Bryant 581B VI. Main Burners, VII. Flue GAS Passageways, VIII. COMBUSTION-AIR Blower

Page 30

B. Low Charge Cooling

Using Cooling Charging Charts, Fig. 39-42, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct super- heat for the various operating conditions. Accurate pressure gage and temperature-sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature-sensing device on the suction line and insu- late it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal oper- ating range of the unit.

C. To Use Cooling Charging Charts

Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully re- claim some of the charge. Recheck the suction pressure as charge is adjusted.

EXAMPLE: (Fig. 41)

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . . 48 F (Suction Temperature may vary ± 5 F.)

D. Refrigerant Leaks

Proceed as follows to repair a refrigerant leak and to charge the unit:

1.Locate leak and ensure that refrigerant system pres- sure has been relieved.

2.Repair leak following accepted practices.

NOTE: Replace ®lter drier in the liquid line whenever the system has been opened for repair.

3.Add a small charge of R-22 refrigerant vapor to system and leak-test unit.

4.Evacuate refrigerant system if additional leaks are not found.

5.Charge unit with R-22 refrigerant, using a volumetric- charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refriger- ant to compensate for internal volume of ®lter drier.

VI. MAIN BURNERS

At the beginning of each heating season, inspect for deterio- ration or blockage due to corrosion or other causes. Observe the main burner ¯ames and adjust if necessary.

VII. FLUE GAS PASSAGEWAYS

To inspect the ¯ue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor assem- bly according to directions in Combustion-Air Blower sec- tion below.

2.Remove the 3 screws holding the blower housing to the ¯ue cover.

3.Remove the ¯ue cover to inspect the heat exchanger.

4.Clean all surfaces as required using a wire brush.

VIII. COMBUSTION-AIR BLOWER

Clean periodically to ensure proper air¯ow and heating effi- ciency. Inspect blower wheel every fall and periodically dur- ing heating season. For the ®rst heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.

Fig. 39 Ð Cooling Charging Chart, 581B036

Fig. 40 Ð Cooling Charging Chart, 581B048

To inspect blower wheel, remove draft hood and screen. Shine a ¯ashlight into opening to inspect wheel. If cleaning is re- quired, remove motor and wheel as follows:

1.Slide burner access panel out.

2.Remove the 2 screws which hold the heat shield in place, and remove heat shield.

3.Remove the 7 screws that attach induced-draft motor mounting plate to blower housing (Fig. 43).

Ð30Ð

Image 30
Contents Important Ð Read Before Installing ContentsSafety Considerations Standard Varislide Corner Unit Economizer Weight Threaded Wire Required Sizes Conduit USE MaximumConnection Sizes Clearance InstallationLocate the Unit Roof Curb MountRoof Curb AccessoryService Plate Sizes Connector Unit Unit SizeIII. RIG and Place Unit Unit MAX Dimensions WeightII. Unit Duct Connections 581B 036Specications Base Unit 581BExternal Trap Condensate Drain Install Flue HoodIV. Field Connections Gas Piping FigNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Field Duct Connections Electrical ConnectionsGND CompEquip IFCRLA LRA FLA MCA MOCP² Power Supply Disconnect Voltage Range FAN MotorNominal Voltage Combustion Minimum Unit Compressor HacrÐ Electrical Data Units with Electrical Convenience Outlet Thermostat ListTypical Access Panel Locations Accessory Installation Optional Varislide EconomizerOptional Parablade Economizer ExampleOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit PRE-START-UP START-UP Compressor RotationII. Heating Section START-UP and Adjustments Pressure Rated Gas Inputs at Indicated Manifold PressuresAltitude Compensation* Ð Units 581B036-072 OrificesLimit Switches Air¯ow and Temperature RiseSafety Check of Limit Control Rollout SwitchChecking Cooling Control Operation III. Cooling Section START-UP and AdjustmentsChecking and Adjusting Refrigerant Charge Unit ControlsIV. Indoor Airflow and Airflow Adjustments Belt Drive MotorsFan Rpm at Motor Pulley Settings Ventilation SequenceEvaporator Fan Motor Data 581B036 Air Delivery Ð Vertical Discharge Units 581B048 Air Delivery Ð Vertical Discharge Units581B060 Air Delivery Ð Vertical Discharge Units 581B072 Air Delivery Ð Vertical Discharge Units581B036 Air Delivery Ð Horizontal Discharge Units 581B048 Air Delivery Ð Horizontal Discharge Units581B060 Air Delivery Ð Horizontal Discharge Units 581B072 Air Delivery Ð Horizontal Discharge UnitsService Cleaning Care and MaintenanmceAIR Filter IV. Economizer Adjustment II. LubricationRefrigerant Charge VI. Main Burners VII. Flue GAS PassagewaysVIII. COMBUSTION-AIR Blower LED Indication Error Code Description IX. Limit SwitchLED Error Code Description Burner IgnitionRemoval and Replacement of Gas Train See Cleaning and AdjustmentXI. Replacement Parts Heating Service Analysis TroubleshootingLED Error Code Service Analysis Problem Cause RemedyCooling Service Analysis Varislide Economizer Troubleshooting OATSAT Damper does not close Parablade Economizer TroubleshootingDamper does not open Or close according toTypical Wiring Schematic and Component Arrangement Component Arrangement Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.