Bryant installation instructions 581B036 Air Delivery Ð Horizontal Discharge Units

Page 26

Table 13 Ð 581B036 Air Delivery Ð Horizontal Discharge Units

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.1

 

0.2

 

0.3

0.4

 

 

0.5

 

0.6

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

526

 

0.06

584

 

0.08

656

 

0.12

734

 

0.22

818

 

0.25

875

 

0.27

1000

570

 

0.09

627

 

0.13

738

 

0.19

800

 

0.26

848

 

0.29

895

 

0.31

1100

614

 

0.13

670

 

0.16

758

 

0.23

812

 

0.29

863

 

0.32

914

 

0.35

1200

658

 

0.16

710

 

0.23

780

 

0.28

840

 

0.32

889

 

0.36

938

 

0.40

1300

703

 

0.20

752

 

0.27

808

 

0.32

868

 

0.37

916

 

0.41

963

 

0.45

1400

725

 

0.29

776

 

0.31

845

 

0.38

891

 

0.42

937

 

0.47

983

 

0.51

1500

755

 

0.33

816

 

0.38

870

 

0.43

924

 

0.48

969

 

0.53

1014

 

0.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.7

 

0.8

 

0.9

1.0

 

 

1.1

 

1.2

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

924

 

0.32

953

 

0.35

989

 

0.38

1028

 

0.42

1074

 

0.45

1120

 

0.50

1000

936

 

0.35

977

 

0.39

1020

 

0.44

1064

 

0.48

1124

 

0.52

1185

 

0.55

1100

960

 

0.39

1005

 

0.43

1052

 

0.49

1100

 

0.52

1163

 

0.56

1225

 

0.60

1200

988

 

0.45

1038

 

0.50

1076

 

0.53

1136

 

0.59

1201

 

0.61

1266

 

0.64

1300

1012

 

0.51

1061

 

0.56

1094

 

0.61

1172

 

0.65

1239

 

0.69

1306

 

0.72

1400

1027

 

0.56

1071

 

0.60

1108

 

0.67

1208

 

0.70

1278

 

0.75

1347

 

0.79

1500

1056

 

0.63

1097

 

0.68

1117

 

0.70

1245

 

0.74

1315

 

0.80

1385

 

0.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive required. (See Note 2.)

2.Motor drive range is 760 to 1090 rpm. All other rpms require ®eld-supplied drive.

3.Values include losses for ®lters, unit casing, and wet coils.

4.Maximum continuous bhp is 1.2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence.

Using your fan motors up to the ratings shown will not result in nuisance trip- ping or premature motor failure. Unit warranty will not be affected.

5.Use of a ®eld-supplied motor may affect wire sizing. Contact your local repre- sentative to verify.

6.Interpolation is permissible. Do not extrapolate.

7.Minimum allowable cfm is 300 cfm/ton.

Table 14 Ð 581B048 Air Delivery Ð Horizontal Discharge Units

 

 

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

(Cfm)

 

0.1

 

0.2

0.3

 

 

0.4

 

 

0.6

 

0.7

 

0.8

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

569

 

0.18

641

 

0.23

701

 

 

0.29

761

 

0.34

 

859

 

0.46

901

 

0.52

943

 

0.58

1300

604

 

0.22

673

 

0.28

731

 

 

0.34

788

 

0.39

 

887

 

0.52

928

 

0.59

968

 

0.65

1400

640

 

0.27

705

 

0.33

761

 

 

0.39

817

 

0.45

 

914

 

0.59

955

 

0.66

996

 

0.72

1500

676

 

0.32

738

 

0.38

793

 

 

0.45

847

 

0.51

 

940

 

0.65

982

 

0.73

1024

 

0.81

1600

713

 

0.38

772

 

0.44

825

 

 

0.51

877

 

0.58

 

967

 

0.73

1009

 

0.81

1051

 

0.89

1700

750

 

0.45

806

 

0.51

857

 

 

0.59

908

 

0.66

 

997

 

0.81

1037

 

0.90

1077

 

1.01

1800

788

 

0.52

841

 

0.59

890

 

 

0.67

939

 

0.75

 

1026

 

0.91

1065

 

1.01

1104

 

1.07

1900

826

 

0.60

876

 

0.68

924

 

 

0.76

971

 

0.84

 

1056

 

1.01

1094

 

1.10

1132

 

1.18

2000

864

 

0.70

912

 

0.77

958

 

 

0.86

1004

 

0.94

 

1087

 

1.12

1125

 

1.21

1162

 

1.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

(Cfm)

 

0.9

 

1.0

1.1

 

 

1.2

 

 

1.4

 

1.6

 

1.8

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

987

 

0.64

1030

 

0.70

1068

 

 

0.79

1106

 

0.87

 

1134

 

0.98

1189

 

1.12

1245

 

1.21

1300

1006

 

0.71

1044

 

0.77

1086

 

 

0.84

1128

 

0.91

 

1183

 

1.10

1226

 

1.23

1297

 

1.35

1400

1033

 

0.79

1069

 

0.86

1104

 

 

0.93

1139

 

1.01

 

1218

 

1.14

1286

 

1.34

1320

 

1.48

1500

1060

 

0.88

1095

 

0.95

1129

 

 

1.02

1162

 

1.09

 

1228

 

1.24

1303

 

1.40

1343

 

1.60

1600

1087

 

1.01

1123

 

1.05

1156

 

 

1.13

1185

 

1.20

 

1250

 

1.35

1319

 

1.51

1382

 

1.68

1700

1114

 

1.07

1151

 

1.15

1183

 

 

1.23

1215

 

1.31

 

1276

 

1.48

1334

 

1.64

1398

 

1.80

1800

1141

 

1.17

1178

 

1.26

1211

 

 

1.35

1243

 

1.43

 

1303

 

1.61

1359

 

1.78

1418

 

1.95

1900

1168

 

1.28

1204

 

1.37

1238

 

 

1.47

1271

 

1.56

 

1330

 

1.74

1386

 

1.93

1439

 

2.11

2000

1197

 

1.39

1231

 

1.48

1265

 

 

1.59

1298

 

1.69

 

1358

 

1.89

1413

 

2.08

1466

 

2.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive required. (See Note 4.)

2. indicates ®eld-supplied motor and drive required.

3.indicates maximum usable bhp.

4.Motor drive range: 840 to 1185 rpm. All other rpms require a ®eld-supplied drive.

5.Values include losses for ®lters, unit casing, and wet coils.

6.Maximum continuous bhp is 1.2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the ratings shown will not result in nuisance trip- ping or premature motor failure. Unit warranty will not be affected.

7.Use of a ®eld-supplied motor may affect wire sizing. Contact your local repre- sentative to verify.

8.Interpolation is permissible. Do not extrapolate.

9.Minimum allowable cfm is 300 cfm/ton.

Ð26Ð

Image 26
Contents Safety Considerations Important Ð Read Before InstallingContents Connection Sizes Standard Varislide Corner Unit Economizer WeightThreaded Wire Required Sizes Conduit USE Maximum Clearance InstallationLocate the Unit Roof Curb MountRoof Curb AccessoryService Plate Sizes Connector Unit Unit SizeIII. RIG and Place Unit Unit MAX Dimensions WeightII. Unit Duct Connections 581B 036Specications Base Unit 581BExternal Trap Condensate Drain Install Flue HoodIV. Field Connections Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Field Duct Connections Electrical ConnectionsGND CompEquip IFCRLA LRA FLA MCA MOCP² Power Supply Disconnect Voltage Range FAN MotorNominal Voltage Combustion Minimum Unit Compressor HacrÐ Electrical Data Units with Electrical Convenience Outlet Thermostat ListTypical Access Panel Locations Accessory Installation Optional Varislide EconomizerOptional Parablade Economizer ExampleOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit PRE-START-UP START-UP Compressor RotationII. Heating Section START-UP and Adjustments Pressure Rated Gas Inputs at Indicated Manifold PressuresAltitude Compensation* Ð Units 581B036-072 OrificesLimit Switches Air¯ow and Temperature RiseSafety Check of Limit Control Rollout SwitchChecking Cooling Control Operation III. Cooling Section START-UP and AdjustmentsChecking and Adjusting Refrigerant Charge Unit ControlsIV. Indoor Airflow and Airflow Adjustments Belt Drive MotorsEvaporator Fan Motor Data Fan Rpm at Motor Pulley SettingsVentilation Sequence 581B036 Air Delivery Ð Vertical Discharge Units 581B048 Air Delivery Ð Vertical Discharge Units581B060 Air Delivery Ð Vertical Discharge Units 581B072 Air Delivery Ð Vertical Discharge Units581B036 Air Delivery Ð Horizontal Discharge Units 581B048 Air Delivery Ð Horizontal Discharge Units581B060 Air Delivery Ð Horizontal Discharge Units 581B072 Air Delivery Ð Horizontal Discharge UnitsAIR Filter Service CleaningCare and Maintenanmce Refrigerant Charge IV. Economizer AdjustmentII. Lubrication VIII. COMBUSTION-AIR Blower VI. Main BurnersVII. Flue GAS Passageways LED Indication Error Code Description IX. Limit SwitchLED Error Code Description Burner IgnitionXI. Replacement Parts Removal and Replacement of Gas Train SeeCleaning and Adjustment Heating Service Analysis TroubleshootingLED Error Code Service Analysis Problem Cause RemedyCooling Service Analysis SAT Varislide Economizer TroubleshootingOAT Damper does not close Parablade Economizer TroubleshootingDamper does not open Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.