APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

Configuration

Service

Configuration

POINT NAME

PASSWORD

EDITABLE

RANGE

DEFAULT

NOTES

LEVEL

 

 

 

 

 

# of Fan Speeds

 

X

1,2,3

3

Used to set number of

 

fan motor speeds

 

 

 

 

 

 

 

 

 

 

When set to Fan On, G output is

 

 

 

 

 

energized when ever any fan speed

G Output Type

 

X

Fan On/Fan Low

Fan On

is active (required for ECM and Fan

 

control board). When set to Fan

 

 

 

 

 

 

 

 

 

 

Low, output is only energized for

 

 

 

 

 

Low Speed

Compressor Stages

 

X

One Stage/Two Stages

One Stage

Defines the number of

 

stages of compression

 

 

 

 

 

Reversing Valve Type

 

X

O type output/B type output

O type

Determines reversing valve

 

signal output type

 

 

 

 

 

Leaving Air Auxiliary

 

X

None/2-Position HW/1 Stage

None

Determines Auxiliary

Heat Type

 

Electric/Modulating HW

Reheat Coil Type

 

 

 

Entering Air Water

 

X

None/2-Position/Modulating

None

Determines Entering Air

Economizer Type

 

Economizer Coil Type

 

 

 

 

2-Position Water

 

X

Normally Closed/Normally Open

Normally

Determines type of 2-position

Valve Type

 

Closed

water valve used

 

 

 

Modulating Water

 

X

Normally Closed/Normally Open

Normally

Determines type of modulating

Valve Type

 

Closed

water valve used

 

 

 

Ventilation Damper

 

X

None/2-Position/DCV

None

Determines Type of ventilation

Type

 

damper control to be used

 

 

 

 

 

 

 

 

 

Used to determine ventilation

Damper Actuator Type

 

X

(0-10 volt)/(2-10 volt)

0-10 volt

damper output signal range

 

 

 

 

 

(closed - open)

Humidity Sensor

 

X

None/Installed

None

Set to Installed if Humidity

 

sensor is present

 

 

 

 

 

Factory Dehumidifica-

Admin Password

 

 

 

Set to Installed if factory-installed

level access only

X

None/Installed

None

dehumidification reheat coil

tion Reheat Coil

 

 

 

 

is present

 

 

 

 

 

Occupancy

 

X

Occupied Open/Occupied Closed

Occupied

Used to determine external occu-

Input Logic

 

CLOSED

pancy switch contact occupied state

 

 

 

Condensate Switch

 

X

5 - 600 seconds

10 sec

Delay before equipment alarms on

Alarm Delay

 

high condensate level

 

 

 

 

Condensate Switch

 

X

Alarm OPEN/Alarm CLOSED

Alarm

Determine Alarm state of

Alarm State

 

CLOSED

condensate switch input

 

 

 

Minimum Condenser

 

 

25 - 60 ° F

60 ° F

Determines the minimum

Water Temperature in

 

X

acceptable water loop temperature

Heating

 

 

 

 

to start heating

Maximum Condenser

 

 

65 - 100 ° F

90 ° F

Determines the maximum

Water Temperature in

 

X

acceptable water loop temperature

Heating

 

 

 

 

to start heating

Minimum Condenser

 

 

30 - 60 ° F

60 ° F

Determines the minimum

Water Temperature in

 

X

acceptable water loop temperature

Cooling

 

 

 

 

to start cooling

Maximum Condenser

 

 

85 - 120 ° F

95 ° F

Determines the maximum

Water Temperature in

 

X

acceptable water loop temperature

Cooling

 

 

 

 

to start cooling

IAQ sensor

 

X

0 - 5 ma

4 ma

Minimum output current (mA)

minimum input

 

for IAQ sensor

 

 

 

 

IAQ sensor

 

X

5 - 20 ma

20 ma

Maximum output current (mA) for

maximum input

 

IAQ sensor

 

 

 

 

IAQ sensor

 

X

0 - 9999 ppm

0 ppm

Corresponding value in ppm for

minimum output

 

minimum output current

 

 

 

 

IAQ sensor

 

X

0 - 9999 ppm

2000 ppm

Corresponding value in ppm for

maximum output

 

maximum output current

 

 

 

 

 

LEGEND

BAS

Building Automation System

DCV

Demand Controlled Ventilation

IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration

47

Image 47
Contents Safety Considerations ContentsGeneral Installation209 224 50PCH,PCV Unit Physical Data203 218 IPT 8412Connections 50PCH Opening UnitTypical Installation 50PCH Units A50-8413 Typical Vertical Installation 50PCV Units A50-8489 Install Condensate DrainMount the Unit Slope to drain A50-6261tfMetal Hose Minimum Bend Radii Fitting Wire Field Power SupplyNEC LOCBMC MvesTXV RVSClippable Field Selection Jumper High-Pressure Water SwitchPower Block HpwsLON Loss of Charge Pressure Switch Condensate PanMotorized Valve End Switch Temperature Switch A50-8493A50-8440 National Electrical Code Temperature SwitchA50-8355 8354 A508356 LWT Wshp Open Control FLA Hacr 50PCH,PCV Unit Electrical DataA50-8162 MCAA50-8442 Wire Field ControlsA50-8441 SPT Sensors Rnet Wiring SpecificationsRnet Wiring Field-Supplied Sensors for Wshp Open ControllerBlower Speed Selection PRE-START-UP50PCH,PCV Blower Performance High-Static Unit 50PCV Blower Performance with Hot Water Reheat HWR Option50PCV Blower Performance with Wet Coil 50PCH,PCV Blower Performance Standard UnitField Selectable Inputs Complete C Control Jumper Settings Refer toDeluxe D Control Jumper Settings Refer to , 15, Operating Limits DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options START-UPOperating Limits 50PCH,PCV Units Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger 50PC036 Typical Unit Operating Pressures and Temperatures 50PC024 Typical Unit Operating Pressures and Temperatures50PC030 Typical Unit Operating Pressures and Temperatures Temp GPM/ton Pressure Heat 50PC042 Typical Unit Operating Pressures and Temperatures50PC048 Typical Unit Operating Pressures and Temperatures 50PC060 Typical Unit Operating Pressures and TemperaturesUnit Start-Up with Wshp Open Controls Unit Start-Up Heating ModeSize Coaxial Water Pressure Drop50PC Pressure DROP, psi kPa Gpm 30 F 50 F 70 F 90 FUnits with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationUnits with Wshp Open Multiple Protocol Auxiliary Modulating Hot Water/Steam Heating Reheat Page Aquazone Deluxe D Control LED Indica Complete C Control LED Code Fault DescriptionsComplete C and Deluxe D Board System Test ESD ServiceDescription Status LED Test LED ’ to 4’ Refrigerant ChargingAir Coil Fan Motor Removal A50-8163 TroubleshootingReplacing the Wshp Open Controller’s Bat Reduced or no airflow in heat TroubleshootingAir temperature out of range Cooling mode FP1125 F orReduced airflow in cooling Reduced or no water flowSensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Test Appendix a Wshp Screen Open ConfigurationService Screen Name Configuration ServicePoint Name Password Editable Range Default Level Alarm Page Copyright 2009 Carrier Corporation II. START-UP 50PCH,PCV START-UP ChecklistA50-8446 Heating Cycle AnalysisCooling Cycle Analysis A50-8445

PCV015-060 specifications

The Carrier PCV015-060 is a cutting-edge packaged cooling and heating unit designed for commercial applications that demand high efficiency, reliability, and adaptability. This model is particularly renowned for its robust performance, making it an ideal choice for businesses seeking optimal indoor climate control.

One of the standout features of the PCV015-060 is its impressive energy efficiency. Equipped with advanced scroll compressors, this unit operates with a higher energy efficiency ratio (EER), translating to lower operational costs and reduced environmental impact. The incorporation of eco-friendly refrigerants further bolsters its sustainability credentials, ensuring compliance with modern environmental regulations.

The PCV015-060 showcases superior airflow design, which minimizes noise levels while maximizing thermal comfort. Its high-efficiency evaporator and condenser coils facilitate enhanced heat transfer, ensuring effective cooling and heating performance even in extreme weather conditions. This model is also designed with multiple fan speed options, allowing users to customize air distribution according to specific requirements.

Built with user-friendly controls, the Carrier PCV015-060 supports advanced digital thermostat interfaces, enabling precise temperature management. Optional integration with building management systems allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance tasks.

Durability is another hallmark of the PCV015-060. The unit is constructed using high-quality materials designed to withstand varying environmental conditions, which enhances the lifespan of the system. Additionally, its modular design simplifies installation and service access, reducing downtime for businesses.

The versatility of the PCV015-060 is underscored by its capability to function effectively in numerous configurations, including rooftop installations and ground-mounted setups. It can efficiently handle diverse applications, from offices to retail spaces, making it an adaptable choice for many commercial needs.

In summary, the Carrier PCV015-060 offers a blend of energy efficiency, advanced technology, and durable construction, making it a formidable solution for businesses seeking reliable climate control. Its commitment to sustainability, user-friendly features, and versatile configurations solidify its standing as a premier choice for commercial heating and cooling needs. With the PCV015-060, businesses can ensure a comfortable environment for both employees and customers while maintaining operational efficiency.