Bryant 581B II. Unit Duct Connections, III. RIG and Place Unit, Unit MAX Dimensions Weight

Page 5

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 5 Ð Unit Leveling Tolerances

II. UNIT DUCT CONNECTIONS

On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. On horizontal units, duct ¯anges should be attached to horizontal openings and all ductwork should be secured to ¯anges. Insulate and weath- erproof all external ductwork, joints, and roof openings with counter ¯ashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be in- sulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable ®re codes.

A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed −0.35 in. wg with Varislide™ economizer, −0.35 in. wg with PARABLADE econo- mizer, or −0.45 in. wg without economizer.

NOTE: Connection must be made to roof curb before unit is set in place.

III. RIG AND PLACE UNIT

Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by us- ing unit frame as a reference. See Table 1 and Fig. 6 for ad- ditional information. Operating weight is shown in Table 1 and Fig. 6.

Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.

IMPORTANT: If unit has forklift protection skids, be sure to remove forklift protection skids from under unit before set- ting unit in place.

CAUTION: All panels must be in place when rigging.

A properly positioned unit will have the following clearances between unit and roof curb: 1¤4-in. clearance between roof curb and base rails on each side and front of unit; 15¤32-in. clear- ance between roof curb and rear of unit. See Fig. 4, Views A-A and C-C.

After unit is in position, remove shipping materials and rig- ging skids.

NOTES:

1. Dimension in ( ) are in millimeters.

2.Hook rigging shackles through holes in base rail as shown in detail ``A.'' Holes in base rails are centered around the unit center of grav- ity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

3.Weights include base unit without economizer. See Table 1 for unit operating weights with an economizer.

CAUTION: All panels must be in place when rigging.

UNIT

MAX

 

 

DIMENSIONS

 

 

 

WEIGHT

``A''

``B''

 

``C''

 

581B

 

 

 

Lb

Kg

in.

mm

in.

 

mm

in.

 

mm

036

530

240

73.69

1872

35.50

 

902

33.31

 

847

048

540

245

73.69

1872

35.50

 

902

33.31

 

847

060

560

254

73.69

1872

35.50

 

902

33.31

 

847

072

615

279

73.69

1872

35.50

 

902

33.31

 

847

Fig. 6 Ð Rigging Details

Ð5Ð

Image 5
Contents Safety Considerations Important Ð Read Before InstallingContents Connection Sizes Standard Varislide Corner Unit Economizer WeightThreaded Wire Required Sizes Conduit USE Maximum Locate the Unit InstallationClearance Roof Curb MountService Plate Sizes Connector Unit AccessoryRoof Curb Unit SizeII. Unit Duct Connections Unit MAX Dimensions WeightIII. RIG and Place Unit 581B 036Base Unit 581B SpecicationsIV. Field Connections Install Flue HoodExternal Trap Condensate Drain Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Electrical Connections Field Duct ConnectionsEquip CompGND IFCNominal Voltage Combustion Minimum Unit Compressor Power Supply Disconnect Voltage Range FAN MotorRLA LRA FLA MCA MOCP² HacrThermostat List Ð Electrical Data Units with Electrical Convenience OutletOptional Varislide Economizer Typical Access Panel Locations Accessory InstallationExample Optional Parablade EconomizerOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit START-UP Compressor Rotation PRE-START-UPII. Heating Section START-UP and Adjustments Altitude Compensation* Ð Units 581B036-072 Rated Gas Inputs at Indicated Manifold PressuresPressure OrificesSafety Check of Limit Control Air¯ow and Temperature RiseLimit Switches Rollout SwitchChecking and Adjusting Refrigerant Charge III. Cooling Section START-UP and AdjustmentsChecking Cooling Control Operation Unit ControlsBelt Drive Motors IV. Indoor Airflow and Airflow AdjustmentsEvaporator Fan Motor Data Fan Rpm at Motor Pulley SettingsVentilation Sequence 581B048 Air Delivery Ð Vertical Discharge Units 581B036 Air Delivery Ð Vertical Discharge Units581B072 Air Delivery Ð Vertical Discharge Units 581B060 Air Delivery Ð Vertical Discharge Units581B048 Air Delivery Ð Horizontal Discharge Units 581B036 Air Delivery Ð Horizontal Discharge Units581B072 Air Delivery Ð Horizontal Discharge Units 581B060 Air Delivery Ð Horizontal Discharge UnitsAIR Filter Service CleaningCare and Maintenanmce Refrigerant Charge IV. Economizer AdjustmentII. Lubrication VIII. COMBUSTION-AIR Blower VI. Main BurnersVII. Flue GAS Passageways LED Error Code Description IX. Limit SwitchLED Indication Error Code Description Burner IgnitionXI. Replacement Parts Removal and Replacement of Gas Train SeeCleaning and Adjustment LED Error Code Service Analysis TroubleshootingHeating Service Analysis Problem Cause RemedyCooling Service Analysis SAT Varislide Economizer TroubleshootingOAT Damper does not open Parablade Economizer TroubleshootingDamper does not close Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.