Bryant 576C, 569D, 566E, 569F, 566D manual Electric Heater Data

Page 75

ELECTRICAL DATA (cont)

ELECTRIC HEATER DATA (cont)

 

 

 

FAN MOTOR

ELECTRIC HEATER(S)

 

 

 

 

HEATER PART NO.

UNIT

V-PH-Hz

Nominal

Actual Capacity (kW)

FLA

MCA*

MOCP*

 

 

 

 

 

 

Hp

kW

FLA

Capacity (kW)

Stage 1

Stage 2

Total

 

 

 

 

 

1.3†

0.97

7.6

25

11.3

7.5

18.8

52.1

74.7

80

 

 

208-3-60

2.4†

1.79

11.0

25

11.3

7.5

18.8

52.1

78.9

80

 

 

2.4

1.79

5.2

25

11.3

7.5

18.8

52.1

71.7

80

 

 

 

2.9

2.16

7.5

25

11.3

7.5

18.8

52.1

74.5

80

CAELHEAT010A00

 

 

3.7

2.76

10.2

25

11.3

7.5

18.8

52.1

77.9

80

 

 

1.3†

0.97

7.6

25

15.0

10.0

25.0

60.1

84.7

90

 

 

 

 

 

240-3-60

2.4†

1.79

11.0

25

15.0

10.0

25.0

60.1

88.9

90

 

 

2.4

1.79

5.2

25

15.0

10.0

25.0

60.1

81.7

90

 

 

 

2.9

2.16

7.5

25

15.0

10.0

25.0

60.1

84.6

90

 

 

 

3.7

2.76

10.2

25

15.0

10.0

25.0

60.1

87.9

90

CAELHEAT011A00

 

480-3-60

2.4

1.79

2.6

25

15.0

10.0

25.0

30.1

40.8

50

 

2.9

2.16

3.4

25

15.0

10.0

25.0

30.1

41.8

50

 

 

 

3.7

2.76

4.8

25

15.0

10.0

25.0

30.1

43.6

50

CAELHEAT012A00

524A-B072-120

575-3-60

1.0

0.75

1.4

25

15.0

10.0

25.0

25.1

33.1

35

2.0

1.49

2.3

25

15.0

10.0

25.0

25.1

34.3

35

 

524A-C072-120

 

3.0

2.24

3.8

25

15.0

10.0

25.0

25.1

36.1

40

 

 

 

 

 

 

2.4†

1.79

11.0

35

15.0

11.3

26.3

73.0

105.0

110

 

 

208-3-60

2.4

1.79

5.2

35

15.0

11.3

26.3

73.0

97.7

100

 

 

2.9

2.16

7.5

35

15.0

11.3

26.3

73.0

100.6

110

 

 

 

CAELHEAT013A00

 

 

3.7

2.76

10.2

35

15.0

11.3

26.3

73.0

104.0

110

 

 

2.4†

1.79

11.0

35

20.0

15.0

35.0

84.2

119.0

125

 

 

 

 

 

240-3-60

2.4

1.79

5.2

35

20.0

15.0

35.0

84.2

111.7

125

 

 

2.9

2.16

7.5

35

20.0

15.0

35.0

84.2

114.6

125

 

 

 

 

 

 

3.7

2.76

10.2

35

20.0

15.0

35.0

84.2

118.0

125

CAELHEAT014A00

 

480-3-60

2.4

1.79

2.6

35

20.0

15.0

35.0

42.1

55.9

60

 

2.9

2.16

3.4

35

20.0

15.0

35.0

42.1

56.9

60

 

 

 

3.7

2.76

4.8

35

20.0

15.0

35.0

42.1

58.6

60

CAELHEAT015A00

 

575-3-60

2.0

1.49

2.3

35

20.0

15.0

35.0

35.1

46.8

50

 

 

 

3.0

2.24

3.8

35

20.0

15.0

35.0

35.1

48.7

50

LEGEND

FLA — Full Load Amps

Hp — Horsepower

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat acces- sory and air handler.

†Single-phase motors. All other motors are 3-phase.

NOTES:

1.Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v capacity (kW) by the factor shown in the table below for the unit voltage.

HEATER

 

 

ACTUAL HEATER VOLTAGE

 

 

 

RATING

200

208

230

240

400

440

460

480

 

550

575

600

VOLTAGE

 

240

0.694

0.751

0.918

1

480

0.694

0.84

0.918

1

 

575

0.915

1

1.089

2.The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh.

3.Heater contactor coils are 24 v and require 8 va holding current.

4.Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg.

5.MCA and MOCP values apply to both standard and alternate fac- tory-supplied motors.

6.Approximate shipping weight for CAELHEAT001A00-015A00 is 55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and CAELHEAT028A00-039A00 is 75 lb each.

524A072-300

75

Image 75
Contents 524A AIR-HANDLING Units FEATURES/BENEFITSTable of Contents Estimated Sound Power Levels Lw 524A072-300 ARI* Capacity RatingsSound LEVELS, dB 569D/576C/566D,E Options and Accessories Options and Accessories566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED Options FIELD-INSTALLED AccessoriesOptions and Accessories 524A-B, C FACTORY-INSTALLED OptionsCommercial Programmable Non-Programmable Thermostat 524A with Discharge Plenum, Return Grille, and Subbase 524A with Hot Water or Steam Coil524A with Economizer 524A with Condensate Trap III Determine Sizes of Liquid and Suction Lines Selection ProcedureIV Determine FAN RPM and BHP Brake Horsepower II Select Condensing Unit AIR-HANDLER CombinationOperating Sequences Controls569D090, 208/230-3-360 and 460-3-60 Units Typical Wiring Schematics576C120, 208/230-3-60 and 460-3-60 Units Typical Wiring SchematicsModel Number Nomenclature Physical Data 569D072-120, 576C120, 569F120 UnitsUnit 569D072-120, 576C120 Dimensions569D072 DimensionsCondensing Unit Ratings Performance DataSHC Performance DataCombination Ratings 569D072/524A-C072 with HIGH-CAPACITY 4-ROW CoilCombination Ratings 569D072/524A-C090 with HIGH-CAPACITY 4-ROW Coil2400 3000 3750 Condenser 569D090/524A-B072 with Standard 3-ROW Coil Unit 569D090569D090/524A-C072 with HIGH-CAPACITY 4-ROW Coil Temp F569D090/524A-C090 with HIGH-CAPACITY 4-ROW Coil 2205 3000 3750 Condenser569D090/524A-B090 with Standard 3-ROW Coil 569D120/524A-B120 with Standard 3-ROW Coil Unit 569D120569D120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 3000 4000 5000 Condenser569D120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 3750 5000 6250 Condenser569D120/524A-B150 with Standard 3-ROW Coil Unit 576C120 576C120/524A-C120 with HIGH-CAPACITY 4-ROW Coil576C120/524A-B120 with Standard 3-ROW Coil 576C120/524A-B150 with Standard 3-ROW Coil 576C120/524A-C150 with HIGH-CAPACITY 4-ROW CoilUnit 569F120 569F120/524A-C120 with HIGH-CAPACITY 4-ROW Coil569F120/524A-B120 with Standard 3-ROW Coil 569F120/524A-B150 with Standard 3-ROW Coil 569F120/524A-C150 with HIGH-CAPACITY 4-ROW CoilElectrical Data Refrigerant Piping Sizes Operating Limits Minimum OUTDOOR-AIR Operating TemperatureApplication Data 569D072-120, 576C090-120, 569F120 Maximum Refrigerant ChargeRooftop Installation 569D072-120, 576C120 Typical Piping and WiringPart 2 Products Guide Specifications 569D072-120, 576C120Commercial AIR-COOLED Condensing Units Part 1 GeneralGuide Specifications 569D072-120, 576C120 Guide Specifications 569F120 Guide Specifications 569F120 566D E X 150 566D150-240 Units 566E150-240 Units Physical DataDimensions Dimensions Aluminum Coil Unit 566D150-240, 566E150-240Air Temperature Entering Condenser F 100 105 115 566D150/524A-B150 with Standard 3-ROW Coil Unit 566D150566D150/524A-C150 with High Capacity 4-ROW Coil Edb566D150/524A-C180 with High Capacity 4-ROW Coil 4500 6000 7500 Condenser566D150/524A-B180 with Standard 3-ROW Coil Unit 566D180 566D180/524A-C180 with HIGH-CAPACITY 4-ROW Coil566D180/524A-B180 with Standard 3-ROW Coil 566D180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 000 10,000 Condenser566D180/524A-B240 with Standard 3-ROW Coil 566D240/524A-B300 with Standard 3-ROW Coil Unit 566D240566D240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 500 10,000 12,500 CondenserUnit 566E150 566E150/524A-C120 with HIGH-CAPACITY 4-ROW Coil566E150/524A-B120 with Standard 3-ROW Coil 566E150/524A-B150 with Standard 3-ROW Coil 566E150/524A-C150 with HIGH-CAPACITY 4-ROW Coil566E150/524A-B180 with Standard 3-ROW Coil 566E150/524A-C180 with HIGH-CAPACITY 4-ROW CoilUnit 566E180 566E180/524A-C150 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B150 with Standard 3-ROW Coil 566E180/524A-B180 with Standard 3-ROW Coil 566E180/524A-C180 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B240 with Standard 3-ROW Coil 566E180/524A-C240 with HIGH-CAPACITY 4-ROW CoilUnit 566E240 566E240/524A-C240 with HIGH-CAPACITY 4-ROW Coil566E240/524A-B240 with Standard 3-ROW Coil 566E240/524A-B300 with Standard 3-ROW Coil 566E240/524A-C300 with HIGH-CAPACITY 4-ROW CoilNominal Voltage Compressor Operating Limits Minimum OUTDOOR-AIR Operating Temperature 566D150-240 UnitsMinimum OUTDOOR-AIR Operating Temperature 566E150-240 Units Application Data 566D150-240, 566E150-240Face-Split Coil Suction Liquid Line Piping Refrigerant Piping Sizes Double Suction RisersSuction Line Piping 566D, 566E150-240 Multiple Condensing Unit ArrangementsRooftop Installation 566D150-240 Ground Level Installation 566D150-240 Typical Piping and WiringGuide Specifications 566D150-240, 566E150-240 Guide Specifications 566D150-240, 566E150-240 Nominal Cooling Tons 072 524A P B 120 000 GCVoltage Coil OptionUnit 524A 524A-B,C Units524A-B,C072-120 Unit Unit Weight524A-B,C150-240 B300 1020 C300 1050 524A-B,C300Unit Airflow 524A-B FAN Performance Data 0.0-1.2 in. wg ESP524A-B FAN Performance Data 1.4-2.4 in. wg ESP 1.2 in. wg ESP FAN Performance Data 524A-C with High Capacity CoilWith High Capacity Coil 1.4-2.4 in. wg ESP FAN Performance Data 524A-CAccessory Plenum AIR Throw Data Accessory Pressure Drop in. wgFACTORY-SUPPLIED Filter Pressure Drop HOT Water COIL† Hydronic Heating CapacitiesHeating Correction Factors ROW Unit Airflow FLA Mocp Unit Voltage FAN Motor Power Supply 524A-B,C Standard Motors 524A-B PH-HzElectrical Data 524A-B,C Alternate MotorsFLA Electric Heater Data Electric Heater Data CAELHEAT019A00 CAELHEAT016A00CAELHEAT017A00 CAELHEAT018A00CAELHEAT028A00 CAELHEAT025A00CAELHEAT026A00 CAELHEAT027A00CAELHEAT037A00 CAELHEAT034A00CAELHEAT035A00 CAELHEAT036A00Standard Motor Unit Size 524A FACTORY-INSTALLED Nozzle and Distributor DataApplication Data 524A FAN Motor DataApplication Data 524A FAN Motor DataStandard Drive Data HIGH-STATIC Drive Data MEDIUM-STATIC Drive DataCommercial Packaged AIR-HANDLING Unit Guide Specifications 524AAir Discharge Plenum Guide Specifications 524AIndex