Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow 5 minutes between tests for the pressure or reversing valve to equalize.

1.Turn thermostat to lowest setting and set thermostat switch to HEAT position.

2.Slowly turn the thermostat to a higher temperature until the compressor activates.

3.Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.

4.Check the temperature of both supply and discharge wa- ter. Compare to Tables 16-22. If temperature is within range, proceed. If temperature is outside the range, check the heating refrigerant pressures in Tables 16-22.

5.Once the unit has begun to run, check for warm air deliv- ery at the unit grille.

6.Check air temperature rise across the coil when compres- sor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.

7.Check for vibration, noise and water leaks.

Unit Start-Up with WSHP Open Controls —

The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Automation System) system or provide additional capabilities to Carrier's WSHP product line. Most settings on the controller have factory defaults set for ease of installation. There are a few settings that must be configured in the field and several settings that can be adjusted if required by unique job condi- tions. Refer to Appendix A — WSHP Open Screen Configura- tion. In order to configure the unit, a BACview6 display is required. See Fig. 31.

NOTE: If the WSHP Open control has lost its programming, all display pixels will be displayed on the SPT sensor. See the WSHP Third Party Integration Guide.

When the unit is OFF, the SPT sensor will indicate OFF. When power is applied, the SPT sensor will indicate tempera- ture in the space at 78 F.

To start-up a unit with WSHP Open controls:

1.To plug in the BACview6 handheld display into a SPT sensor, point the two ears on the connector up and tilt the bottom of the plug toward you. Insert the plug up into the SPT sensor while pushing the bottom of the plug away from you.

2.BACview6 should respond with "Establishing Connec- tion." The Home screen will then appear on the display showing operating mode and space temperature. Press any button to continue.

See Appendix A — WSHP Open Screen Configuration for the hierarchal structure of the WSHP Open controller. All functions of the controller can be set from the Home screen.

3.When the Login is requested, type 1111 and push the OK softkey. The Logout will then be displayed to indicate the password was accepted.

4.To set the Clock if it is not already displayed:

a.Select System Settings from the Home screen, then press Clockset.

b.Scroll to hour, minute and second using the arrow keys. Use the number keypad to set actual time.

c.Scroll to day, month and year using arrow keys. Use number keypad to set date.

5.To set Daylight Savings Time (DST):

a.Push the DST softkey. The display will indicate 02:00:060 which is equal to 2:00AM.

b.To program the beginning and end dates, scroll down to the beginning month and press the enter key. The softkeys (INCR and DECR) will activate to increment the month in either direction, Jan, Feb, March, etc.

c.Use number keys to select the day of month and year.

d.Push the OK softkey to finalize the data.

6.To view configuration settings:

a.Select the Config softkey.

b.Select the Service Config softkey. Scroll through the factory settings by using the up and down arrow keys. See below for factory settings.

Only the following settings will need to be checked.

# of Fan Speeds — This should be set to "1" for units with PSC motors and set to "3" for units with ECM motors.

Compressor Stages — This should be set to "1."

Factory Dehumidification Reheat Coil — This should be set to "none" unless the modulating hot water reheat option is supplied in the unit, then set to "installed."

Fig. 31 — BACview6 Display Interface

*Sponsored by ASHRAE (American Society of Heating, Refrigerat- ing and Air Conditioning Engineers).

31

Image 31
Contents Safety Considerations ContentsGeneral Installation203 218 50PCH,PCV Unit Physical Data209 224 IPT 8412Connections 50PCH Opening UnitTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Mount the Unit Install Condensate DrainA50-8489 Metal Hose Minimum Bend Radii A50-6261tfSlope to drain Fitting Wire Field Power SupplyNEC LOCBMC MvesTXV RVSClippable Field Selection Jumper High-Pressure Water SwitchPower Block HpwsLON Loss of Charge Pressure Switch Condensate PanMotorized Valve End Switch Temperature Switch A50-8493A50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control FLA Hacr 50PCH,PCV Unit Electrical DataA50-8162 MCAA50-8441 Wire Field ControlsA50-8442 SPT Sensors Rnet Wiring SpecificationsRnet Wiring Field-Supplied Sensors for Wshp Open ControllerBlower Speed Selection PRE-START-UP50PCH,PCV Blower Performance High-Static Unit 50PCV Blower Performance with Hot Water Reheat HWR Option50PCV Blower Performance with Wet Coil 50PCH,PCV Blower Performance Standard UnitDeluxe D Control Jumper Settings Refer to , 15, Complete C Control Jumper Settings Refer toField Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits 50PCH,PCV Units 50PC030 Typical Unit Operating Pressures and Temperatures 50PC024 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat 50PC042 Typical Unit Operating Pressures and Temperatures50PC048 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and TemperaturesUnit Start-Up with Wshp Open Controls Unit Start-Up Heating ModeSize Coaxial Water Pressure Drop50PC Pressure DROP, psi kPa Gpm 30 F 50 F 70 F 90 FUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C and Deluxe D Board System Test Complete C Control LED Code Fault DescriptionsAquazone Deluxe D Control LED Indica Description Status LED Test LED ServiceESD Air Coil Fan Motor Removal Refrigerant Charging’ to 4’ Replacing the Wshp Open Controller’s Bat TroubleshootingA50-8163 Reduced or no airflow in heat TroubleshootingAir temperature out of range Cooling mode FP1125 F orReduced airflow in cooling Reduced or no water flowSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Service Appendix a Wshp Screen Open ConfigurationTest Point Name Password Editable Range Default Level Configuration ServiceScreen Name Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistA50-8446 Heating Cycle AnalysisCooling Cycle Analysis A50-8445

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.