Bryant 581B Troubleshooting, LED Error Code Service Analysis, Heating Service Analysis

Page 33

TROUBLESHOOTING

Table 18 Ð LED Error Code Service Analysis

PROBLEM

CAUSE

REMEDY

Hardware failure.

Loss of power to IGC.

Check 5-amp fuse on IGC, power to unit, 24-v circuit breaker, and

(LED Off)

 

transformer. Units without a 24-v circuit breaker have an internal over-

 

 

load in the 24-v transformer. If the overload trips, allow 10 minutes for

 

 

automatic reset.

Limit switch fault.

High-temperature limit switch

Check the operation of the indoor (evaporator) fan motor. Ensure that

(LED 2 Flashes)

is open.

the supply-air temperature rise is in accordance with the range on the

 

 

unit nameplate.

Flame sense fault.

The IGC sensed ¯ame that

Reset unit. If problem persists, replace control board.

(LED 3 Flashes)

should not be present.

 

4 consecutive limit switch trips.

Inadequate air¯ow to unit.

Check operation of indoor (evaporator) fan motor and that supply-air

(LED 4 Flashes)

 

temperature rise agrees with range on unit nameplate information.

Ignition lockout.

Unit unsuccessfully attempted

Check ignitor and ¯ame sense electrode spacing, gas, etc. Ensure that

(LED 5 Flashes)

ignition for 15 minutes.

¯ame sense and ignition wires are properly terminated. Verify that unit

 

 

is obtaining proper amount of gas.

Induced-draft motor fault.

IGC does not sense that

Check for proper voltage. If motor is operating, check the speed sensor

(LED 6 Flashes)

induced-draft motor is operating.

plug/IGC Terminal J2 connection. Proper connection: PIN 1-White,

 

 

PIN 2-Red, PIN 3-Black.

Rollout switch fault.

Rollout switch has opened.

Rollout switch will automatically reset, but IGC will continue to lock out

(LED 7 Flashes)

 

unit. Check gas valve operation. Ensure that induced-draft blower

 

 

wheel is properly secured to motor shaft. Reset unit at unit disconnect.

Internal control fault.

Microprocessor has sensed an

If error code is not cleared by resetting unit power, replace the IGC.

(LED 8 Flashes)

error in the software or hardware.

 

LEGEND

IGC Ð Integrated Gas Unit Controller

LED Ð Light-Emitting Diode

WARNING: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.

IMPORTANT: Refer to Table 19 Ð Heating Service Analysis for ad- ditional troubleshooting analysis.

Table 19 Ð Heating Service Analysis

PROBLEM

CAUSE

REMEDY

Burners will not

Misaligned spark electrodes.

Check ¯ame ignition and sensor electrode positioning. Adjust as needed.

ignite.

No gas at main burners.

Check gas line for air, purge as necessary. After purging gas line of air, allow gas

 

 

to dissipate for at least 5 minutes before attempting to relight unit.

 

 

Check gas valve.

 

Water in gas line.

Drain water and install drip leg to trap water.

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

No 24 v power supply to

Check transformer. Transformers with internal overcurrent protection require a cool

 

control circuit.

down period before resetting. Check 24-v circuit breaker, reset as necessary.

 

Miswired or loose connections.

Check all wiring and wirenut connections.

 

Burned-out heat anticipator in

Replace thermostat.

 

thermostat.

 

 

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

Inadequate heating.

Dirty air ®lter.

Clean or replace ®lter as necessary.

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input. If too low, increase

 

 

manifold pressure, or replace with correct ori®ces.

 

Unit undersized for application.

Replace with proper unit or add additional unit.

 

Restricted air¯ow.

Clean ®lter, replace ®lter, or remove any restrictions.

 

Blower speed too low.

Install ®eld-supplied motor and drive or adjust pulley to increase fan speed.

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings, and temperature rise

 

 

of unit. Adjust as needed.

 

Too much outdoor air.

Adjust minimum position.

 

 

Check economizer operation.

Poor ¯ame

Incomplete combustion (lack of

Check all screws around ¯ue outlets and burner compartment. Tighten as

characteristics.

combustion air) results in:

necessary.

 

Aldehyde odors, carbon monoxide,

Cracked heat exchanger.

 

sooting ¯ame, or ¯oating ¯ame.

 

 

Over®red unit Ð reduce input, change ori®ces, or adjust gas line or manifold

 

 

 

 

pressure.

 

 

Check vent for restriction. Clean as necessary.

 

 

Check ori®ce to burner alignment.

Burners will not

Unit is locked into Heating mode

Wait until mandatory one minute time period has elapsed or reset power to unit.

turn off.

for a one minute minimum.

 

Ð33Ð

Image 33
Contents Important Ð Read Before Installing ContentsSafety Considerations Standard Varislide Corner Unit Economizer Weight Threaded Wire Required Sizes Conduit USE MaximumConnection Sizes Locate the Unit InstallationClearance Roof Curb MountService Plate Sizes Connector Unit AccessoryRoof Curb Unit SizeII. Unit Duct Connections Unit MAX Dimensions WeightIII. RIG and Place Unit 581B 036Base Unit 581B SpecicationsIV. Field Connections Install Flue HoodExternal Trap Condensate Drain Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Electrical Connections Field Duct ConnectionsEquip CompGND IFCNominal Voltage Combustion Minimum Unit Compressor Power Supply Disconnect Voltage Range FAN MotorRLA LRA FLA MCA MOCP² HacrThermostat List Ð Electrical Data Units with Electrical Convenience OutletOptional Varislide Economizer Typical Access Panel Locations Accessory InstallationExample Optional Parablade EconomizerOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit START-UP Compressor Rotation PRE-START-UPII. Heating Section START-UP and Adjustments Altitude Compensation* Ð Units 581B036-072 Rated Gas Inputs at Indicated Manifold PressuresPressure OrificesSafety Check of Limit Control Air¯ow and Temperature RiseLimit Switches Rollout SwitchChecking and Adjusting Refrigerant Charge III. Cooling Section START-UP and AdjustmentsChecking Cooling Control Operation Unit ControlsBelt Drive Motors IV. Indoor Airflow and Airflow AdjustmentsFan Rpm at Motor Pulley Settings Ventilation SequenceEvaporator Fan Motor Data 581B048 Air Delivery Ð Vertical Discharge Units 581B036 Air Delivery Ð Vertical Discharge Units581B072 Air Delivery Ð Vertical Discharge Units 581B060 Air Delivery Ð Vertical Discharge Units581B048 Air Delivery Ð Horizontal Discharge Units 581B036 Air Delivery Ð Horizontal Discharge Units581B072 Air Delivery Ð Horizontal Discharge Units 581B060 Air Delivery Ð Horizontal Discharge UnitsService Cleaning Care and MaintenanmceAIR Filter IV. Economizer Adjustment II. LubricationRefrigerant Charge VI. Main Burners VII. Flue GAS PassagewaysVIII. COMBUSTION-AIR Blower LED Error Code Description IX. Limit SwitchLED Indication Error Code Description Burner IgnitionRemoval and Replacement of Gas Train See Cleaning and AdjustmentXI. Replacement Parts LED Error Code Service Analysis TroubleshootingHeating Service Analysis Problem Cause RemedyCooling Service Analysis Varislide Economizer Troubleshooting OATSAT Damper does not open Parablade Economizer TroubleshootingDamper does not close Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.