APPLICATION DATA — 566D150-240, 566E150-240

1.INSTALLATION — Select equipment to match or to be slightly less than peak load. This provides better humidity control, less unit cycling, and less part-load operation.

When selecting vapor line sizes, oil return must be evalu- ated, particularly at part-load conditions.

The indoor fan must always be operating when outdoor unit is operating.

Ductwork should be sized according to unit size, not build- ing load.

To minimize the possibility of air recirculation, avoid the use of concentric supply/return grilles.

Indoor equipment should be selected at no less than 300 cfm/ton.

OPERATING LIMITS

Maximum Outdoor

115 F

Minimum Outdoor Ambient

See Minimum Outdoor-Air

Operating Temperature

 

table below.

Minimum Return-Air

55 F

Temperature

 

Maximum Return-Air

95 F

Temperature

 

Normal Acceptable Saturation

25 to 55 F

Suction Temperature Range

 

Maximum Discharge

295 F

Temperature

 

Minimum Discharge Superheat

60 F

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566D150-240 UNITS

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

OUTDOOR-AIR

 

 

 

 

 

FULL LOAD

 

OPERATING

 

240-

 

UNIT

NO. OF

 

 

 

(%)

 

 

With

 

 

 

566D

CYLINDERS

CAPACITY

TEMPERATURE (F)

 

566D/E150

 

 

Base

 

Low-Ambient

 

 

 

6

100

 

 

 

 

20

 

 

 

 

 

 

 

Unit

 

Control

 

 

 

 

6

100

20

 

 

 

 

 

150

4

67

31

 

 

 

 

 

 

2*

33*

40

 

 

 

 

 

180

 

 

 

 

–20

 

 

 

4

67

33

 

 

 

 

 

 

 

 

 

 

2*

33*

47

 

 

 

 

 

240

4

100

15

 

 

 

 

 

2

50

20

 

 

 

 

 

 

 

 

*Requires field-installed unloader.

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566E150-240 UNITS

 

 

 

 

 

 

 

MINIMUM

 

 

FULL LOAD

 

 

 

OUTDOOR-AIR

UNIT

 

 

SATURATED COND

TEMPERATURE (F)

566E

 

CAPACITY

 

TEMPERATURE (F)

 

 

 

 

(%)

 

Base

 

With

 

 

 

 

 

 

Low-Ambient

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

Control

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

180

 

100/50

 

 

90

50

 

–20

240

 

 

 

 

 

 

 

 

 

 

LIQUID LINE DATA — 566D150-240 UNITS

 

 

 

 

 

 

 

 

MAX

 

LIQUID LINE

UNIT

 

Max Allow.

 

 

Max Allow.

ALLOW.

 

 

Pressure

 

 

Temp

566D

LIFT

 

 

 

 

Drop

 

 

Loss

 

 

(ft)

 

 

 

 

 

 

(psi)

 

 

(°F)

 

 

 

 

 

 

 

15067

180

82

7

2

24087

NOTE: Data above is for units operating at 45 F saturated suction and 95 F entering air.

LIQUID LINE DATA — 566E150-240 UNITS

 

MAX

LIQUID LINE

UNIT

ALLOW.

Max Allow.

Max Allow.

Pressure

Temp

566E

LIFT

Drop

Loss

 

(ft)

 

(psi)

(°F)

 

 

150

60

7

2

180

240

 

 

 

2.REFRIGERANT PIPING — It is recommended that the refrigerant piping for all commercial split systems include a liquid line solenoid valve, a liquid line filter drier, and a sight glass.

For refrigerant lines longer than 75 lineal ft, a liquid line solenoid valve and a suction accumulator are required. Refer to the Refrigerant Specialties table.

REFRIGERANT SPECIALTIES PART NUMBERS

UNIT

LIQUID LINE

LIQUID LINE

LLSV

SIGHT

FILTER

SUCTION LINE

SIZE (in.)

SOLENOID VALVE (LLSV)

COIL

GLASS

DRIER

ACCUMULATOR

 

566D150

1/2

200RB7T4M

AMG/24V

AMI-1TT4

P502-8757S*

S-7063

5/8

200RA8T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7063

 

 

1/2

200RB7T4M

AMG/24V

AMI-1TT4

P502-8757S*

S-7721

566D180

5/8

200RA8T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7721

 

7/8

200RA8T7M

AMG/24V

AMI-1TT7

P502-8757S

S-7721

566D240

5/8

200RA9T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7721

7/8

200RA9T7M

AMG/24V

AMI-1TT7

P502-8757S

S-7721

 

566E150

1/2

200RB5T4M Qty 2

AMG/24V Qty 2

AMI-1TT4 Qty 2

P502-8304S Qty 2

S-7063S* Qty 2

566E180

1/2

200RB5T4M Qty 2

AMG/24V Qty 2

AMI-1TT4 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

5/8

200RB5T5M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

 

566E240

1/2

200RB6T4M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8307S*

S-7063S Qty 2

5/8

200RB6T5M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8307S*

S-7063S Qty 2

 

*Bushings required.

54

Image 54
Contents FEATURES/BENEFITS 524A AIR-HANDLING UnitsTable of Contents Estimated Sound Power Levels Lw 524A072-300 ARI* Capacity RatingsSound LEVELS, dB 569D/576C/566D,E FIELD-INSTALLED Accessories Options and Accessories566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED Options Options and AccessoriesOptions and Accessories 524A-B, C FACTORY-INSTALLED OptionsCommercial Programmable Non-Programmable Thermostat 524A with Discharge Plenum, Return Grille, and Subbase 524A with Hot Water or Steam Coil524A with Economizer 524A with Condensate Trap II Select Condensing Unit AIR-HANDLER Combination Selection ProcedureIV Determine FAN RPM and BHP Brake Horsepower III Determine Sizes of Liquid and Suction LinesControls Operating SequencesTypical Wiring Schematics 569D090, 208/230-3-360 and 460-3-60 UnitsTypical Wiring Schematics 576C120, 208/230-3-60 and 460-3-60 UnitsModel Number Nomenclature Physical Data 569D072-120, 576C120, 569F120 UnitsUnit Dimensions 569D072-120, 576C120Dimensions 569D072Performance Data Condensing Unit Ratings569D072/524A-C072 with HIGH-CAPACITY 4-ROW Coil Performance DataCombination Ratings SHCCombination Ratings 569D072/524A-C090 with HIGH-CAPACITY 4-ROW Coil2400 3000 3750 Condenser Temp F Unit 569D090569D090/524A-C072 with HIGH-CAPACITY 4-ROW Coil 569D090/524A-B072 with Standard 3-ROW Coil569D090/524A-C090 with HIGH-CAPACITY 4-ROW Coil 2205 3000 3750 Condenser569D090/524A-B090 with Standard 3-ROW Coil 3000 4000 5000 Condenser Unit 569D120569D120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 569D120/524A-B120 with Standard 3-ROW Coil569D120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 3750 5000 6250 Condenser569D120/524A-B150 with Standard 3-ROW Coil Unit 576C120 576C120/524A-C120 with HIGH-CAPACITY 4-ROW Coil576C120/524A-B120 with Standard 3-ROW Coil 576C120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 576C120/524A-B150 with Standard 3-ROW CoilUnit 569F120 569F120/524A-C120 with HIGH-CAPACITY 4-ROW Coil569F120/524A-B120 with Standard 3-ROW Coil 569F120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 569F120/524A-B150 with Standard 3-ROW CoilElectrical Data Maximum Refrigerant Charge Operating Limits Minimum OUTDOOR-AIR Operating TemperatureApplication Data 569D072-120, 576C090-120, 569F120 Refrigerant Piping SizesTypical Piping and Wiring Rooftop Installation 569D072-120, 576C120Part 1 General Guide Specifications 569D072-120, 576C120Commercial AIR-COOLED Condensing Units Part 2 ProductsGuide Specifications 569D072-120, 576C120 Guide Specifications 569F120 Guide Specifications 569F120 566D E X 150 566D150-240 Units Physical Data 566E150-240 UnitsDimensions Dimensions 566D150-240, 566E150-240 Aluminum Coil UnitAir Temperature Entering Condenser F 100 105 115 Edb Unit 566D150566D150/524A-C150 with High Capacity 4-ROW Coil 566D150/524A-B150 with Standard 3-ROW Coil566D150/524A-C180 with High Capacity 4-ROW Coil 4500 6000 7500 Condenser566D150/524A-B180 with Standard 3-ROW Coil Unit 566D180 566D180/524A-C180 with HIGH-CAPACITY 4-ROW Coil566D180/524A-B180 with Standard 3-ROW Coil 566D180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 000 10,000 Condenser566D180/524A-B240 with Standard 3-ROW Coil 500 10,000 12,500 Condenser Unit 566D240566D240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566D240/524A-B300 with Standard 3-ROW CoilUnit 566E150 566E150/524A-C120 with HIGH-CAPACITY 4-ROW Coil566E150/524A-B120 with Standard 3-ROW Coil 566E150/524A-C150 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B150 with Standard 3-ROW Coil566E150/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B180 with Standard 3-ROW CoilUnit 566E180 566E180/524A-C150 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B150 with Standard 3-ROW Coil 566E180/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B180 with Standard 3-ROW Coil566E180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B240 with Standard 3-ROW CoilUnit 566E240 566E240/524A-C240 with HIGH-CAPACITY 4-ROW Coil566E240/524A-B240 with Standard 3-ROW Coil 566E240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566E240/524A-B300 with Standard 3-ROW CoilNominal Voltage Compressor Application Data 566D150-240, 566E150-240 Minimum OUTDOOR-AIR Operating Temperature 566D150-240 UnitsMinimum OUTDOOR-AIR Operating Temperature 566E150-240 Units Operating LimitsFace-Split Coil Suction Liquid Line Piping Refrigerant Piping Sizes Double Suction RisersSuction Line Piping Multiple Condensing Unit Arrangements 566D, 566E150-240Rooftop Installation 566D150-240 Typical Piping and Wiring Ground Level Installation 566D150-240Guide Specifications 566D150-240, 566E150-240 Guide Specifications 566D150-240, 566E150-240 Coil Option 524A P B 120 000 GCVoltage Nominal Cooling Tons 072524A-B,C Units Unit 524AUnit Unit Weight 524A-B,C072-120524A-B,C150-240 524A-B,C300 B300 1020 C300 1050524A-B FAN Performance Data 0.0-1.2 in. wg ESP Unit Airflow524A-B FAN Performance Data 1.4-2.4 in. wg ESP FAN Performance Data 524A-C with High Capacity Coil 1.2 in. wg ESPFAN Performance Data 524A-C With High Capacity Coil 1.4-2.4 in. wg ESPAccessory Plenum AIR Throw Data Accessory Pressure Drop in. wgFACTORY-SUPPLIED Filter Pressure Drop ROW Unit Airflow Hydronic Heating CapacitiesHeating Correction Factors HOT Water COIL†524A-B PH-Hz Unit Voltage FAN Motor Power Supply524A-B,C Standard Motors FLA MocpElectrical Data 524A-B,C Alternate MotorsFLA Electric Heater Data Electric Heater Data CAELHEAT018A00 CAELHEAT016A00CAELHEAT017A00 CAELHEAT019A00CAELHEAT027A00 CAELHEAT025A00CAELHEAT026A00 CAELHEAT028A00CAELHEAT036A00 CAELHEAT034A00CAELHEAT035A00 CAELHEAT037A00FAN Motor Data FACTORY-INSTALLED Nozzle and Distributor DataApplication Data 524A Standard Motor Unit Size 524AApplication Data 524A FAN Motor DataStandard Drive Data MEDIUM-STATIC Drive Data HIGH-STATIC Drive DataGuide Specifications 524A Commercial Packaged AIR-HANDLING UnitGuide Specifications 524A Air Discharge PlenumIndex

569F, 566E, 566D, 569D, 576C specifications

Bryant has long been recognized for its innovative heating and cooling solutions, and the Bryant 576C, 569D, 566D, 566E, and 569F models exemplify the brand's commitment to energy efficiency, comfort, and advanced technology. Each model is designed to cater to various residential and commercial heating and cooling needs, ensuring optimal performance and reliability.

The Bryant 576C is a highly efficient air conditioning unit that offers remarkable SEER ratings, making it an eco-friendly choice for homeowners. Its advanced technology includes a variable-speed compressor, which adjusts the cooling output based on the home’s requirements, ensuring maximum comfort while minimizing energy consumption. Additionally, its Quiet operation allows for a peaceful indoor environment, as the system operates at low sound levels even during peak performance.

The Bryant 569D heating system stands out for its durability and energy efficiency. Designed with a two-stage gas valve, it provides flexible heating output, allowing for improved temperature control. This model is equipped with an ECM blower motor, ensuring quiet operation and consistent airflow. Its efficiency ratings are impressive, providing significant savings on energy bills while maintaining an ideal indoor climate.

Similarly, the Bryant 566D model emphasizes performance and reliability. Its variable-speed blower motor enhances comfort levels by providing better humidity control and even heating throughout the living space. With an emphasis on high-quality construction materials, this model ensures a long lifespan, making it a wise investment for homeowners looking for effective heating solutions.

The Bryant 566E model incorporates state-of-the-art technology, including smart thermostat compatibility, which allows users to control their heating and cooling systems remotely. This feature enhances convenience and helps to optimize energy usage based on the occupants' schedules. With its excellent design and efficiency, the 566E is perfect for those seeking a modern heating solution without compromising on comfort.

Lastly, the Bryant 569F is ideal for homeowners wanting a balance between efficiency and performance. With an ENERGY STAR certification, this model provides reliable heating while keeping energy costs low. Its compact design makes it suitable for various spaces, and the integrated safety features ensure peace of mind for users.

In summary, whether you choose the Bryant 576C, 569D, 566D, 566E, or 569F, each model reflects a commitment to quality, efficiency, and innovation, ensuring that homeowners can achieve the perfect climate in their living spaces. These heating and cooling systems leverage advanced technologies that not only provide comfort but also promote energy savings and environmental responsibility.