Bryant 581B installation instructions II. Heating Section START-UP and Adjustments

Page 18

II.HEATING SECTION START-UP AND ADJUSTMENTS

CAUTION: Complete the required procedures given in the Pre-Start-Up section on this page before starting unit.

Do not jumper any safety devices when operating the unit.

Ensure that burner ori®ces are properly aligned. Unstable operation may occur when the burner ori®ces in the mani- fold are misaligned.

Follow the lighting instructions on the heating section opera- tion label (located inside the burner access door) to start the heating section.

When lighting the unit for the ®rst time, perform the follow- ing additional steps: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recom- mended that the ground joint union be loosened and the supply line be allowed to purge until the odor of gas is de- tected. Never purge gas lines into a combustion chamber. Im- mediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit in accordance with Check- ing Heating Control Operation section below.

A. Checking Heating Control Operation

Start and check the unit for proper heating control operation as follows: (Also see unit lighting instructions located inside the burner access panel.)

1.Turn on unit electrical supply and manual gas valve.

2.Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature.

3.The induced-draft motor will start immediately. The evapo- rator fan will have a 45-second delay before starting.

4.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24-v power to W1.

5.The evaporator-fan motor will turn on 45 seconds after burner ignition.

6.The evaporator-fan motor will turn off 45 seconds after thermostat temperature is satis®ed.

7.Adjust air¯ow to obtain a temperature rise within the range speci®ed on the unit nameplate.

NOTE: The default value for the evaporator-fan motor ON/ OFF delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modi®es this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be ex- tended to 180 seconds. When one ¯ash of the light-emitting diode (LED) is observed, the evaporator-fan ON/OFF delay has been modi®ed.

If the limit switch trips at the start of the heating cycle dur- ing the evaporator ON delay, the time period of the ON delay for the next cycle will be 5 seconds less than the time at which the switch tripped.

EXAMPLE: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur at 25 seconds.

To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.

The evaporator-fan OFF delay can also be modi®ed. Once the call for heating has ended, there is a 10 minute period during which the modi®cation can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds. A maximum of 9 trips can occur, ex- tending the evaporator-fan OFF delay to 180 seconds.

To restore the original default value, reset the power to the unit.

To shut off unit set system switch selector at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting.

B. Safety Relief

A soft solder joint at the suction service Schrader port pro- vides pressure relief under abnormal temperature and pres- sure conditions.

C. Ventilation (Continuous Fan)

Set fan and system switch selectors at ON and OFF posi- tions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.

D. Gas Input

Check gas input and manifold pressure after unit start-up. (See Table 5.) If adjustment is required proceed as follows.

CAUTION: These units are designed to consume the rated gas inputs using the ®xed ori®ces at speci- ®ed manifold pressures as shown in Table 5. DO NOT REDRILL THE ORIFICES UNDER ANY CIRCUMSTANCES.

The rated gas inputs shown in Table 5 are for altitudes from sea level up to 2000 ft above sea level. These inputs are based on natural gas with a heating value of 1050 Btu/ft3 at

0.65speci®c gravity, or LP gas with a heating value of

2500 Btu/ft3 at 1.5 speci®c gravity. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. When the gas supply being used has a different heating value or speci®c gravity, refer to national and local codes, or contact your distributor or branch to determine the required ori®ce size. Refer to Table 6 for the correct ori®ce to use at high al- titudes. Kits are available from your distributor.

E. Adjusting Gas Input

The gas input to the unit is determined by measuring the gas ¯ow at the meter or by measuring the manifold pressure. Measuring the gas ¯ow at the meter is recommended for natu- ral gas units. The manifold pressure must be measured to determine the input of propane gas units.

Measuring Gas Flow at Meter Method Ð Natural Gas Units

Minor adjustment can be made by changing the manifold pres- sure. The manifold pressure must be maintained between 3.2 and 3.8 in. wg on high-®re, two-stage units. If larger adjust- ments are required, change main burner ori®ces following the recommendations of national and local codes.

NOTE: All other appliances that use the same meter must be turned off when gas ¯ow is measured at the meter.

Proceed as follows:

1.Turn off gas supply to unit.

2.Remove pipe plug on outlet of gas valve or manifold, then connect manometer at this point. Turn on gas to unit.

Ð18Ð

Image 18
Contents Important Ð Read Before Installing ContentsSafety Considerations Standard Varislide Corner Unit Economizer Weight Threaded Wire Required Sizes Conduit USE MaximumConnection Sizes Clearance InstallationLocate the Unit Roof Curb MountRoof Curb AccessoryService Plate Sizes Connector Unit Unit SizeIII. RIG and Place Unit Unit MAX Dimensions WeightII. Unit Duct Connections 581B 036Specications Base Unit 581BExternal Trap Condensate Drain Install Flue HoodIV. Field Connections Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Field Duct Connections Electrical ConnectionsGND CompEquip IFCRLA LRA FLA MCA MOCP² Power Supply Disconnect Voltage Range FAN MotorNominal Voltage Combustion Minimum Unit Compressor HacrÐ Electrical Data Units with Electrical Convenience Outlet Thermostat ListTypical Access Panel Locations Accessory Installation Optional Varislide EconomizerOptional Parablade Economizer ExampleOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit PRE-START-UP START-UP Compressor RotationII. Heating Section START-UP and Adjustments Pressure Rated Gas Inputs at Indicated Manifold PressuresAltitude Compensation* Ð Units 581B036-072 OrificesLimit Switches Air¯ow and Temperature RiseSafety Check of Limit Control Rollout SwitchChecking Cooling Control Operation III. Cooling Section START-UP and AdjustmentsChecking and Adjusting Refrigerant Charge Unit ControlsIV. Indoor Airflow and Airflow Adjustments Belt Drive MotorsFan Rpm at Motor Pulley Settings Ventilation SequenceEvaporator Fan Motor Data 581B036 Air Delivery Ð Vertical Discharge Units 581B048 Air Delivery Ð Vertical Discharge Units581B060 Air Delivery Ð Vertical Discharge Units 581B072 Air Delivery Ð Vertical Discharge Units581B036 Air Delivery Ð Horizontal Discharge Units 581B048 Air Delivery Ð Horizontal Discharge Units581B060 Air Delivery Ð Horizontal Discharge Units 581B072 Air Delivery Ð Horizontal Discharge UnitsService Cleaning Care and MaintenanmceAIR Filter IV. Economizer Adjustment II. LubricationRefrigerant Charge VI. Main Burners VII. Flue GAS PassagewaysVIII. COMBUSTION-AIR Blower LED Indication Error Code Description IX. Limit SwitchLED Error Code Description Burner IgnitionRemoval and Replacement of Gas Train See Cleaning and AdjustmentXI. Replacement Parts Heating Service Analysis TroubleshootingLED Error Code Service Analysis Problem Cause RemedyCooling Service Analysis Varislide Economizer Troubleshooting OATSAT Damper does not close Parablade Economizer TroubleshootingDamper does not open Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.