Page 3

or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate- rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Verify that the unit is the correct model for the entering water temperature of the job.

3.Do not remove the packaging until the unit is ready for installation.

4.Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

5.Inspect all electrical connections. Be sure connections are clean and tight at the terminals.

6.Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.

7.Remove the four 1/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra- tion and sound alternation.

CAUTION

Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.

8.Remove any blower support cardboard from inlet of the blower.

9.Locate and verify any accessory kit located in compressor section.

10.Remove any access panel screws that may be difficult to remove once unit is installed.

Table 1 — 50PCH,PCV Unit Physical Data

50PCH,PCV UNIT

015

 

 

018

 

 

024

 

 

030

 

 

036

 

 

042

 

048

 

 

060

COMPRESSOR (1 each)

 

Rotary

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

 

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

 

 

R-410A

 

 

 

 

 

 

Factory Charge (oz)

32

 

 

43

 

 

43

 

 

47

 

 

50

 

 

70

 

74

 

 

82

 

 

 

 

 

 

 

FAN MOTOR AND BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Type/Speeds

 

 

 

 

 

 

 

 

 

 

PSC/3

 

 

 

 

 

 

Fan Motor (hp)

1/6

 

 

1/6

 

 

1/4

 

 

3/4

 

 

1/2

 

 

3/4

 

3/4

 

 

1

 

 

 

 

 

 

 

Blower Wheel Size (Dia x W) (in.)

 

8 x 7

 

 

 

9 x 7

 

 

9 x 8

 

 

10 x 10

 

 

11 x 10

WATER CONNECTION SIZE IPT (in.)

 

1/2

 

 

 

 

 

 

3/4

 

 

 

 

 

1

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

 

16 x 22

 

 

 

 

 

20 x 25

 

 

20 x 35

 

 

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty) 1 in. Throwaway

 

 

 

(1) 16 x 25

 

 

 

 

 

(1) 20 x 28 or

 

(1) 20 x 24,

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

(2) 20 x 14

 

(1) 20 x 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

153

 

 

158

 

 

189

 

 

197

 

 

203

 

 

218

 

263

 

 

303

 

 

 

 

 

Packaged

158

 

 

163

 

 

194

 

 

202

 

 

209

 

 

224

 

270

 

 

310

Corner Weight (lb)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Left-Front

53

 

 

55

 

 

62

 

 

67

 

 

75

 

 

81

 

98

 

 

103

Right-Front

36

 

 

37

 

 

40

 

 

41

 

 

47

 

 

50

 

60

 

 

64

Left-Back

34

 

 

35

 

 

39

 

 

40

 

 

44

 

 

48

 

58

 

 

61

Right-Back

30

 

 

31

 

 

33

 

 

34

 

 

37

 

 

39

 

47

 

 

75

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

20 x 17.25

 

 

 

 

 

24 x 17.75

 

24 x 28.25

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty) 1 in. Throwaway

 

 

 

(1) 20 x 20

 

 

 

 

 

(1) 24 x 24

 

(1) 14 x 28, (1) 18 x 24

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

153

 

 

158

 

 

189

 

 

197

 

 

203

 

 

218

 

263

 

 

278

 

 

 

 

 

Packaged

158

 

 

163

 

 

194

 

 

202

 

 

209

 

 

224

 

270

 

 

285

LEGEND

 

 

 

 

 

 

*Front is located at control box end.

 

 

 

 

 

 

IPT — Internal Pipe Thread

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

All units have grommet compressor mountings, and 1/2-in. and

PSC — Permanent Split Capacitor

 

 

 

 

 

 

 

 

 

 

 

 

3/4-in. electrical knockouts.

 

 

 

 

 

 

2. Maximum water working pressure is 500 psig.

3

Image 3
Contents Safety Considerations ContentsGeneral Installation50PCH,PCV Unit Physical Data 203 218209 224 IPT 8412Connections 50PCH Opening UnitTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Install Condensate Drain Mount the UnitA50-8489 A50-6261tf Metal Hose Minimum Bend RadiiSlope to drain Fitting Wire Field Power SupplyNEC LOCBMC MvesTXV RVSClippable Field Selection Jumper High-Pressure Water SwitchPower Block HpwsLON Loss of Charge Pressure Switch Condensate PanMotorized Valve End Switch Temperature Switch A50-8493A50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control FLA Hacr 50PCH,PCV Unit Electrical DataA50-8162 MCAWire Field Controls A50-8441A50-8442 SPT Sensors Rnet Wiring SpecificationsRnet Wiring Field-Supplied Sensors for Wshp Open ControllerBlower Speed Selection PRE-START-UP50PCH,PCV Blower Performance High-Static Unit 50PCV Blower Performance with Hot Water Reheat HWR Option50PCV Blower Performance with Wet Coil 50PCH,PCV Blower Performance Standard UnitComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units 50PC024 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat 50PC042 Typical Unit Operating Pressures and Temperatures50PC048 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and TemperaturesUnit Start-Up with Wshp Open Controls Unit Start-Up Heating ModeSize Coaxial Water Pressure Drop50PC Pressure DROP, psi kPa Gpm 30 F 50 F 70 F 90 FUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C Control LED Code Fault Descriptions Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Service Description Status LED Test LEDESD Refrigerant Charging Air Coil Fan Motor Removal’ to 4’ Troubleshooting Replacing the Wshp Open Controller’s BatA50-8163 Reduced or no airflow in heat TroubleshootingAir temperature out of range Cooling mode FP1125 F orReduced airflow in cooling Reduced or no water flowSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistA50-8446 Heating Cycle AnalysisCooling Cycle Analysis A50-8445

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.