Bryant 566E, 576C, 569D, 569F, 566D Guide Specifications 524A, Commercial Packaged AIR-HANDLING Unit

Page 82

GUIDE SPECIFICATIONS — 524A

524A072-300

COMMERCIAL PACKAGED AIR-HANDLING UNIT

HVAC GUIDE SPECIFICATIONS

SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO 25 TONS, NOMINAL COOLING

BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION COIL)

PART 1 — GENERAL

1.01SYSTEM DESCRIPTION

A.Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multiposition design and shall be capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only verti- cal units are to be applied without ductwork.)

B.Unit with direct-expansion coil shall be used in a refriger- ant circuit with a matching air-cooled condensing unit.

1.02QUALITY ASSURANCE

A.Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration, latest edition.

B.Unit shall be constructed in accordance with ETL and ETL, Canada, standards and shall carry the ETL and ETL, Canada, labels.

C.Unit insulation and adhesive shall comply with NFPA-90A requirements for flame spread and smoke generation. Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM standards G21 and 22.

D.Unit shall be manufactured in a facility registered to the ISO 9001:2000 manufacturing quality standard.

E.Direct-expansion coils shall be burst and leak tested at 435 psi.

1.03 DELIVERY AND STORAGE

Units shall be stored and handled per manufacturer’s recommendations.

PART 2 — PRODUCTS

2.01EQUIPMENT

Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or a vertical configuration. Unit shall consist of forward- curved belt-driven centrifugal fan(s), motor and drive assembly, prewired fan motor contactor, factory-installed refrigerant metering devices (direct-expansion coil units), cooling coil, 2-in. disposable air filters, and condensate drain pans for vertical or horizontal configurations.

A.Base Unit:

1.Cabinet shall be constructed of mill-galvanized steel.

2.Cabinet panels shall be fully insulated with 1/2-in. fire-retardant material. Insulation shall contain an EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM standards G21 and 22.

3.Unit shall contain non-corroding condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of the unit to prevent standing water from accumulating in pans.

4.Unit shall have factory-supplied 2-in. throwaway-type filters installed upstream from the cooling coil. Filter access shall be from either the right or left side of the unit.

B.Coils:

Coils shall consist of 3 rows (524A-B) or 4 rows (524A-C) of copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil.

1.Direct-expansion coils shall feature factory-installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be capable of external adjustment. Coil tubing shall be internally rifled to maximize heat transfer.

2.High-Capacity Coil:

The high-capacity 4-row coil consists of 4 rows of 3/8-in. copper tubes with sine-wave aluminum fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled to maximize heat transfer. Suction and liquid line connections shall be made on the same side of the coil. Direct-expansion coils shall feature factory-installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be capable of external adjustment.

C. Operating Characteristics:

 

 

 

Unit shall be capable of providing

 

 

cfm airflow at an

external static pressure of

 

 

in. wg.

D.Motor:

Fan motor of the size and electrical characteristics speci- fied on the equipment schedule shall be factory supplied and installed.

Motors rated at 1.3 through 3.7 hp shall have internal thermal overload protection. Motors rated at 5, 71/2, and 10 hp shall be protected by a circuit breaker.

E.Special Features:

1. Alternate Motor and Drive:

An alternate motor and/or medium-static or high- static drive shall be available to meet the airflow and external static pressure requirements specified on the equipment schedule.

2. External Paint:

Where conditions require, units shall be painted with an American Sterling Gray finish.

3. Hot Water Coil:

Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fins bonded to the tubes by mechanical expansion. Coil shall be mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 150 psig.

4. Steam Distributing Coil:

Coil shall consist of one row of copper tubes with aluminum plate fins, and shall have inner steam dis- tributing tubes. Coil shall be mounted in a galvanized steel housing and shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 20 psig at 260 F.

82

Image 82
Contents FEATURES/BENEFITS 524A AIR-HANDLING UnitsTable of Contents ARI* Capacity Ratings Estimated Sound Power Levels Lw 524A072-300Sound LEVELS, dB 569D/576C/566D,E FIELD-INSTALLED Accessories Options and Accessories566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED Options Options and Accessories524A-B, C FACTORY-INSTALLED Options Options and AccessoriesCommercial Programmable Non-Programmable Thermostat 524A with Hot Water or Steam Coil 524A with Discharge Plenum, Return Grille, and Subbase524A with Economizer 524A with Condensate Trap II Select Condensing Unit AIR-HANDLER Combination Selection ProcedureIV Determine FAN RPM and BHP Brake Horsepower III Determine Sizes of Liquid and Suction LinesControls Operating SequencesTypical Wiring Schematics 569D090, 208/230-3-360 and 460-3-60 UnitsTypical Wiring Schematics 576C120, 208/230-3-60 and 460-3-60 UnitsModel Number Nomenclature 569D072-120, 576C120, 569F120 Units Physical DataUnit Dimensions 569D072-120, 576C120Dimensions 569D072Performance Data Condensing Unit Ratings569D072/524A-C072 with HIGH-CAPACITY 4-ROW Coil Performance DataCombination Ratings SHC569D072/524A-C090 with HIGH-CAPACITY 4-ROW Coil Combination Ratings2400 3000 3750 Condenser Temp F Unit 569D090569D090/524A-C072 with HIGH-CAPACITY 4-ROW Coil 569D090/524A-B072 with Standard 3-ROW Coil2205 3000 3750 Condenser 569D090/524A-C090 with HIGH-CAPACITY 4-ROW Coil569D090/524A-B090 with Standard 3-ROW Coil 3000 4000 5000 Condenser Unit 569D120569D120/524A-C120 with HIGH-CAPACITY 4-ROW Coil 569D120/524A-B120 with Standard 3-ROW Coil3750 5000 6250 Condenser 569D120/524A-C150 with HIGH-CAPACITY 4-ROW Coil569D120/524A-B150 with Standard 3-ROW Coil 576C120/524A-C120 with HIGH-CAPACITY 4-ROW Coil Unit 576C120576C120/524A-B120 with Standard 3-ROW Coil 576C120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 576C120/524A-B150 with Standard 3-ROW Coil569F120/524A-C120 with HIGH-CAPACITY 4-ROW Coil Unit 569F120569F120/524A-B120 with Standard 3-ROW Coil 569F120/524A-C150 with HIGH-CAPACITY 4-ROW Coil 569F120/524A-B150 with Standard 3-ROW CoilElectrical Data Maximum Refrigerant Charge Operating Limits Minimum OUTDOOR-AIR Operating TemperatureApplication Data 569D072-120, 576C090-120, 569F120 Refrigerant Piping SizesTypical Piping and Wiring Rooftop Installation 569D072-120, 576C120Part 1 General Guide Specifications 569D072-120, 576C120Commercial AIR-COOLED Condensing Units Part 2 ProductsGuide Specifications 569D072-120, 576C120 Guide Specifications 569F120 Guide Specifications 569F120 566D E X 150 566D150-240 Units Physical Data 566E150-240 UnitsDimensions Dimensions 566D150-240, 566E150-240 Aluminum Coil UnitAir Temperature Entering Condenser F 100 105 115 Edb Unit 566D150566D150/524A-C150 with High Capacity 4-ROW Coil 566D150/524A-B150 with Standard 3-ROW Coil4500 6000 7500 Condenser 566D150/524A-C180 with High Capacity 4-ROW Coil566D150/524A-B180 with Standard 3-ROW Coil 566D180/524A-C180 with HIGH-CAPACITY 4-ROW Coil Unit 566D180566D180/524A-B180 with Standard 3-ROW Coil 000 10,000 Condenser 566D180/524A-C240 with HIGH-CAPACITY 4-ROW Coil566D180/524A-B240 with Standard 3-ROW Coil 500 10,000 12,500 Condenser Unit 566D240566D240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566D240/524A-B300 with Standard 3-ROW Coil566E150/524A-C120 with HIGH-CAPACITY 4-ROW Coil Unit 566E150566E150/524A-B120 with Standard 3-ROW Coil 566E150/524A-C150 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B150 with Standard 3-ROW Coil566E150/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E150/524A-B180 with Standard 3-ROW Coil566E180/524A-C150 with HIGH-CAPACITY 4-ROW Coil Unit 566E180566E180/524A-B150 with Standard 3-ROW Coil 566E180/524A-C180 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B180 with Standard 3-ROW Coil566E180/524A-C240 with HIGH-CAPACITY 4-ROW Coil 566E180/524A-B240 with Standard 3-ROW Coil566E240/524A-C240 with HIGH-CAPACITY 4-ROW Coil Unit 566E240566E240/524A-B240 with Standard 3-ROW Coil 566E240/524A-C300 with HIGH-CAPACITY 4-ROW Coil 566E240/524A-B300 with Standard 3-ROW CoilNominal Voltage Compressor Application Data 566D150-240, 566E150-240 Minimum OUTDOOR-AIR Operating Temperature 566D150-240 UnitsMinimum OUTDOOR-AIR Operating Temperature 566E150-240 Units Operating LimitsRefrigerant Piping Sizes Double Suction Risers Face-Split Coil Suction Liquid Line PipingSuction Line Piping Multiple Condensing Unit Arrangements 566D, 566E150-240Rooftop Installation 566D150-240 Typical Piping and Wiring Ground Level Installation 566D150-240Guide Specifications 566D150-240, 566E150-240 Guide Specifications 566D150-240, 566E150-240 Coil Option 524A P B 120 000 GCVoltage Nominal Cooling Tons 072524A-B,C Units Unit 524AUnit Unit Weight 524A-B,C072-120524A-B,C150-240 524A-B,C300 B300 1020 C300 1050524A-B FAN Performance Data 0.0-1.2 in. wg ESP Unit Airflow524A-B FAN Performance Data 1.4-2.4 in. wg ESP FAN Performance Data 524A-C with High Capacity Coil 1.2 in. wg ESPFAN Performance Data 524A-C With High Capacity Coil 1.4-2.4 in. wg ESPAccessory Pressure Drop in. wg Accessory Plenum AIR Throw DataFACTORY-SUPPLIED Filter Pressure Drop ROW Unit Airflow Hydronic Heating CapacitiesHeating Correction Factors HOT Water COIL†524A-B PH-Hz Unit Voltage FAN Motor Power Supply524A-B,C Standard Motors FLA Mocp524A-B,C Alternate Motors Electrical DataFLA Electric Heater Data Electric Heater Data CAELHEAT018A00 CAELHEAT016A00CAELHEAT017A00 CAELHEAT019A00CAELHEAT027A00 CAELHEAT025A00CAELHEAT026A00 CAELHEAT028A00CAELHEAT036A00 CAELHEAT034A00CAELHEAT035A00 CAELHEAT037A00 FAN Motor Data FACTORY-INSTALLED Nozzle and Distributor Data Application Data 524A Standard Motor Unit Size 524AFAN Motor Data Application Data 524AStandard Drive Data MEDIUM-STATIC Drive Data HIGH-STATIC Drive DataGuide Specifications 524A Commercial Packaged AIR-HANDLING UnitGuide Specifications 524A Air Discharge PlenumIndex