Bryant 581B Typical Access Panel Locations Accessory Installation, Optional Varislide Economizer

Page 13

Heat Anticipator Setting

The room thermostat heat anticipator must be properly ad- justed to ensure proper heating performance. Set the heat anticipator, using an ammeter to determine the exact re- quired setting.

NOTE: For thermostat selection purposes, use .14 amp for the approximate required setting. Set heat anticipator stage 1 and 2 at .14 amp.

Failure to make a proper heat anticipator adjustment may result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; how- ever, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.

Fig. 16 Ð Typical Access Panel Locations

F. Accessory Installation

At this time any required accessories should be installed on the unit. Control wiring information is provided in the unit wiring book. Refer to accessory Installation Instructions pro- vided with accessory.

G. Optional Varislide™ Economizer

The optional economizer hood assembly is packaged and shipped in the ®lter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.

NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical dis- charge application, discard this plate.

Assembly

1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7.

2.Remove ®lter access panel by raising panel and swing- ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove ®lter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 16. Remove optional outdoor-air damper hood package from ®lter section.

3.Assemble outdoor-air hood top and side plates as shown in Fig. 17. Install seal strips on hoop top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time.

4.Slide economizer into unit and secure with screws. See Fig. 18.

NOTE: Be sure to engage rear economizer ¯ange under tabs in vertical return-air opening.

5.To convert to horizontal discharge application:

a.Rotate the economizer 90 degrees until the econo- mizer motor faces the condenser section (see Fig. 19.).

b.Rotate the barometric relief damper cover 90 degrees.

c.Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assem- bly.) See Fig. 20.

6.Insert economizer plug into economizer harness. Re- move tape from barometric relief damper. See Fig. 21.

7.If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum po- sition setting for required air¯ow. See Fig. 22. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 22. Tighten screws.

Ð13Ð

Fig. 17 Ð Outdoor-Air Hood Details

ECONOMIZER

ECONOMIZER

ECONOMIZER

TOP

CONTROL BOARD

PLUG

MOTOR

SCREW

BAROMETRIC

RELIEF DAMPER

ECONOMIZER

POSITION SETTING

MOUNTING SCREWS

BRACKET

Fig. 18 Ð Varislide Economizer Installed in Unit

Image 13
Contents Contents Important Ð Read Before InstallingSafety Considerations Threaded Wire Required Sizes Conduit USE Maximum Standard Varislide Corner Unit Economizer WeightConnection Sizes Locate the Unit InstallationClearance Roof Curb MountService Plate Sizes Connector Unit AccessoryRoof Curb Unit SizeII. Unit Duct Connections Unit MAX Dimensions WeightIII. RIG and Place Unit 581B 036Base Unit 581B SpecicationsIV. Field Connections Install Flue HoodExternal Trap Condensate Drain Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Electrical Connections Field Duct ConnectionsEquip CompGND IFCNominal Voltage Combustion Minimum Unit Compressor Power Supply Disconnect Voltage Range FAN MotorRLA LRA FLA MCA MOCP² HacrThermostat List Ð Electrical Data Units with Electrical Convenience OutletOptional Varislide Economizer Typical Access Panel Locations Accessory InstallationExample Optional Parablade EconomizerOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit START-UP Compressor Rotation PRE-START-UPII. Heating Section START-UP and Adjustments Altitude Compensation* Ð Units 581B036-072 Rated Gas Inputs at Indicated Manifold PressuresPressure OrificesSafety Check of Limit Control Air¯ow and Temperature RiseLimit Switches Rollout SwitchChecking and Adjusting Refrigerant Charge III. Cooling Section START-UP and AdjustmentsChecking Cooling Control Operation Unit ControlsBelt Drive Motors IV. Indoor Airflow and Airflow AdjustmentsVentilation Sequence Fan Rpm at Motor Pulley SettingsEvaporator Fan Motor Data 581B048 Air Delivery Ð Vertical Discharge Units 581B036 Air Delivery Ð Vertical Discharge Units581B072 Air Delivery Ð Vertical Discharge Units 581B060 Air Delivery Ð Vertical Discharge Units581B048 Air Delivery Ð Horizontal Discharge Units 581B036 Air Delivery Ð Horizontal Discharge Units581B072 Air Delivery Ð Horizontal Discharge Units 581B060 Air Delivery Ð Horizontal Discharge UnitsCare and Maintenanmce Service CleaningAIR Filter II. Lubrication IV. Economizer AdjustmentRefrigerant Charge VII. Flue GAS Passageways VI. Main BurnersVIII. COMBUSTION-AIR Blower LED Error Code Description IX. Limit SwitchLED Indication Error Code Description Burner IgnitionCleaning and Adjustment Removal and Replacement of Gas Train SeeXI. Replacement Parts LED Error Code Service Analysis TroubleshootingHeating Service Analysis Problem Cause RemedyCooling Service Analysis OAT Varislide Economizer TroubleshootingSAT Damper does not open Parablade Economizer TroubleshootingDamper does not close Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.