING UnitsTable of Contents Estimated Sound Power Levels Lw 524A072-300 ARI* Capacity RatingsSound LEVELS, dB 569D/576C/566D,E FIELD-INSTALLED Accessories Options and Accessories566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED Options Options and AccessoriesOptions and Accessories 524A-B, C FACTORY-INSTALLED OptionsCommercial Programmable Non-Programmable Thermostat 524A with Discharge Plenum, Return Grille, and Subbase 524A with Hot Water or Steam Coil524A with Economizer 524A with Condensate Trap II Select Condensing Unit AIR-HANDLER Combination Selection ProcedureIV Determine FAN RPM and BHP Brake Horsepower III Determine Sizes of Liquid and Suction LinesControls Operating SequencesTypical Wiring Schematics 569D090, 208/230-3-360 and 460-3-60 UnitsTypical Wiring Schematics 576C120, 208/230-3-60 and 460-3-60 UnitsModel Number Nomenclature Physical Data 569D072-120, 576C120, 569F120 UnitsUnit Dimensions 569D072-120, 576C120Dimensions 569D072Performance Data Condensing Unit Ratings569D072/524A-C072 with HIGH-CAPACITY 4-ROW Coil Performance DataCombination Ratings SHCCombination Ratings 569D072/524A-C090 with HIGH-CAPACITY 4-ROW Coil2400 3000 3750 Condenser Temp F Unit 569D090569D090/524A-C072 with HIGH-CAPACITY 4-ROW Coil 569D090/524A-B072 with Standard 3-ROW Coil569D090/524A-C090 with HIGH-CAPACITY 4-ROW Coil 2205 3000 3750 Condenser569D090/524A-B090 with Standard 3-ROW Coil 3000 4000 5000 Condenser Unit 569D120569D120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 569D120/524A-B120 with Standard 3-ROW Coil569D120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 3750 5000 6250 Condenser569D120/524A-B150 with Standard 3-ROW Coil Unit 576C120 576C120/524A-C120 with HIGH-CAPACITY 4-ROW Coil576C120/524A-B120 with Standard 3-ROW Coil 576C120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 576C120/524A-B150 with Standard 3-ROW CoilUnit 569F120 569F120/524A-C120 with HIGH-CAPACITY 4-ROW Coil569F120/524A-B120 with Standard 3-ROW Coil 569F120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 569F120/524A-B150 with Standard 3-ROW CoilElectrical Data Maximum Refrigerant Charge Operating Limits Minimum OUTDOOR-AIR Operating Temperature Application Data 569D072-120, 576C090-120, 569F120 Refrigerant Piping SizesTypical Piping and Wiring Rooftop Installation 569D072-120, 576C120Part 1 General Guide Specifications 569D072-120, 576C120Commercial AIR-COOLED Condensing Units Part 2 ProductsGuide Specifications 569D072-120, 576C120 Guide Specifications 569F120 Guide Specifications 569F120 566D E X 150 566D150-240 Units Physical Data 566E150-240 UnitsDimensions Dimensions 566D150-240, 566E150-240 Aluminum Coil UnitAir Temperature Entering Condenser F 100 105 115 Edb Unit 566D150566D150/524A-C150 with High Capacity 4-ROW Coil 566D150/524A-B150 with Standard 3-ROW Coil566D150/524A-C180 with High Capacity 4-ROW Coil 4500 6000 7500 Condenser566D150/524A-B180 with Standard 3-ROW Coil Unit 566D180 566D180/524A-C180 with HIGH-CAPACITY 4-ROW Coil566D180/524A-B180 with Standard 3-ROW Coil 566D180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 000 10,000 Condenser566D180/524A-B240 with Standard 3-ROW Coil 500 10,000 12,500 Condenser Unit 566D240566D240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566D240/524A-B300 with Standard 3-ROW CoilUnit 566E150 566E150/524A-C120 with HIGH-CAPACITY 4-ROW Coil566E150/524A-B120 with Standard 3-ROW Coil 566E150/524A-C150 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B150 with Standard 3-ROW Coil566E150/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B180 with Standard 3-ROW CoilUnit 566E180 566E180/524A-C150 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B150 with Standard 3-ROW Coil 566E180/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B180 with Standard 3-ROW Coil566E180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B240 with Standard 3-ROW CoilUnit 566E240 566E240/524A-C240 with HIGH-CAPACITY 4-ROW Coil566E240/524A-B240 with Standard 3-ROW Coil 566E240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566E240/524A-B300 with Standard 3-ROW CoilNominal Voltage Compressor Application Data 566D150-240, 566E150-240 Minimum OUTDOOR-AIR Operating Temperature 566D150-240 UnitsMinimum OUTDOOR-AIR Operating Temperature 566E150-240 Units Operating LimitsFace-Split Coil Suction Liquid Line Piping Refrigerant Piping Sizes Double Suction RisersSuction Line Piping Multiple Condensing Unit Arrangements 566D, 566E150-240Rooftop Installation 566D150-240 Typical Piping and Wiring Ground Level Installation 566D150-240Guide Specifications 566D150-240, 566E150-240 Guide Specifications 566D150-240, 566E150-240 Coil Option 524A P B 120 000 GCVoltage Nominal Cooling Tons 072524A-B,C Units Unit 524AUnit Unit Weight 524A-B,C072-120524A-B,C150-240 524A-B,C300 B300 1020 C300 1050524A-B FAN Performance Data 0.0-1.2 in. wg ESP Unit Airflow524A-B FAN Performance Data 1.4-2.4 in. wg ESP FAN Performance Data 524A-C with High Capacity Coil 1.2 in. wg ESPFAN Performance Data 524A-C With High Capacity Coil 1.4-2.4 in. wg ESPAccessory Plenum AIR Throw Data Accessory Pressure Drop in. wgFACTORY-SUPPLIED Filter Pressure Drop ROW Unit Airflow Hydronic Heating CapacitiesHeating Correction Factors HOT Water COIL†524A-B PH-Hz Unit Voltage FAN Motor Power Supply524A-B,C Standard Motors FLA MocpElectrical Data 524A-B,C Alternate MotorsFLA Electric Heater Data Electric Heater Data CAELHEAT018A00 CAELHEAT016A00CAELHEAT017A00 CAELHEAT019A00CAELHEAT027A00 CAELHEAT025A00CAELHEAT026A00 CAELHEAT028A00CAELHEAT036A00 CAELHEAT034A00CAELHEAT035A00 CAELHEAT037A00FAN Motor Data FACTORY-INSTALLED Nozzle and Distributor DataApplication Data 524A Standard Motor Unit Size 524AApplication Data 524A FAN Motor DataStandard Drive Data MEDIUM-STATIC Drive Data HIGH-STATIC Drive DataGuide Specifications 524A Commercial Packaged AIR-HANDLING UnitGuide Specifications 524A Air Discharge PlenumIndex