Carrier PCV015-060 specifications Unit Start-Up Cooling Mode, Operating Limits 50PCH,PCV Units

Page 28

Table 14 — Operating Limits — 50PCH,PCV Units

AIR LIMITS

50PCH,PCV

Cooling (F)

Heating (F)

 

Min. Ambient Air – db

45

39

Rated Ambient Air – db

80.6

68

Max. Ambient Air – db

110

85

Min. Entering Air – db/wb

50

40

Rated Entering Air – db/wb

80.6/66.2

68

Max. Entering Air – db/wb

110/83

80

WATER LIMITS

 

 

Min. Entering Water

30

20

Normal Entering Water

50-110

30-70

Max. Entering Water

120

90

Normal Water Flow

2.5-3.0 gpm per ton

LEGEND

 

 

db — Dry Bulb wb — Wet Bulb

Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the prop- er direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

1.Turn off power to the unit. Install disconnect tag.

2.Reverse any two of the unit power leads.

3.Reapply power to the unit and verify pressures are correct.

The suction and discharge pressure levels should now move to their normal start-up levels.

When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.

After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.

NOTE: There is a 5-minute time delay before the compressor will start.

Unit Start-Up Cooling Mode

1.Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres- sor activates.

2.Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.

3.Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. See Table 15. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap includes a water seal.

4.Check the temperature of both supply and discharge wa- ter. Compare to Tables 16-22. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 16-22.

5.Check air temperature drop across the coil when com- pressor is operating. Air temperature drop should be between 15 and 25 F.

Table 15 — Water Temperature Change

Through Heat Exchanger

 

COOLING

HEATING

WATER FLOW RATE (GPM)

RISE (F)

DROP (F)

 

Min

Max

Min

Max

For Closed Loop: Ground Source or

9

12

4

8

Cooling/Boiler Systems at 3 gpm/ton

 

 

 

 

For Open Loop: Ground Water Systems at

20

26

10

17

1.5 gpm/ton

 

 

 

 

Table 16 — 50PC015,018 Typical Unit Operating Pressures and Temperatures

ENTERING

 

 

 

COOLING

 

 

 

 

 

HEATING

 

 

 

 

 

WATER

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

 

FLOW

 

TEMP

Pressure

Pressure

heat

cooling

Temp

Drop

Pressure

Pressure

heat

cooling

Temp

Rise

 

(F)

(GPM/ton)

Rise

Drop

 

 

(psig)

(psig)

(F)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

 

(F)

 

(F) DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

120-130

155-175

27-32

11-16

16.9-19.9

16-22

73-

83

268-288

8-13

4-

9

6.1-

8.1

15-21

 

30

2.25

120-130

142-162

27-32

9-14

12.5-14.5

17-23

75-

85

270-290

8-13

4-

9

4.4-

6.4

16-22

 

 

3

120-130

128-148

27-32

9-14

8.1-10.1

17-23

78-

88

272-292

8-13

4-

9

2.9-

4.9

16-22

 

 

1.5

137-147

220-240

16-21

10-15

17.0-19.0

16-22

102-112

295-315

8-13

8-13

9.1-11.1

20-26

 

50

2.25

137-147

206-226

16-21

8-13

12.6-14.6

17-23

106-116

297-317

8-13

8-13

6.9-

8.9

21-27

 

 

3

137-147

192-212

16-21

8-13

8.4-10.4

17-23

110-120

299-319

8-13

8-13

4.7-

6.7

21-27

 

 

1.5

142-152

287-307

7-12

10-15

15.9-17.9

16-22

131-141

324-344

9-14

10-15

12.1-14.1

25-33

 

70

2.25

142-152

273-239

7-12

8-13

11.8-13.8

17-23

137-147

326-346

9-14

10-15

9.3-11.3

26-34

 

 

3

142-152

259-279

7-12

8-13

7.8- 9.8

17-23

144-154

328-348

9-14

10-15

6.6-

8.6

26-34

 

 

1.5

146-156

375-395

6-11

10-15

14.9-16.9

16-22

174-184

360-380

10-15

12-17

15.8-17.8

32-40

 

90

2.25

146-156

361-381

6-11

8-13

11.0-13.0

17-23

180-190

367-387

11-16

12-17

11.9-13.9

33-41

 

 

3

146-156

347-367

6-11

8-13

7.2- 9.2

17-23

187-197

374-394

12-17

12-17

8.0-10.0

33-41

 

110

1.5

154-164

478-498

6-11

10-15

14.0-16.0

16-22

 

 

 

 

2.25

154-164

461-481

6-11

8-13

10.2-12.2

16-22

 

 

 

 

 

3

154-164

445-465

6-11

8-13

6.5- 8.5

16-22

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB

Dry Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Heating Operation in This Temperature Range

 

 

 

 

 

 

 

 

 

 

 

 

28

Image 28
Contents Contents Safety ConsiderationsInstallation General203 218 50PCH,PCV Unit Physical Data209 224 8412 Connections 50PCHOpening Unit IPTTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Mount the Unit Install Condensate DrainA50-8489 Metal Hose Minimum Bend Radii A50-6261tfSlope to drain Wire Field Power Supply FittingLOC BMCMves NECRVS TXVHigh-Pressure Water Switch Power BlockHpws Clippable Field Selection JumperLoss of Charge Pressure Switch Condensate Pan Motorized Valve End Switch Temperature SwitchA50-8493 LONNational Electrical Code Temperature Switch A50-8440A50-8355 A50 83548356 LWT Wshp Open Control 50PCH,PCV Unit Electrical Data A50-8162MCA FLA HacrA50-8441 Wire Field ControlsA50-8442 Rnet Wiring Specifications Rnet WiringField-Supplied Sensors for Wshp Open Controller SPT SensorsPRE-START-UP Blower Speed Selection50PCV Blower Performance with Hot Water Reheat HWR Option 50PCV Blower Performance with Wet Coil50PCH,PCV Blower Performance Standard Unit 50PCH,PCV Blower Performance High-Static UnitDeluxe D Control Jumper Settings Refer to , 15, Complete C Control Jumper Settings Refer toField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsSTART-UP Operating LimitsWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits 50PCH,PCV Units 50PC030 Typical Unit Operating Pressures and Temperatures 50PC024 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and Temperatures 50PC048 Typical Unit Operating Pressures and Temperatures50PC060 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure HeatUnit Start-Up Heating Mode Unit Start-Up with Wshp Open ControlsCoaxial Water Pressure Drop 50PC Pressure DROP, psi kPaGpm 30 F 50 F 70 F 90 F SizeApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C and Deluxe D Board System Test Complete C Control LED Code Fault DescriptionsAquazone Deluxe D Control LED Indica Description Status LED Test LED ServiceESD Air Coil Fan Motor Removal Refrigerant Charging’ to 4’ Replacing the Wshp Open Controller’s Bat TroubleshootingA50-8163 Troubleshooting Air temperature out of rangeCooling mode FP1125 F or Reduced or no airflow in heatReduced or no water flow Reduced airflow in coolingAppendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Copyright 2009 Carrier Corporation 50PCH,PCV START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisA50-8445 A50-8446

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.