Bryant 569D, 576C, 566E Hydronic Heating Capacities, Heating Correction Factors, ROW Unit Airflow

Page 71
2. Leaving db = ent db (F) +

PERFORMANCE DATA (cont)

HYDRONIC HEATING CAPACITIES

 

 

 

1-ROW

 

 

2-ROW

 

UNIT

AIRFLOW

 

STEAM*

 

HOT WATER COIL†

 

524A-B

(Cfm)

 

 

 

 

 

 

Water

 

524A-C

Cap.

 

Ldb

Cap.

Ldb

 

Flow

PD

 

 

 

 

 

 

 

 

 

 

 

(Gpm)

 

 

1,800

146

 

134

156.0

140

 

15.6

3.4

072

2,400

173

 

126

183.0

131

 

18.3

4.3

 

3,000

209

 

123

206.0

124

 

20.6

5.2

 

2,250

168

 

129

174.0

133

 

17.4

4.0

090

3,000

209

 

123

206.0

124

 

20.6

5.2

 

3,750

240

 

117

238.0

118

 

23.8

6.5

 

3,000

209

 

123

299.0

152

 

29.9

5.0

120

4,000

243

 

115

275.0

124

 

27.5

6.6

 

5,000

279

 

111

316.0

119

 

31.6

8.2

 

3,750

370

 

150

362.0

149

 

36.2

4.2

150

5,000

425

 

137

409.0

136

 

40.9

5.1

 

6,250

465

 

128

456.0

128

 

45.6

6.0

 

4,500

402

 

141

412.0

145

 

41.2

4.5

180

6,000

458

 

129

471.0

133

 

47.1

5.5

 

7,500

479

 

118

529.0

125

 

52.9

6.6

 

6,000

458

 

129

506.0

138

 

50.6

5.1

240

8,000

487

 

115

584.0

128

 

58.4

6.3

 

10,000

499

 

105

652.0

120

 

65.2

7.5

 

7,500

511

 

122

649.0

140

 

64.9

5.7

300

10,000

575

 

112

752.0

130

 

75.2

7.1

 

12,500

626

 

106

842.0

122

 

84.2

8.5

LEGEND

Cap. — Capacity (Btuh in thousands)

Lab — Leaving-Air Dry-Bulb Temp (F)

PD — Pressure Drop (ft water)

*Based on 5 psig steam, 60 F entering-air temperature. All steam coils are non-freeze type.

†Based on 200 F entering water, 20 F water temperature drop, 60 F entering-air temperature.

NOTES:

1. Maximum operating limits for heating coils: 20 psig at 260 F. Capacity (Btuh)

1.1 x cfm

3. See Heating Correction Factors table.

HEATING CORRECTION FACTORS

HOT WATER COIL

Water Temp

Ent Water

 

Entering-Air Temp (F)

 

Drop

Temp

40

50

60

70

80

(F)

(F)

 

 

 

 

 

 

140

0.72

0.64

0.57

0.49

0.41

10

160

0.89

0.81

0.74

0.66

0.58

240

1.06

0.98

0.90

0.83

0.75

 

200

1.22

1.15

1.07

1.00

0.92

 

220

1.39

1.32

1.24

1.17

1.09

 

140

0.64

0.57

0.49

0.41

0.33

20

160

0.81

0.74

0.66

0.58

0.51

240

0.98

0.91

0.83

0.75

0.68

 

200

1.15

1.08

1.00

0.93

0.85

 

220

1.32

1.25

1.17

1.10

1.02

 

140

0.56

0.49

0.41

0.33

0.24

30

160

0.74

0.66

0.58

0.51

0.43

240

0.91

0.83

0.76

0.68

0.60

 

200

1.08

1.00

0.93

0.85

0.78

 

220

1.25

1.18

1.10

1.03

0.95

STEAM COIL

Steam Pressure

 

 

Entering-Air Temp (F)

 

 

(psig)

40

50

 

60

 

70

80

0

1.06

0.98

 

0.91

 

0.85

0.78

2

1.09

1.02

 

0.95

 

0.89

0.82

5

1.13

1.06

 

1.00

 

0.93

0.87

NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.

524A072-300

71

Image 71
Contents 524A AIR-HANDLING Units FEATURES/BENEFITSTable of Contents Sound LEVELS, dB 569D/576C/566D,E Estimated Sound Power Levels Lw 524A072-300ARI* Capacity Ratings Options and Accessories Options and Accessories566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED Options FIELD-INSTALLED AccessoriesCommercial Programmable Non-Programmable Thermostat Options and Accessories524A-B, C FACTORY-INSTALLED Options 524A with Economizer 524A with Condensate Trap 524A with Discharge Plenum, Return Grille, and Subbase524A with Hot Water or Steam Coil III Determine Sizes of Liquid and Suction Lines Selection ProcedureIV Determine FAN RPM and BHP Brake Horsepower II Select Condensing Unit AIR-HANDLER CombinationOperating Sequences Controls569D090, 208/230-3-360 and 460-3-60 Units Typical Wiring Schematics576C120, 208/230-3-60 and 460-3-60 Units Typical Wiring SchematicsModel Number Nomenclature Unit Physical Data569D072-120, 576C120, 569F120 Units 569D072-120, 576C120 Dimensions569D072 DimensionsCondensing Unit Ratings Performance DataSHC Performance DataCombination Ratings 569D072/524A-C072 with HIGH-CAPACITY 4-ROW Coil2400 3000 3750 Condenser Combination Ratings569D072/524A-C090 with HIGH-CAPACITY 4-ROW Coil 569D090/524A-B072 with Standard 3-ROW Coil Unit 569D090569D090/524A-C072 with HIGH-CAPACITY 4-ROW Coil Temp F569D090/524A-B090 with Standard 3-ROW Coil 569D090/524A-C090 with HIGH-CAPACITY 4-ROW Coil2205 3000 3750 Condenser 569D120/524A-B120 with Standard 3-ROW Coil Unit 569D120569D120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 3000 4000 5000 Condenser569D120/524A-B150 with Standard 3-ROW Coil 569D120/524A-C150 with HIGH-CAPACITY 4-ROW Coil3750 5000 6250 Condenser 576C120/524A-B120 with Standard 3-ROW Coil Unit 576C120576C120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 576C120/524A-B150 with Standard 3-ROW Coil 576C120/524A-C150 with HIGH-CAPACITY 4-ROW Coil569F120/524A-B120 with Standard 3-ROW Coil Unit 569F120569F120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 569F120/524A-B150 with Standard 3-ROW Coil 569F120/524A-C150 with HIGH-CAPACITY 4-ROW CoilElectrical Data Refrigerant Piping Sizes Operating Limits Minimum OUTDOOR-AIR Operating TemperatureApplication Data 569D072-120, 576C090-120, 569F120 Maximum Refrigerant ChargeRooftop Installation 569D072-120, 576C120 Typical Piping and WiringPart 2 Products Guide Specifications 569D072-120, 576C120Commercial AIR-COOLED Condensing Units Part 1 GeneralGuide Specifications 569D072-120, 576C120 Guide Specifications 569F120 Guide Specifications 569F120 566D E X 150 566D150-240 Units 566E150-240 Units Physical DataDimensions Dimensions Aluminum Coil Unit 566D150-240, 566E150-240Air Temperature Entering Condenser F 100 105 115 566D150/524A-B150 with Standard 3-ROW Coil Unit 566D150566D150/524A-C150 with High Capacity 4-ROW Coil Edb566D150/524A-B180 with Standard 3-ROW Coil 566D150/524A-C180 with High Capacity 4-ROW Coil4500 6000 7500 Condenser 566D180/524A-B180 with Standard 3-ROW Coil Unit 566D180566D180/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566D180/524A-B240 with Standard 3-ROW Coil 566D180/524A-C240 with HIGH-CAPACITY 4-ROW Coil000 10,000 Condenser 566D240/524A-B300 with Standard 3-ROW Coil Unit 566D240566D240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 500 10,000 12,500 Condenser566E150/524A-B120 with Standard 3-ROW Coil Unit 566E150566E150/524A-C120 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B150 with Standard 3-ROW Coil 566E150/524A-C150 with HIGH-CAPACITY 4-ROW Coil566E150/524A-B180 with Standard 3-ROW Coil 566E150/524A-C180 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B150 with Standard 3-ROW Coil Unit 566E180566E180/524A-C150 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B180 with Standard 3-ROW Coil 566E180/524A-C180 with HIGH-CAPACITY 4-ROW Coil566E180/524A-B240 with Standard 3-ROW Coil 566E180/524A-C240 with HIGH-CAPACITY 4-ROW Coil566E240/524A-B240 with Standard 3-ROW Coil Unit 566E240566E240/524A-C240 with HIGH-CAPACITY 4-ROW Coil 566E240/524A-B300 with Standard 3-ROW Coil 566E240/524A-C300 with HIGH-CAPACITY 4-ROW CoilNominal Voltage Compressor Operating Limits Minimum OUTDOOR-AIR Operating Temperature 566D150-240 UnitsMinimum OUTDOOR-AIR Operating Temperature 566E150-240 Units Application Data 566D150-240, 566E150-240Suction Line Piping Face-Split Coil Suction Liquid Line PipingRefrigerant Piping Sizes Double Suction Risers 566D, 566E150-240 Multiple Condensing Unit ArrangementsRooftop Installation 566D150-240 Ground Level Installation 566D150-240 Typical Piping and WiringGuide Specifications 566D150-240, 566E150-240 Guide Specifications 566D150-240, 566E150-240 Nominal Cooling Tons 072 524A P B 120 000 GCVoltage Coil OptionUnit 524A 524A-B,C Units524A-B,C072-120 Unit Unit Weight524A-B,C150-240 B300 1020 C300 1050 524A-B,C300Unit Airflow 524A-B FAN Performance Data 0.0-1.2 in. wg ESP524A-B FAN Performance Data 1.4-2.4 in. wg ESP 1.2 in. wg ESP FAN Performance Data 524A-C with High Capacity CoilWith High Capacity Coil 1.4-2.4 in. wg ESP FAN Performance Data 524A-CFACTORY-SUPPLIED Filter Pressure Drop Accessory Plenum AIR Throw DataAccessory Pressure Drop in. wg HOT Water COIL† Hydronic Heating CapacitiesHeating Correction Factors ROW Unit AirflowFLA Mocp Unit Voltage FAN Motor Power Supply524A-B,C Standard Motors 524A-B PH-HzFLA Electrical Data524A-B,C Alternate Motors Electric Heater Data Electric Heater Data CAELHEAT019A00 CAELHEAT016A00CAELHEAT017A00 CAELHEAT018A00CAELHEAT028A00 CAELHEAT025A00CAELHEAT026A00 CAELHEAT027A00CAELHEAT037A00 CAELHEAT034A00CAELHEAT035A00 CAELHEAT036A00Standard Motor Unit Size 524A FACTORY-INSTALLED Nozzle and Distributor DataApplication Data 524A FAN Motor DataStandard Drive Data Application Data 524AFAN Motor Data HIGH-STATIC Drive Data MEDIUM-STATIC Drive DataCommercial Packaged AIR-HANDLING Unit Guide Specifications 524AAir Discharge Plenum Guide Specifications 524AIndex