Bryant 581B IV. Field Connections, External Trap Condensate Drain, Install Flue Hood

Page 7

IV. FIELD CONNECTIONS

A. External Trap Condensate Drain

The unit's 3¤4-in. condensate drain connections are located at the bottom and side of the unit. Unit discharge connec- tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug from the bottom con- nection to the side connection. See Fig. 7. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drain- age. Install a trap at least 4-in. deep and protect against freeze- up. See Fig. 8. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.

B. Install Flue Hood

Flue hood is shipped screwed to the burner compartment ac- cess panel. Remove from shipping location and using screws provided, install ¯ue hood in location shown in Fig. 2 and 9.

NOTE: Drain plug is shown in factory-installed position.

Fig. 7 Ð Condensate Drain Pan

NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A 4-in. trap is recommended.

Fig. 8 Ð External Trap Condensate Drain

Fig. 9 Ð Flue Hood Details

For units being installed in California Air Quality Manage- ment Districts which require NOx emissions of 40 nanograms/ joule or less, kit CRLOWNOX001A00 must be installed.

C. Gas Piping (Fig. 10)

Unit is equipped for use with type of gas shown on nameplate.

The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1¤2-in. female NPT gas inlet on the manual shutoff or gas valve.

Install a separate gas supply line that runs directly from the meter to the heating section. Refer to Table 2 and the NFGC for gas pipe sizing. Do not use cast iron pipe. Check the local utility for recommendations concerning existing lines. Choose a supply pipe that is large enough to keep the pressure loss as low as practical. Never use pipe smaller than the 1¤2-in. fe- male NPT gas inlet on the unit gas valve.

For natural gas applications, the gas pressure at unit gas con- nection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 581B048,060,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

LEGEND

NFGC Ð National Fuel Gas Code

*Field Supplied.

NOTE: Follow all local codes.

STEEL PIPE NOMINAL

SPACING OF SUPPORTS

DIAMETER (in.)

X DIMENSION (ft)

1¤2

6

3¤4 or 1

8

11¤4 or Larger

10

Fig. 10 Ð Gas Piping Guide

(With Accessory Utility Connections Package)

Ð7Ð

Image 7
Contents Contents Important Ð Read Before InstallingSafety Considerations Threaded Wire Required Sizes Conduit USE Maximum Standard Varislide Corner Unit Economizer WeightConnection Sizes Roof Curb Mount InstallationLocate the Unit ClearanceUnit Size AccessoryService Plate Sizes Connector Unit Roof Curb581B 036 Unit MAX Dimensions WeightII. Unit Duct Connections III. RIG and Place UnitBase Unit 581B SpecicationsGas Piping Fig Install Flue HoodIV. Field Connections External Trap Condensate DrainNominal Internal Length of PIPE, FT Iron Pipe Diameter Size Electrical Connections Field Duct ConnectionsIFC CompEquip GNDHacr Power Supply Disconnect Voltage Range FAN MotorNominal Voltage Combustion Minimum Unit Compressor RLA LRA FLA MCA MOCP²Thermostat List Ð Electrical Data Units with Electrical Convenience OutletOptional Varislide Economizer Typical Access Panel Locations Accessory InstallationExample Optional Parablade EconomizerOutdoor-Air Thermostat/Enthalpy Control Installation Parablade Economizer Installed in Unit START-UP Compressor Rotation PRE-START-UPII. Heating Section START-UP and Adjustments Orifices Rated Gas Inputs at Indicated Manifold PressuresAltitude Compensation* Ð Units 581B036-072 PressureRollout Switch Air¯ow and Temperature RiseSafety Check of Limit Control Limit SwitchesUnit Controls III. Cooling Section START-UP and AdjustmentsChecking and Adjusting Refrigerant Charge Checking Cooling Control OperationBelt Drive Motors IV. Indoor Airflow and Airflow AdjustmentsVentilation Sequence Fan Rpm at Motor Pulley SettingsEvaporator Fan Motor Data 581B048 Air Delivery Ð Vertical Discharge Units 581B036 Air Delivery Ð Vertical Discharge Units581B072 Air Delivery Ð Vertical Discharge Units 581B060 Air Delivery Ð Vertical Discharge Units581B048 Air Delivery Ð Horizontal Discharge Units 581B036 Air Delivery Ð Horizontal Discharge Units581B072 Air Delivery Ð Horizontal Discharge Units 581B060 Air Delivery Ð Horizontal Discharge UnitsCare and Maintenanmce Service CleaningAIR Filter II. Lubrication IV. Economizer AdjustmentRefrigerant Charge VII. Flue GAS Passageways VI. Main BurnersVIII. COMBUSTION-AIR Blower Burner Ignition IX. Limit SwitchLED Error Code Description LED Indication Error Code DescriptionCleaning and Adjustment Removal and Replacement of Gas Train SeeXI. Replacement Parts Problem Cause Remedy TroubleshootingLED Error Code Service Analysis Heating Service AnalysisCooling Service Analysis OAT Varislide Economizer TroubleshootingSAT Or close according to Parablade Economizer TroubleshootingDamper does not open Damper does not closeTypical Wiring Schematic and Component Arrangement Component Arrangement Page III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 52 pages 16.87 Kb Manual 64 pages 44.36 Kb

581B specifications

The Bryant 581B is an innovative and highly efficient gas furnace that stands out in the HVAC market for its remarkable performance, reliability, and advanced features. Designed to provide optimal heating comfort, the Bryant 581B is perfect for homeowners seeking both quality and energy efficiency.

One of the main features of the Bryant 581B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 80%, this gas furnace maximizes energy usage, ensuring that a significant portion of the fuel is converted into heat for your home. This efficiency not only translates into lower energy bills but also reduces the carbon footprint, making it an environmentally friendly choice.

The furnace is equipped with a multi-speed blower motor that enhances comfort by providing consistent airflow throughout the home. This technology adjusts to different heating demands, ensuring that every room reaches the desired temperature without the discomfort of hot or cold spots. The quiet operation of the blower motor also adds to the overall comfort, creating a peaceful home environment.

Another notable characteristic of the Bryant 581B is its durable construction. It features a robust heat exchanger built from high-quality materials, designed to withstand the rigors of daily use. The compact design of the furnace allows it to fit seamlessly into various spaces, making it an ideal choice for both new installations and replacement projects.

The Bryant 581B also comes with advanced safety features, including a self-diagnostic control board that monitors the system's performance. This feature allows for easy troubleshooting and maintenance, prolonging the life of the furnace. Additionally, the furnace is equipped with an induced draft blower that enhances venting efficiency and safety by ensuring that combustion gases are safely expelled from the home.

For homeowners looking for enhanced control, the Bryant 581B is compatible with a range of smart thermostats, providing the ability to monitor and adjust heating settings remotely. This integration with smart technology ensures that homeowners can maintain their desired comfort levels while maximizing efficiency.

In conclusion, the Bryant 581B gas furnace is a top-tier option that combines efficiency, durability, and modern technology. With its high AFUE rating, multi-speed blower, and advanced safety features, it promises to deliver unparalleled comfort and peace of mind for years to come. Whether for a new build or an upgrade, the Bryant 581B is an investment that pays off in both comfort and savings.