Bryant 581B Parablade Economizer Troubleshooting, Damper does not open, Damper does not close

Page 36

Table 22 Ð PARABLADE Economizer Troubleshooting

PROBLEM

CAUSE

 

REMEDY

Damper does not open.

Evaporator fan not on.

Check wiring between G on connection board and indoor fan contactor.

 

No power to economizer motor.

1. Disconnect power at TR and TR1. Disconnect jumper across P and P1.

 

 

2.

Connect jumper across TR and 1.

 

 

3.

Connect jumper across T1 and T.

 

 

4.

If connected, remove enthalpy sensor from terminals S0 and +. Factory-

 

 

 

installed 620 ohm resistor should be connected to terminals SR and +.

 

 

5.

Apply power (24 vac) to terminals TR and TR1. The LED should be off

 

 

 

and the damper should be in the closed position.

 

 

6.

Disconnect the factory-installed 620 ohm resistor from terminals SR and

 

 

 

+. The LED should light up and the motor should drive towards open. If

 

 

 

this does not happen, replace the economizer control module.

 

Economizer motor failure.

If the indoor fan and economizer motor are energized, verify that there is a

 

 

minimum of 24 vac at terminals TR and TR1. If the motor is not operating,

 

 

replace the motor.

Economizer operation

Economizer control module

1.

To simulate high or low enthalpy, reconnect the factory-installed 620 ohm

limited to minimum

failure.

 

resistor across terminals SR and +.

position.

 

2.

Connect 1.2 Kohm checkout resistor across terminals SO and +. Turn the

 

 

 

 

 

enthalpy set point to ``A.'' The LED should turn on, indicating low en-

 

 

 

thalpy. The motor should drive towards open. If LED does not light, re-

 

 

 

place module. If motor does not drive open, check motor operation.

 

 

3.

Turn the enthalpy set point to ``D.'' The LED should turn off, indicating

 

 

 

high enthalpy. The motor should drive towards closed. If these actions do

 

 

 

not occur, replace module.

 

 

4.

Disconnection 1.2 Kohm checkout resistor before resuming operation.

Damper does not close.

No power to economizer.

1. Disconnect power at TR and TR1. Disconnect jumper across P and P1.

 

 

2.

Connect jumper across TR and 1.

 

 

3.

Connect jumper across T1 and T.

 

 

4.

If connected, remove enthalpy sensor from terminals SO and +. Factory-

 

 

 

installed 620 ohm resistor should be connected to terminals SR and +.

 

 

5.

Apply power (24 Vac) to terminals TR and TR1. The LED should be off

 

 

 

and the damper should be in the closed position.

 

 

6.

Disconnect the factory-installed 620 ohm resistor from terminals SR and

 

 

 

+. The LED should light up and the motor should drive towards open. If

 

 

 

this does not happen, replace the economizer control module.

 

Return spring failure.

If power to unit is off and damper does not close, check for a bound linkage.

 

 

If linkage is not bound, then internal spring may be broken. Replace

 

 

actuator.

 

Economizer motor failure.

If the economizer control module is functioning properly, verify that there is a

 

 

minimum of 24 Vac at terminals TR and TR1. If the motor is not operating,

 

 

replace the motor.

Damper does not open

Sensor incorrectly wired or bad.

To verify sensor operation, reconnect the + lead of the outdoor enthalpy sen-

or close according to

 

sor to the + terminal of the economizer control module. Connect a DC mil-

enthalpy readings.

 

liammeter between terminals SO of the economizer control module and

 

 

terminals S of the enthalpy sensor. The milliammeter should indicate be-

 

 

tween 3 and 25 mA if the sensor is operating properly. If the milliammeter

 

 

indicates 0, the sensor may be wired backwards. If any other readings are

 

 

shown, replace the sensor.

Ð36Ð

Image 36
Contents Important Ð Read Before Installing ContentsSafety Considerations Standard Varislide Corner Unit Economizer Weight Threaded Wire Required Sizes Conduit USE MaximumConnection Sizes Installation Locate the UnitClearance Roof Curb MountAccessory Service Plate Sizes Connector UnitRoof Curb Unit SizeUnit MAX Dimensions Weight II. Unit Duct ConnectionsIII. RIG and Place Unit 581B 036Specications Base Unit 581BInstall Flue Hood IV. Field ConnectionsExternal Trap Condensate Drain Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Field Duct Connections Electrical ConnectionsComp EquipGND IFCPower Supply Disconnect Voltage Range FAN Motor Nominal Voltage Combustion Minimum Unit CompressorRLA LRA FLA MCA MOCP² HacrÐ Electrical Data Units with Electrical Convenience Outlet Thermostat ListTypical Access Panel Locations Accessory Installation Optional Varislide EconomizerOptional Parablade Economizer ExampleOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit PRE-START-UP START-UP Compressor RotationII. Heating Section START-UP and Adjustments Rated Gas Inputs at Indicated Manifold Pressures Altitude Compensation* Ð Units 581B036-072Pressure OrificesAir¯ow and Temperature Rise Safety Check of Limit ControlLimit Switches Rollout SwitchIII. Cooling Section START-UP and Adjustments Checking and Adjusting Refrigerant ChargeChecking Cooling Control Operation Unit ControlsIV. Indoor Airflow and Airflow Adjustments Belt Drive MotorsFan Rpm at Motor Pulley Settings Ventilation SequenceEvaporator Fan Motor Data 581B036 Air Delivery Ð Vertical Discharge Units 581B048 Air Delivery Ð Vertical Discharge Units581B060 Air Delivery Ð Vertical Discharge Units 581B072 Air Delivery Ð Vertical Discharge Units581B036 Air Delivery Ð Horizontal Discharge Units 581B048 Air Delivery Ð Horizontal Discharge Units581B060 Air Delivery Ð Horizontal Discharge Units 581B072 Air Delivery Ð Horizontal Discharge UnitsService Cleaning Care and MaintenanmceAIR Filter IV. Economizer Adjustment II. LubricationRefrigerant Charge VI. Main Burners VII. Flue GAS PassagewaysVIII. COMBUSTION-AIR Blower IX. Limit Switch LED Error Code DescriptionLED Indication Error Code Description Burner IgnitionRemoval and Replacement of Gas Train See Cleaning and AdjustmentXI. Replacement Parts Troubleshooting LED Error Code Service AnalysisHeating Service Analysis Problem Cause RemedyCooling Service Analysis Varislide Economizer Troubleshooting OATSAT Parablade Economizer Troubleshooting Damper does not openDamper does not close Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.