Carrier PCV015-060 specifications 50PCH,PCV Unit Electrical Data, A50-8162, Mca, FLA Hacr, Fla

Page 21

Table 3 — 50PCH,PCV Unit Electrical Data

50PCH,PCV

VOLTAGE

RATED

VOLTAGE

COMPRESSOR

 

STANDARD UNITS

 

UNITS WITH HIGH STATIC BLOWER

UNIT SIZE

CODE

VOLTAGE

MIN/MAX

QTY

RLA

LRA

Fan Motor

 

Total Unit

MCA

Max Fuse/

Fan Motor

Total Unit

MCA

Max Fuse/

V-Ph-Hz*

 

 

 

 

 

 

 

 

FLA

 

 

FLA

 

HACR

FLA

FLA

 

HACR

015

 

3

208/230-1-60

197/254

1

6.0

29.0

1.00

 

 

7.0

8.5

15

1.00

1.00

7.0

15

 

4

265-1-60

239/292

1

5.4

28.0

0.86

 

 

6.3

7.6

15

0.86

0.86

6.3

15

 

 

 

 

018

 

3

208/230-1-60

197/254

1

7.2

33.0

1.00

 

 

8.2

10.0

15

1.50

1.50

8.7

15

 

4

265-1-60

239/292

1

5.9

28.0

0.86

 

 

6.8

8.2

15

1.30

1.30

7.2

15

 

 

 

 

024

 

3

208/230-1-60

197/254

1

12.8

58.3

1.50

 

 

14.3

17.5

30

3.00

3.00

15.8

30

 

4

265-1-60

239/292

1

9.6

54.0

1.30

 

 

10.9

13.3

20

2.70

2.70

12.3

20

 

 

 

 

 

 

3

208/230-1-60

197/254

1

14.1

73.0

3.00

 

 

17.1

20.6

30

3.00

3.00

17.1

30

030

 

4

265-1-60

239/292

1

11.2

60.0

2.70

 

 

13.9

16.7

25

2.70

2.70

13.9

25

 

5

208/230-3-60

197/254

1

8.9

58.0

3.00

 

 

11.9

14.1

20

3.00

3.00

11.9

20

 

 

 

 

 

 

6

460-3-60

414/506

1

4.2

28.0

1.70

 

 

5.9

7.0

15

1.70

1.70

5.9

15

 

 

3

208/230-1-60

197/254

1

16.7

79.0

1.80

 

 

18.5

22.7

35

3.00

3.00

19.7

40

036

 

4

265-1-60

239/292

1

13.5

72.0

2.00

 

 

15.5

18.9

30

2.70

2.70

16.2

30

 

5

208/230-3-60

197/254

1

10.4

73.0

1.80

 

 

12.2

14.8

25

3.00

3.00

13.4

25

 

 

 

 

 

 

6

460-3-60

414/506

1

5.8

38.0

1.24

 

 

7.0

8.5

15

1.70

1.70

7.5

15

 

 

3

208/230-1-60

197/254

1

17.9

112.0

3.00

 

 

20.9

25.4

40

3.00

3.00

20.9

40

042

 

5

208/230-3-60

197/254

1

13.5

88.0

3.00

 

 

16.5

19.9

30

3.00

3.00

16.5

30

 

6

460-3-60

414/506

1

6.0

44.0

1.70

 

 

7.7

9.2

15

1.70

1.70

7.7

15

 

 

 

 

 

 

1

575-3-60

518/633

1

4.9

34.0

1.40

 

 

6.3

7.5

15

1.40

1.40

6.3

15

 

 

3

208/230-1-60

197/254

1

21.8

117.0

3.40

 

 

25.2

30.7

50

4.90

4.90

26.7

50

048

 

5

208/230-3-60

197/254

1

13.7

83.1

3.40

 

 

17.1

20.5

30

4.90

4.90

18.6

35

 

6

460-3-60

414/506

1

6.2

41.0

1.80

 

 

8.0

9.6

15

2.50

2.50

8.7

15

 

 

 

 

 

 

1

575-3-60

518/633

1

4.8

33.0

1.40

 

 

6.2

7.4

15

1.90

1.90

6.7

15

 

 

3

208/230-1-60

197/254

1

26.3

134.0

4.90

 

 

31.2

37.8

60

5.80

5.80

32.1

60

060

 

5

208/230-3-60

197/254

1

15.6

110.0

4.90

 

 

20.5

24.4

40

5.80

5.80

21.4

40

 

6

460-3-60

414/506

1

7.8

52.0

2.50

 

 

10.3

12.3

20

2.60

2.60

10.4

20

 

 

 

 

 

 

1

575-3-60

518/633

1

5.8

38.9

1.90

 

 

7.7

9.2

15

2.30

2.30

8.1

15

 

 

LEGEND

 

 

 

 

 

*Units using 460-v and ECM (electronically commutated motor), modulating

FLA

Full Load Amps

 

 

 

 

 

HWR (hot water reheat), and/or internal secondary pump will require a neutral

 

 

 

 

 

wire from the supply side in order to feed accessory with 265-v.

 

HACR

Heating, Air Conditioning and Refrigeration

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

 

 

1. HACR circuit breaker in U.S.A. only.

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

2.

All fuses

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Class RK-5.

 

 

 

 

 

a50-8162

Fig. 23 — Typical Single-Phase Line Voltage Power Connection

21

Image 21
Contents Safety Considerations ContentsGeneral Installation50PCH,PCV Unit Physical Data 203 218209 224 Connections 50PCH 8412Opening Unit IPTTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units Install Condensate Drain Mount the UnitA50-8489 A50-6261tf Metal Hose Minimum Bend RadiiSlope to drain Fitting Wire Field Power SupplyBMC LOCMves NECTXV RVSPower Block High-Pressure Water SwitchHpws Clippable Field Selection JumperMotorized Valve End Switch Temperature Switch Loss of Charge Pressure Switch Condensate PanA50-8493 LONA50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control A50-8162 50PCH,PCV Unit Electrical DataMCA FLA HacrWire Field Controls A50-8441A50-8442 Rnet Wiring Rnet Wiring SpecificationsField-Supplied Sensors for Wshp Open Controller SPT SensorsBlower Speed Selection PRE-START-UP50PCV Blower Performance with Wet Coil 50PCV Blower Performance with Hot Water Reheat HWR Option50PCH,PCV Blower Performance Standard Unit 50PCH,PCV Blower Performance High-Static UnitComplete C Control Jumper Settings Refer to Deluxe D Control Jumper Settings Refer to , 15,Field Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsSTART-UP Operating LimitsUnit Start-Up Cooling Mode Water Temperature Change Through Heat ExchangerOperating Limits 50PCH,PCV Units 50PC024 Typical Unit Operating Pressures and Temperatures 50PC030 Typical Unit Operating Pressures and Temperatures50PC036 Typical Unit Operating Pressures and Temperatures 50PC048 Typical Unit Operating Pressures and Temperatures 50PC042 Typical Unit Operating Pressures and Temperatures50PC060 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure HeatUnit Start-Up with Wshp Open Controls Unit Start-Up Heating Mode50PC Pressure DROP, psi kPa Coaxial Water Pressure DropGpm 30 F 50 F 70 F 90 F SizeAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Complete C Control LED Code Fault Descriptions Complete C and Deluxe D Board System TestAquazone Deluxe D Control LED Indica Service Description Status LED Test LEDESD Refrigerant Charging Air Coil Fan Motor Removal’ to 4’ Troubleshooting Replacing the Wshp Open Controller’s BatA50-8163 Air temperature out of range TroubleshootingCooling mode FP1125 F or Reduced or no airflow in heatReduced airflow in cooling Reduced or no water flowAlarm Status Appendix a Wshp Open Screen ConfigurationStatus SensorMaintenance Appendix a Wshp Open Screen ConfigurationSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Point Name Password Editable Range Default LevelScreen Name Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistCooling Cycle Analysis Heating Cycle AnalysisA50-8445 A50-8446

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.